Raypak 240692 manual Wiring Power Source to Controller, Checkyourpowersource

Page 8

CHECKYOURPOWERSOURCE

Using a volt-ohm meter, check the following voltages at the circuit breaker panel:

BLACK CIRCUIT

BREAKER

WHITE

GREEN

GROUND

A B C

AC = 108 Volts AC Minimum, 132 Volts MAX AB = 108 Volts AC Minimum, 132 Volts MAX BC = Must be less than 1.0 Volts AC

VOLT-OHM

METER

WIRING: POWER SOURCE TO CONTROLLER

Observe polarity.

Observe proper wire colors while making electrical connections.

Provide an external surge suppressor capable of maintaining system integrity.

Provide overload protection and a disconnect means for equipment serviceability as required by local and state code.

Conduit cannot be used as the ground. (There must be a “WIRED” ground.)

Very Important: A grounding electrode conductor shall be used to connect the equipment grounding conductors, the equipment enclosures, and where the system is grounded, the grounded service conductor to the grounding electrode.

GRN

120VAC

HOT

WHT

RTN

SUPPLY

 

GND

 

 

BLK

 

 

 

 

GRN

 

 

WHT

 

 

BLK

SPG

SINGLE POINT

GROUND

8

Image 8
Contents Electronic Boiler Sequencer & Outdoor Reset Controller Installation and Operating Instructions Series Electronic Boiler ControlTable of Contents Important Safety Instructions BasicsConcept of Operation Optional ConfigurationsIntroduction Control Features Standard Indicator LightsInstallation and Mounting Mechanical InstallationElectrical Installation Install Conduit AS AppropriateWiring Power Source to Controller CheckyourpowersourceAIR Temperature Sensor Outdoor AIR Temperature SensorTypical Water Sensor Water Temperature Sensor InstallationHydronic Installations Domestic HOT Water Installations Domestic HOT Water Application Setup ProcedurePool Heating Installations Field Wiring Single-Stage On/Off BoilersInstallation Verification Procedure Power TestControl Familiarization Sequence of Operation Manual OverrideSeries Electronic Boiler Control Module Indicator Lights Reset Ratio Control FunctionsReset Ratio Chart Pump TURN-OFF DelayStage TURN-ON Delay Outdoor Cutoff TemperatureControl Band Outdoor Cutoff DeadbandMaximum Water Temperature SET PointCircuit Board Interior Jumper & Switches AutoSlave DHWManual LEAD-LAG Output OverrideDigital Display Option Optional ControlsNight Setback Option Replacement Parts List Call OUT DescriptionInterior Jumper & Switch Settings System START-UP SettingsSystem Setting Entered on Date Troubleshooting Guide OFFLimited Warranty Litho in U.S.A