Air Filter

An air filter is supplied standard with the heater. This filter is shipped loose for field installation. Refer to the Air Filter Kit Installation Instructions (Part No. 241338) for details.

Fig. 8: Air Filter Box

Direct Vent

If outside air is drawn through the intake pipe directly to the unit for combustion:

1.Install combustion air direct vent in accordance with Fig. 27 (horizontal) or Fig. 28 (vertical) of this manual (pages 28 and 29, respectively).

2.Provide adequate ventilation of the space occu- pied by the heater( s) by an opening (s) for ventilation air at the highest practical point com- municating with the outdoors. The total cross-sectional area shall be at least 1 in.2 of free area per 20,000 BTUH (111 mm2 per kW) of total input rating of all equipment in the room when the opening is communicating directly with the out- doors or through vertical duct(s). The total cross-sectional area shall be at least 1 in.2 of free area per 10,000 BTUH (222 mm2 per kW) of total input rating of all equipment in the room when the opening is communicating with the outdoors through horizontal duct(s).

3.In cold climates, and to mitigate potential freeze- up, Raypak highly recommends the installation of a motorized sealed damper to prevent the circula- tion of cold air through the heater during the non-operating hours.

TruSeal™ Combustion Air

In addition to the 3 previous steps, combustion air may be ducted directly to the heater by using PVC, CPVC

or sealed single-wall galvanized ducting. The duct will attach directly to the air collar located on the rear of the heater, using three or four sheet metal screws (not supplied) equally positioned around the circumference of the duct. The screen assembly should be removed before attaching any air duct to the heater. The screws and duct connection point must be sealed with RTV (not supplied). TruSeal is generally used when dam- aging contaminants are present in the mechanical room.

All ducting must be self-supported.

CAUTION: Use TruSeal combustion air if damaging airborne contaminants are or may be present in the heater area. See the Appendix of this manual regarding air contamination.

Conventional Combustion Air Supply

U.S. Installations

All Air from Inside the Building

The confined space shall be provided with TWO per- manent openings communicating directly with an additional room(s) of sufficient volume so that the com- bined volume of all spaces meets the criteria for a room large in comparison (NFGC). The total input of all gas utilization equipment installed in the combined space shall be considered in making this determina- tion. Each opening shall have a minimum free area of 1 in.2 per 1,000 BTUH (2,225 mm2 per kW) of the total input rating of all gas utilization equipment in the con- fined space, but not less than 100 in.2 (645 cm2). One opening shall commence within 12 in. (305 mm) of the top, and one opening shall commence within 12 in. (305 mm) of the bottom of the enclosure. The mini- mum dimension of air openings shall be not less than 3 in. (76 mm) in any direction.

All Air from Outdoors

The confined space shall communicate with the out- doors in accordance with one of the methods below. The minimum dimension of air openings shall not be less than 3 in. (76 mm) in any direction. Where ducts are used, they shall be of the same cross-sectional area as the net free area of the openings to which they connect.

1.Two permanent openings, one commencing within 12 in. (305 mm) of the top, and one com- mencing within 12 in. (305 mm) of the bottom of

