Raypak 5042004 operating instructions Water Piping, Canadian Installations, General

Page 12

the enclosure, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely com- municate with the outdoors.

a.Where directly communicating with the out- doors or where communicating to the outdoors through vertical ducts, each open- ing shall have a minimum free area of 1 in.2 per 4,000 BTUH (550 mm2 per kW) of total input rating of all equipment in the enclosure.

b.Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 in.2 per 2,000 BTUH (1,100 mm2 per kW) of total input rat- ing of all equipment in the enclosure.

2.One permanent opening, commencing within 12 in. (305 mm) of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (152 mm) from the front of the appliance. The opening shall directly communicate with the out- doors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors, and shall have a minimum free area of:

a.1 in.2 per 3,000 BTUH (740 mm2 per kW) of the total input rating of all equipment located in the enclosure, and

b.Not less than the sum of the areas of all vent connectors in the confined space.

WARNING: Do not use the “one permanent opening” method if the equipment room is under negative pressure conditions.

Canadian Installations

CAUTION: All combustion air must be drawn from outside of the building; the mechanical equipment room must communicate directly with the outdoors.

1. Ventilation of the space occupied by the heater shall be provided by an opening(s) for ventilation air at the highest practical point communicating with the outdoors. The total cross-sectional area of such an opening(s) shall be at least 10% of the area required in 2. and 3. (below), but in no case shall the cross-sectional area be less than 10 in.2 (65 cm2).

12

2.For heaters using a barometric damper in the vent system there shall be a permanent air supply opening(s) having a cross section area of not less than 1 in.2 per 7,000 BTUH (320 mm2 per kW) up to and including 1 million BTUH, plus 1 in.2 per 14,000 BTUH (160 mm2 per kW) in excess of 1 million BTUH. This opening(s) shall be either located at or ducted to a point not more than 18 in. (450 mm) nor less than 6 in. (152 mm) above the floor level. The duct can also “goose neck” through the roof. The duct is preferred to be straight down and terminated 18 in. (450 mm) from the floor, but not near piping. This air supply opening require- ment shall be in addition to the air opening for ventilation air required in 1. (above).

WARNING: Care must be taken to ensure that the equipment room is not under negative pressure conditions.

3.For heaters not using a barometric damper in the vent system, and when air supply is provided by natural air flow from outdoors for a power burner and there is no draft regulator, drafthood or similar flue gas dilution device installed in the same space, in addition to the opening for ventilation air required in 1., there shall be a permanent air sup- ply opening(s) having a total cross-sectional area of not less than 1 in.2 for each 30,000 BTUH (74 mm2 per kW) of total rated input of the burner(s), and the location of the opening(s) shall not inter- fere with the intended purpose of the opening(s) for ventilation air referred to in 1. This opening(s) can be ducted to a point not more than 18 in. (450 mm) nor less than 6 in. (152 mm) above the floor level. The duct can also “goose neck” through the roof. The duct is preferred to be straight down 18 in. (450 mm) from the floor, but not near piping.

4.Refer to the B149 Installation Code for additional information.

Water Piping

General

The heater should be located so that any water leaks will not cause damage to the adjacent area or struc- tures.

NOTE: In lieu of installing the System Temp Sensor in the system return loop, an alternate system using a buffer tank (see Fig. 31) can be used for better sys- tem temperature control.

