MAXIMUM WATER TEMPERATURE

The Maximum Output Temperature is the system output high limit. This potentiometer sets the maximum value the Target Temperature is allowed to reach regardless of other operational settings or conditions.

The Maximum Water Temperature range is from 70°F to 235°F. Recommended Initial Setting for Maximum Water Temperature is 180°F.

SET POINT

The Set Point is the system output temperature desired when the outdoor temperature is 70°F. This potentiometer may be set to any temperature from 40°F to 220°F, and is the base-line setting for all operations. Note: Set Point cannot be below 105°F in normal operation unless the No Min Set Point switch is in the ON position. (See Mode Selector Switch). In domestic water supply applications, Set Point determines the water tem- perature maintained by the control.

The Set Point range is from 40°F to 220°F. Recommended Initial Setting Set for Point is 120°F.

CAUTION: Setting the Set Point below 105°F may cause the boiler to condense which will damage the boiler.

22

Image 22
Contents Electronic Boiler Sequencer & Outdoor Reset Controller Installation and Operating Instructions Series Electronic Boiler ControlTable of Contents Important Safety Instructions BasicsIntroduction Optional ConfigurationsConcept of Operation Control Features Standard Indicator LightsElectrical Installation Installation and MountingMechanical Installation Install Conduit AS AppropriateWiring Power Source to Controller CheckyourpowersourceAIR Temperature Sensor Outdoor AIR Temperature SensorHydronic Installations Water Temperature Sensor InstallationTypical Water Sensor Domestic HOT Water Installations Domestic HOT Water Application Setup ProcedurePool Heating Installations Field Wiring Single-Stage On/Off BoilersInstallation Verification Procedure Power TestControl Familiarization Sequence of Operation Manual OverrideSeries Electronic Boiler Control Module Indicator Lights Reset Ratio Control FunctionsReset Ratio Chart Pump TURN-OFF DelayControl Band Stage TURN-ON DelayOutdoor Cutoff Temperature Outdoor Cutoff DeadbandMaximum Water Temperature SET PointCircuit Board Interior Jumper & Switches AutoManual LEAD-LAG SlaveDHW Output OverrideNight Setback Option Optional ControlsDigital Display Option Replacement Parts List Call OUT DescriptionSystem Setting Entered on Date System START-UP SettingsInterior Jumper & Switch Settings Troubleshooting Guide OFFLimited Warranty Litho in U.S.A