11

Image 11
Contents Reference Catalog no .54E Effective Replaces 241317 Rev Do so may result in an explosion or firePage Contents Pay Attention to These Terms Model Identification Before InstallationInstallations at Elevation Product ReceiptGeneral Information Component LocationsWater Time to Produce Serious Temp Burn General SafetyTime/Temperature Relationships in Scalds Equipment Base InstallationInstallation Codes Indoor InstallationsIndoor Units Outdoor InstallationsCombustion and Ventilation Air Table E Vent/Air Inlet Termination Clearances Direct Vent InstallationsConventional Combustion Air Supply Air FilterGeneral Canadian InstallationsWater Piping Cold Water Operation Relief Valve Piping Temperature & Pressure GaugeHydrostatic Test Cold Water Starts Hydronic HeatingPump Selection Feedwater RegulatorGpm PipingAir-Separation/Expansion Tank Model Input Output 20 ∆T 30 ∆T 40 ∆T Min. FlowPool Heating Three-Way ValvesDomestic Hot Water Potable Water and Space HeatingPool heating application. Use the following instruc Exceed 5 ppm Pool/Spa Water ChemistryWinterizing Your Heater Automatic Chlorinators Chemical Feeders Gas SupplyGas Supply Connection Gas Supply PressureHigh Fire Values Electrical Power ConnectionsModel In. NPT 4 in. NPT 2 in. NPT Model Manifold Gas PressureMaking the Electrical Connections Check the Power SourceField-Connected Controllers Appliance Categories Field Wiring ConnectionVenting Vent Terminal Location InstallationsSupport of Vent Stack Installation Venting Installation TipsVenting Configurations Canadian InstallationsTermination Max. Length* ftMin 10 ØTypical Common Venting Common VentingHorizontal Through-the-Wall Direct Venting Category Model Vent Size Volume Flue ProductsEngineered Vent Systems Horizontal Through-the-Wall Direct Venting Direct Vent-VerticalCombustion Air Air Inlet Horizontal Max. Length** ft Vent Outdoor InstallationModel Certified Freeze Protection ControlsDifferential Graph Operating Modes10 VDC 20 mA Boiler Target Mode 3 Dedicated DHW10 VDC 20 mA DefinitionsPool Heater P, WHP Modes Default Setting Range Boiler H7 Modes Default SettingWater Heater WH1 Modes Default Setting Range Rank Number Field Type Fault DescriptionOperation Code Condition High Limit-Manual ResetHeater Sequence of Operation Ignition ModuleHigh & Low Gas Pressure Switches Optional High Limit-Auto Reset OptionalFlow Switch Modulating Temperature ControlUDB Diagnostic Board Blocked Vent SwitchAir Pressure Switch Wiring Diagram Models H & WH Wiring Diagram Models P & WHP Initial Start-up START-UPPre Start-up Pre Start-up CheckBlower Check Start-UpFollow-Up Safety InspectionFinishing Manifold CheckPost Start-Up Check Leak Test Procedure Dual-Seat Gas ValveLighting Instructions OperationTo Turn Off Gas To Appliance UDB Fault HistoryStep TroubleshootingPreventive Maintenance Schedule MaintenanceSuggested Minimum Maintenance Schedule Annually Filter MaintenanceWeekly Semi-AnnuallyInside Air Contamination Filter ReplacementAppendix Important Instructions for the Commonwealth of Massachusetts Limited Parts Warranty MVB Types H and WH Limited Parts Warranty MVB Types P & WHP Nominal Factory Recommended Settings START-UP Checklist for FAN-ASSISTED Raypak Products

5042004 specifications

The Raypak 5042004 is a highly efficient pool heater designed for residential and commercial applications, providing warmth and comfort for swimming pools and spas. It is a part of Raypak's extensive lineup of pool heating solutions, known for their reliability and energy efficiency. This model caters to different heating needs while maximizing performance and reducing energy consumption.

One of the standout features of the Raypak 5042004 is its use of advanced heat exchanger technology. Constructed with a durable copper fin design, the heat exchanger enhances thermal conductivity, allowing the unit to heat water quickly and effectively. This ensures a consistently enjoyable swimming experience, even in cooler weather conditions. The heater’s aluminum cabinet is designed to withstand harsh weather and resist corrosion, increasing its longevity and reliability.

In addition to its robust construction, the Raypak 5042004 incorporates a user-friendly digital control system. This control system allows users to set their desired temperature with precision, enabling easy adjustments and enhanced control over the heating process. The digital display provides real-time feedback, giving users insight into the system's operation and current water temperature.

Moreover, this model offers a specialized environmentally friendly option. The Raypak 5042004 is designed to run efficiently on both natural gas and propane, which provides flexibility regarding fuel choice based on availability and personal preference. This versatility is paired with low NOx (nitric oxide) emissions, making it compliant with stringent environmental regulations, making it an eco-friendly choice for consumers.

The ease of installation is another characteristic that sets the Raypak 5042004 apart from its competitors. The unit includes versatile piping options and integrated automation features that facilitate quick and hassle-free installation, ultimately saving time and effort for both professional installers and DIY enthusiasts.

In summary, the Raypak 5042004 is a cutting-edge pool heater that combines high efficiency, robust construction, user-friendly controls, and eco-friendly features. Its advanced heating technologies, durable design, and versatile fuel options make it an excellent choice for anyone looking to enhance their swimming experience year-round while being conscious of energy consumption and environmental impact.