CONTROL FEATURES
The
•Standard Indicator Lights:
Stages 1 to 8: Red, indicates which stages are turned on.
Pump: | Green, indicates that the pump circuit is energized. |
Call for Heat: | Green, indicates that a call for heat signal is present. |
Control On: | Green, indicates outdoor temperature is below the Outdoor Cutoff Temperature |
| potentiometer setting and that the boiler will respond to a call for heat. |
Setting Error: | Red, indicates one or more of the |
Sensor Error: | Red, indicates that the Water or Outdoor Temperature Sensor has an |
•Adjustment Knobs:
| Reset Ratio: | 0.12:1 to 8:1; determines how much the |
|
| Temperature will change for a given outdoor temperature change. |
| Control Band: | 1°F to 10°F; the temperature above or below the Target Temperature at which the boiler |
|
| turns off and on. |
| Pump Off Delay: | 0 to 10 min.; determines when the pump shuts off after entering Outdoor Cutoff mode. |
. | Outdoor Cutoff | 32°F to 200°F; a warm weather shutdown feature. When the outdoor temperature |
| Temperature: | exceeds this setting, the boiler will not fire unless placed in manual override mode. |
| Outdoor Cutoff | 1°F to 10°F; the number of degrees below the Outdoor Cutoff (O/C) |
| Deadband: | Temperature which causes the O/C to reset. |
| Boiler On Delay: | 0 to 5 min.; sets the time interval between sequential boiler start ups. |
| Stage On Delay: | 0 to 60 sec.; determines the time delay between stages turning on. |
| Max. Water Temp.: | 70°F to 235°F; the maximum value that the Target Temperature is allowed to reach. |
| Set Point: | 40°F to 220°F; the system output temperature desired when the outdoor temperature is |
|
| 70°F or, in domestic water applications, the desired water temperature. |
•Logic Test Button, Jumper and Switches:
System Test Button (S1): | initiates micro self test which causes the status indicator lights to blink 5 times |
| indicating the |
Last Stage Jumper (J2): | selects the last active stage used for boiler control. |
First Stage #1 Selector (S2): | designates the first stage of each boiler in a |
| position #1 should always be on. |
Mode Selector (S3): | switch #1 selects either Manual or Auto |
| Outdoor Reset defeat. Switch #3 configures the |
| operation. Switch #4 allows the Set Point to be set below 105°F. |
Bypass Switches (S5): | allows user to turn on any stage(s) regardless of current settings and |
| conditions if, and only if, the pump relay is already activated. |
6