Image 12
Contents Do so may result in an explosion or fire Reference Catalog no .54E Effective Replaces 241317 RevPage Contents Pay Attention to These Terms Before Installation Installations at ElevationProduct Receipt Model IdentificationComponent Locations General InformationGeneral Safety Time/Temperature Relationships in ScaldsWater Time to Produce Serious Temp Burn Installation Installation CodesIndoor Installations Equipment BaseOutdoor Installations Combustion and Ventilation AirIndoor Units Table E Vent/Air Inlet Termination Clearances Installations Conventional Combustion Air SupplyAir Filter Direct VentCanadian Installations Water PipingGeneral Relief Valve Piping Temperature & Pressure Gauge Hydrostatic TestCold Water Operation Hydronic Heating Pump SelectionFeedwater Regulator Cold Water StartsPiping Air-Separation/Expansion TankModel Input Output 20 ∆T 30 ∆T 40 ∆T Min. Flow GpmThree-Way Valves Domestic Hot WaterPotable Water and Space Heating Pool HeatingPool heating application. Use the following instruc Pool/Spa Water Chemistry Winterizing Your HeaterExceed 5 ppm Gas Supply Gas Supply ConnectionGas Supply Pressure Automatic Chlorinators Chemical FeedersElectrical Power Connections Model In. NPT 4 in. NPT 2 in. NPTModel Manifold Gas Pressure High Fire ValuesCheck the Power Source Field-Connected ControllersMaking the Electrical Connections Field Wiring Connection VentingAppliance Categories Installations Support of Vent StackVent Terminal Location Venting Installation Tips Venting ConfigurationsCanadian Installations InstallationMax. Length* ft Min10 Ø TerminationCommon Venting Typical Common VentingModel Vent Size Volume Flue Products Engineered Vent SystemsHorizontal Through-the-Wall Direct Venting Category Direct Vent-Vertical Horizontal Through-the-Wall Direct VentingOutdoor Installation Model CertifiedCombustion Air Air Inlet Horizontal Max. Length** ft Vent Controls Freeze ProtectionOperating Modes Differential GraphMode 3 Dedicated DHW 10 VDC 20 mA Boiler TargetDefinitions 10 VDC 20 mABoiler H7 Modes Default Setting Pool Heater P, WHP Modes Default Setting RangeWater Heater WH1 Modes Default Setting Range Number Field Type Fault Description OperationRank High Limit-Manual Reset Heater Sequence of OperationIgnition Module Code ConditionHigh Limit-Auto Reset Optional Flow SwitchModulating Temperature Control High & Low Gas Pressure Switches OptionalBlocked Vent Switch Air Pressure SwitchUDB Diagnostic Board Wiring Diagram Models H & WH Wiring Diagram Models P & WHP START-UP Pre Start-upPre Start-up Check Initial Start-upStart-Up Blower CheckSafety Inspection FinishingManifold Check Follow-UpLeak Test Procedure Dual-Seat Gas Valve Post Start-Up CheckOperation Lighting InstructionsUDB Fault History To Turn Off Gas To ApplianceTroubleshooting StepMaintenance Suggested Minimum Maintenance SchedulePreventive Maintenance Schedule Filter Maintenance WeeklySemi-Annually AnnuallyFilter Replacement AppendixInside Air Contamination Important Instructions for the Commonwealth of Massachusetts Limited Parts Warranty MVB Types H and WH Limited Parts Warranty MVB Types P & WHP START-UP Checklist for FAN-ASSISTED Raypak Products Nominal Factory Recommended Settings

5042004 specifications

The Raypak 5042004 is a highly efficient pool heater designed for residential and commercial applications, providing warmth and comfort for swimming pools and spas. It is a part of Raypak's extensive lineup of pool heating solutions, known for their reliability and energy efficiency. This model caters to different heating needs while maximizing performance and reducing energy consumption.

One of the standout features of the Raypak 5042004 is its use of advanced heat exchanger technology. Constructed with a durable copper fin design, the heat exchanger enhances thermal conductivity, allowing the unit to heat water quickly and effectively. This ensures a consistently enjoyable swimming experience, even in cooler weather conditions. The heater’s aluminum cabinet is designed to withstand harsh weather and resist corrosion, increasing its longevity and reliability.

In addition to its robust construction, the Raypak 5042004 incorporates a user-friendly digital control system. This control system allows users to set their desired temperature with precision, enabling easy adjustments and enhanced control over the heating process. The digital display provides real-time feedback, giving users insight into the system's operation and current water temperature.

Moreover, this model offers a specialized environmentally friendly option. The Raypak 5042004 is designed to run efficiently on both natural gas and propane, which provides flexibility regarding fuel choice based on availability and personal preference. This versatility is paired with low NOx (nitric oxide) emissions, making it compliant with stringent environmental regulations, making it an eco-friendly choice for consumers.

The ease of installation is another characteristic that sets the Raypak 5042004 apart from its competitors. The unit includes versatile piping options and integrated automation features that facilitate quick and hassle-free installation, ultimately saving time and effort for both professional installers and DIY enthusiasts.

In summary, the Raypak 5042004 is a cutting-edge pool heater that combines high efficiency, robust construction, user-friendly controls, and eco-friendly features. Its advanced heating technologies, durable design, and versatile fuel options make it an excellent choice for anyone looking to enhance their swimming experience year-round while being conscious of energy consumption and environmental impact.