FIELD WIRING
Single-Stage (On/Off) Boilers
-All stage connections on the control board are connected at the {TH} (Thermostat) location on the boiler wiring diagram.
Multiple-Stage Boilers
-First stage connections on the control board are connected at the {TH} (Thermostat) location on the boiler wiring diagram.
-Second (or third, etc.) stage connections on the control board are connected at the locations shown on the boiler wiring diagram.
Utilize Shielded Cable
Outdoor Air Temperature
Sensor (see NOTE 4)
Water Temperature
Sensor
P5
Stage 1
Stage 2
Stage 3
Stage 4
Stage 5 |
|
Stage 6 |
|
Stage 7 |
|
Stage 8 |
|
| P6 |
Pump Relay |
|
Pilot Duty Only |
|
2.5 Amp Max | P4 |
250V Max |
|
Thermostat |
|
(Jumpered) or |
|
Building Management System | P1 |
Outdoor Temp |
|
Water Temp |
|
| P2 |
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
1
2
3
1
2
3
4
Notes:
1.Tighten terminal strip clamping screws to 4
2.Use copper conductors only.
3.For supply connections, use wires sized on the basis of 60°C (140°F) ampacity and rated a min. 90°C (194°F).
4.The outdoor sensor must be connected, otherwise a sensor error will be displayed.
13