Raypak 5042004 operating instructions VDC 20 mA Boiler Target, Mode 3 Dedicated DHW

Page 32

ELECTRONIC

trol operates the boiler burner to maintain the boiler target at the boiler outlet sensor.

Mode 7 – Designed for an external input signal with primary/secondary piping. The external input signal can be provided from a BMS, an EMS or an external control. The external input signal changes the boiler target according to a linear scale (see Tables O & P). The control operates the boiler burner to maintain the boiler target at the system sensor. See Fig. 35.

Fig. 33: Mode 3 Dedicated DHW

Mode 4 (Not supported) – Outdoor reset using pri- mary piping. The heater is operated as in Mode 1. However, the target temperature is based on outdoor reset.

Mode 5 – Outdoor reset using primary/secondary pip- ing. The heater is operated as in Mode 2. However, the target temperature is based on outdoor reset. See Fig. 34.

*Maximum 4 times the pipe diameter* or 12”, whichever is less.

Fig. 34: Mode 5 Primary/Secondary Piping with

Outdoor Reset

Mode 6 (Not supported) – Designed for an external input signal with primary piping. The external input sig- nal can be provided from a BMS, an EMS or a sequencing control. The external input signal changes the boiler target according to a linear scale. The con-

 

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Maximum 4 times the pipe diameter or 12”, whichever is less.

Fig. 35: Mode 7 Primary/Secondary Piping with

 

External Target Temp

 

 

 

 

 

 

 

 

 

 

 

0-10 VDC

 

 

0-20 mA*

Boiler Target

0

0

 

 

--- (OFF)

1

2

 

 

 

50°F

2

4

 

 

68.9°F

3

6

 

 

87.8°F

4

8

 

 

106.7°F

5

10

 

 

125.6°F

6

12

 

 

144.1°F

7

14

 

 

163.3°F

8

16

 

 

182.2°F

9

18

 

 

201.1°F

10

20

 

 

220°F

*Requires a 500Ω resistor.

Table O: 0-10 VDC or 0-20 mA External Input Signal

32

Image 32
Contents Do so may result in an explosion or fire Reference Catalog no .54E Effective Replaces 241317 RevPage Contents Pay Attention to These Terms Before Installation Installations at ElevationProduct Receipt Model IdentificationComponent Locations General InformationWater Time to Produce Serious Temp Burn General SafetyTime/Temperature Relationships in Scalds Installation Installation CodesIndoor Installations Equipment BaseIndoor Units Outdoor InstallationsCombustion and Ventilation Air Table E Vent/Air Inlet Termination Clearances Installations Conventional Combustion Air SupplyAir Filter Direct VentGeneral Canadian InstallationsWater Piping Cold Water Operation Relief Valve Piping Temperature & Pressure GaugeHydrostatic Test Hydronic Heating Pump SelectionFeedwater Regulator Cold Water StartsPiping Air-Separation/Expansion TankModel Input Output 20 ∆T 30 ∆T 40 ∆T Min. Flow GpmThree-Way Valves Domestic Hot WaterPotable Water and Space Heating Pool HeatingPool heating application. Use the following instruc Exceed 5 ppm Pool/Spa Water ChemistryWinterizing Your Heater Gas Supply Gas Supply ConnectionGas Supply Pressure Automatic Chlorinators Chemical FeedersElectrical Power Connections Model In. NPT 4 in. NPT 2 in. NPTModel Manifold Gas Pressure High Fire ValuesMaking the Electrical Connections Check the Power SourceField-Connected Controllers Appliance Categories Field Wiring ConnectionVenting Vent Terminal Location InstallationsSupport of Vent Stack Venting Installation Tips Venting ConfigurationsCanadian Installations InstallationMax. Length* ft Min10 Ø TerminationCommon Venting Typical Common VentingHorizontal Through-the-Wall Direct Venting Category Model Vent Size Volume Flue ProductsEngineered Vent Systems Direct Vent-Vertical Horizontal Through-the-Wall Direct VentingCombustion Air Air Inlet Horizontal Max. Length** ft Vent Outdoor InstallationModel Certified Controls Freeze ProtectionOperating Modes Differential GraphMode 3 Dedicated DHW 10 VDC 20 mA Boiler TargetDefinitions 10 VDC 20 mABoiler H7 Modes Default Setting Pool Heater P, WHP Modes Default Setting RangeWater Heater WH1 Modes Default Setting Range Rank Number Field Type Fault DescriptionOperation High Limit-Manual Reset Heater Sequence of OperationIgnition Module Code ConditionHigh Limit-Auto Reset Optional Flow SwitchModulating Temperature Control High & Low Gas Pressure Switches OptionalUDB Diagnostic Board Blocked Vent SwitchAir Pressure Switch Wiring Diagram Models H & WH Wiring Diagram Models P & WHP START-UP Pre Start-upPre Start-up Check Initial Start-upStart-Up Blower CheckSafety Inspection FinishingManifold Check Follow-UpLeak Test Procedure Dual-Seat Gas Valve Post Start-Up CheckOperation Lighting InstructionsUDB Fault History To Turn Off Gas To ApplianceTroubleshooting StepPreventive Maintenance Schedule MaintenanceSuggested Minimum Maintenance Schedule Filter Maintenance WeeklySemi-Annually AnnuallyInside Air Contamination Filter ReplacementAppendix Important Instructions for the Commonwealth of Massachusetts Limited Parts Warranty MVB Types H and WH Limited Parts Warranty MVB Types P & WHP START-UP Checklist for FAN-ASSISTED Raypak Products Nominal Factory Recommended Settings

5042004 specifications

The Raypak 5042004 is a highly efficient pool heater designed for residential and commercial applications, providing warmth and comfort for swimming pools and spas. It is a part of Raypak's extensive lineup of pool heating solutions, known for their reliability and energy efficiency. This model caters to different heating needs while maximizing performance and reducing energy consumption.

One of the standout features of the Raypak 5042004 is its use of advanced heat exchanger technology. Constructed with a durable copper fin design, the heat exchanger enhances thermal conductivity, allowing the unit to heat water quickly and effectively. This ensures a consistently enjoyable swimming experience, even in cooler weather conditions. The heater’s aluminum cabinet is designed to withstand harsh weather and resist corrosion, increasing its longevity and reliability.

In addition to its robust construction, the Raypak 5042004 incorporates a user-friendly digital control system. This control system allows users to set their desired temperature with precision, enabling easy adjustments and enhanced control over the heating process. The digital display provides real-time feedback, giving users insight into the system's operation and current water temperature.

Moreover, this model offers a specialized environmentally friendly option. The Raypak 5042004 is designed to run efficiently on both natural gas and propane, which provides flexibility regarding fuel choice based on availability and personal preference. This versatility is paired with low NOx (nitric oxide) emissions, making it compliant with stringent environmental regulations, making it an eco-friendly choice for consumers.

The ease of installation is another characteristic that sets the Raypak 5042004 apart from its competitors. The unit includes versatile piping options and integrated automation features that facilitate quick and hassle-free installation, ultimately saving time and effort for both professional installers and DIY enthusiasts.

In summary, the Raypak 5042004 is a cutting-edge pool heater that combines high efficiency, robust construction, user-friendly controls, and eco-friendly features. Its advanced heating technologies, durable design, and versatile fuel options make it an excellent choice for anyone looking to enhance their swimming experience year-round while being conscious of energy consumption and environmental impact.