WATER TEMPERATURE SENSOR INSTALLATION

DOMESTIC HOT WATER INSTALLATIONS

Y-Series Controller

Fig. # 9497.1

Air temperature sensor must be installed across air temperature sensor contacts. The sensor is not activated and can be left stored in controller enclosure.

DOMESTIC HOT WATER APPLICATION SETUP PROCEDURE

1.Install a 10,000 Ohm, 1/8 Watt resistor between pins 1 and 2 on P2 connector (see pg. 13), in place of the Outdoor Air Temperature Sensor. The Outdoor Air Temperature will appear to be about 77°F.

2.Set switch #2 (Outdoor Reset) to ON - 70°F Defeat, on S3. (See pg.s 15 and 23-24.)

3.Set the Outdoor Cutoff Temperature to 200°F. (See pg. 21.)

4.Adjust the Set Point to desired domestic hot water temperature. Controller will track the Set Point Temperature. (See pg. 22.)

NOTE: The Outdoor Air Temperature sensor can be used as a replacement for the Water Temperature Sensor. Both sensors are identical.

11

Image 11
Contents Electronic Boiler Sequencer & Outdoor Reset Controller Series Electronic Boiler Control Installation and Operating InstructionsTable of Contents Basics Important Safety InstructionsConcept of Operation Optional ConfigurationsIntroduction Standard Indicator Lights Control FeaturesInstall Conduit AS Appropriate Installation and MountingMechanical Installation Electrical InstallationCheckyourpowersource Wiring Power Source to ControllerOutdoor AIR Temperature Sensor AIR Temperature SensorTypical Water Sensor Water Temperature Sensor InstallationHydronic Installations Domestic HOT Water Application Setup Procedure Domestic HOT Water InstallationsPool Heating Installations Single-Stage On/Off Boilers Field WiringPower Test Installation Verification ProcedureControl Familiarization Manual Override Sequence of OperationSeries Electronic Boiler Control Module Indicator Lights Control Functions Reset RatioPump TURN-OFF Delay Reset Ratio ChartOutdoor Cutoff Deadband Stage TURN-ON DelayOutdoor Cutoff Temperature Control BandSET Point Maximum Water TemperatureCircuit Board Auto Interior Jumper & SwitchesOutput Override SlaveDHW Manual LEAD-LAGDigital Display Option Optional ControlsNight Setback Option Call OUT Description Replacement Parts ListInterior Jumper & Switch Settings System START-UP SettingsSystem Setting Entered on Date OFF Troubleshooting GuideLimited Warranty Litho in U.S.A