Raypak 5042004 Combustion and Ventilation Air, Outdoor Installations, Indoor Units

Page 9

Venting not shown for clarity. Heater must be vented per instruc-

tions in this manual

Fig. 6: Minimum Clearances from Combustible Surfaces – Indoor and Outdoor Installations

serviced in its installed location without movement or removal of the heater.

Service clearances less than the minimum may require removal of the heater to service either the heat exchanger or the burner components. In either case, the heater must be installed in a manner that will enable the heater to be serviced without removing any structure around the heater.

Outdoor Installations

These heaters are design-certified for outdoor installa- tion. Heaters must not be installed under an overhang unless they are in accordance with local installation

9

codes and the requirments of the gas supplier. Three sides must be open in the area under the overhang. Roof water drainage must be diverted away from heaters installed under overhangs.

The combustion air intake terminal MUST be used for outdoor installations. The elbow is shipped loose to be installed on the rear of the heater at the job site.

Heater

Min. Clearance

Minimum

from Combustible

Service

Side

Surfaces

Clearance

Rear

12”

24”

Front

Open

24”

Right Side

1”

1”

Left Side

1”

1”

Top

Unobstructed

10”

Vent

12”

12”

Termination

Table D: Clearances – Outdoor Installations

Combustion and Ventilation Air

NOTE: Use of this heater in construction areas where fine particulate matter, such as concrete or dry-wall dust, is present may result in damage to the heater that is not covered by the warranty. If operated in a construction environment, a clean source of combustion air must be provided directly to the heater.

Indoor Units

This heater must be supplied with sufficient quantities of non-contaminated air to support proper combustion and equipment ventilation. Combustion air can be sup- plied via conventional means where combustion air is drawn from the area immediately surrounding the heater, or via direct vent, where combustion air is drawn directly from outside. All installations must com- ply with the requirements of the NFGC (U.S.) and B149 (Canada), and all local codes.

CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater and void the warranty. (See the Appendix.)

NOTE: It is recommended that the intake vent be insulated to minimize sweating.

Image 9
Contents Reference Catalog no .54E Effective Replaces 241317 Rev Do so may result in an explosion or firePage Contents Pay Attention to These Terms Installations at Elevation Before InstallationProduct Receipt Model IdentificationGeneral Information Component LocationsGeneral Safety Time/Temperature Relationships in ScaldsWater Time to Produce Serious Temp Burn Installation Codes InstallationIndoor Installations Equipment BaseOutdoor Installations Combustion and Ventilation AirIndoor Units Table E Vent/Air Inlet Termination Clearances Conventional Combustion Air Supply InstallationsAir Filter Direct VentCanadian Installations Water PipingGeneral Relief Valve Piping Temperature & Pressure Gauge Hydrostatic TestCold Water Operation Pump Selection Hydronic HeatingFeedwater Regulator Cold Water StartsAir-Separation/Expansion Tank PipingModel Input Output 20 ∆T 30 ∆T 40 ∆T Min. Flow GpmDomestic Hot Water Three-Way ValvesPotable Water and Space Heating Pool HeatingPool heating application. Use the following instruc Pool/Spa Water Chemistry Winterizing Your HeaterExceed 5 ppm Gas Supply Connection Gas SupplyGas Supply Pressure Automatic Chlorinators Chemical FeedersModel In. NPT 4 in. NPT 2 in. NPT Electrical Power ConnectionsModel Manifold Gas Pressure High Fire ValuesCheck the Power Source Field-Connected ControllersMaking the Electrical Connections Field Wiring Connection VentingAppliance Categories Installations Support of Vent StackVent Terminal Location Venting Configurations Venting Installation TipsCanadian Installations InstallationMin Max. Length* ft10 Ø TerminationTypical Common Venting Common VentingModel Vent Size Volume Flue Products Engineered Vent SystemsHorizontal Through-the-Wall Direct Venting Category Horizontal Through-the-Wall Direct Venting Direct Vent-VerticalOutdoor Installation Model CertifiedCombustion Air Air Inlet Horizontal Max. Length** ft Vent Freeze Protection ControlsDifferential Graph Operating Modes10 VDC 20 mA Boiler Target Mode 3 Dedicated DHW10 VDC 20 mA DefinitionsPool Heater P, WHP Modes Default Setting Range Boiler H7 Modes Default SettingWater Heater WH1 Modes Default Setting Range Number Field Type Fault Description OperationRank Heater Sequence of Operation High Limit-Manual ResetIgnition Module Code ConditionFlow Switch High Limit-Auto Reset OptionalModulating Temperature Control High & Low Gas Pressure Switches OptionalBlocked Vent Switch Air Pressure SwitchUDB Diagnostic Board Wiring Diagram Models H & WH Wiring Diagram Models P & WHP Pre Start-up START-UPPre Start-up Check Initial Start-upBlower Check Start-UpFinishing Safety InspectionManifold Check Follow-UpPost Start-Up Check Leak Test Procedure Dual-Seat Gas ValveLighting Instructions OperationTo Turn Off Gas To Appliance UDB Fault HistoryStep TroubleshootingMaintenance Suggested Minimum Maintenance SchedulePreventive Maintenance Schedule Weekly Filter MaintenanceSemi-Annually AnnuallyFilter Replacement AppendixInside Air Contamination Important Instructions for the Commonwealth of Massachusetts Limited Parts Warranty MVB Types H and WH Limited Parts Warranty MVB Types P & WHP Nominal Factory Recommended Settings START-UP Checklist for FAN-ASSISTED Raypak Products

5042004 specifications

The Raypak 5042004 is a highly efficient pool heater designed for residential and commercial applications, providing warmth and comfort for swimming pools and spas. It is a part of Raypak's extensive lineup of pool heating solutions, known for their reliability and energy efficiency. This model caters to different heating needs while maximizing performance and reducing energy consumption.

One of the standout features of the Raypak 5042004 is its use of advanced heat exchanger technology. Constructed with a durable copper fin design, the heat exchanger enhances thermal conductivity, allowing the unit to heat water quickly and effectively. This ensures a consistently enjoyable swimming experience, even in cooler weather conditions. The heater’s aluminum cabinet is designed to withstand harsh weather and resist corrosion, increasing its longevity and reliability.

In addition to its robust construction, the Raypak 5042004 incorporates a user-friendly digital control system. This control system allows users to set their desired temperature with precision, enabling easy adjustments and enhanced control over the heating process. The digital display provides real-time feedback, giving users insight into the system's operation and current water temperature.

Moreover, this model offers a specialized environmentally friendly option. The Raypak 5042004 is designed to run efficiently on both natural gas and propane, which provides flexibility regarding fuel choice based on availability and personal preference. This versatility is paired with low NOx (nitric oxide) emissions, making it compliant with stringent environmental regulations, making it an eco-friendly choice for consumers.

The ease of installation is another characteristic that sets the Raypak 5042004 apart from its competitors. The unit includes versatile piping options and integrated automation features that facilitate quick and hassle-free installation, ultimately saving time and effort for both professional installers and DIY enthusiasts.

In summary, the Raypak 5042004 is a cutting-edge pool heater that combines high efficiency, robust construction, user-friendly controls, and eco-friendly features. Its advanced heating technologies, durable design, and versatile fuel options make it an excellent choice for anyone looking to enhance their swimming experience year-round while being conscious of energy consumption and environmental impact.