Raypak 399B-2339B operating instructions Material Vent Length, Termination

Page 31

 

Certified

 

Maximum

Combustion

 

Air Inlet Max. Length*

 

Model

Vent

Air

 

 

Venting

Equivalent

 

 

 

 

 

 

No.

Size

Intake Pipe

 

 

 

 

 

 

Material

Vent Length*

6”

 

8”

10”

 

12”

 

 

Material

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

399B

 

 

 

 

100’

 

 

 

 

 

 

 

6”

 

 

 

 

 

 

 

 

499B

 

 

 

75’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

649B

 

 

 

 

 

 

100’

 

 

 

 

 

 

 

 

40’

 

 

 

 

 

749B

 

8”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

899B

 

 

 

 

30’

 

80’

 

 

 

 

 

 

70’Room Air

Galvanized

 

 

 

 

 

 

989B

 

10”

 

 

 

 

 

 

Category III

 

Steel,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1259B

 

 

40’ Ducted

PVC, ABS,

 

 

 

75’

 

100’

 

 

Combustion Air

CPVC

 

 

 

 

 

 

12”

 

 

 

 

 

 

1529B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1799B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1999B

 

14”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40’

 

75’

2069B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2339B

 

16”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Subtract 10 ft per elbow. Max. 3 elbows.

Maximum combustion air duct length terminated at 100 equivalent ft.

Table M: Category III Horizontal and Direct Venting

The vent must be installed to prevent flue gas leakage. Care must be taken during assembly to ensure that all joints are sealed properly and are airtight. The vent must be installed to prevent the potential accumulation of condensate in the vent pipes. It is required that:

1.The vent must be installed with a slight downward slope of not more than 1/4 inch per foot of hori- zontal run to the vent terminal.

2.The vent must be insulated through the length of the horizontal run.

For installations in extremely cold climate, it is re- quired that:

1.The vent must be installed with a slight upward slope of not more than 1/4 inch per foot of hori- zontal run to the vent terminal. In this case, an approved condensate trap must be installed per applicable codes.

2.The vent must be insulated through the length of the horizontal run.

Termination

The flue direct vent cap MUST be mounted on the ex- terior of the building. The direct vent cap cannot be installed in a well or below grade. The direct vent cap must be installed at least 1 ft above ground level and above normal snow levels. The Raypak-approved stainless steel flue direct vent cap must be used (sales order option D-15).

WARNING: No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the safety and health of inhabitants.

Use only the special gas vent pipes listed for use with Category III gas burning heaters, such as the AL29-4C stainless steel vents offered by Heat Fab Inc. (800- 772-0739), Protech System, Inc. (800-766-3473), Z-Flex (800-654-5600) or American Metal Products (800-423-4270). Pipe joints must be positively sealed. Follow the vent manufacturer’s installation instructions carefully.

31

Image 31
Contents Installation & Operating Instructions Page Contents Pay Attention to These Terms Model Identification Before InstallationInstallations at Elevation Product ReceiptComponent Locations Back Component LocationsBurners per Valve Stages Fire at Stage General InformationTime/Temperature Relationships in Scalds General SafetyWater Time to Produce Serious Temp Burn Stacking InstallationInstallation Codes Equipment BaseTable D Vent/Air Inlet Termination Clearances Outdoor Installations Indoor InstallationsClearances Conventional Combustion Air Supply Combustion and Ventilation AirAll Air from Outdoors Canadian InstallationsHydrostatic Test Water PipingGeneral Reversing Water Connections Relief Valve PipingModels 399B-899B Models 989B-2339B Cold Water OperationCold Water Starts Cold Water Run Temperature & Pressure GaugeHydronic Heating Pump SelectionThree-Way Valves Pressure Drop in Feet of Head Feedwater RegulatorPiping Air-Separation/Expansion TankPotable Water and Space Heating Gas SupplyModel Gas Supply ConnectionTable I Maximum Equivalent Pipe Length Gas Supply Pressure Models 399B-2339B Adjustment Models 989B-2339BReversing Gas Supply Connection Making the Electrical Connections Electrical Power ConnectionsCheck the Power Source Field-Connected ControllersOn-Off Wiring Connections Field Wiring ConnectionStage Wiring Connections Single Stage Tankstat Support of Vent Stack VentingBarometric Damper Vent Terminal Location InstallationsCanadian Installations Venting Installation TipsChanging the Flue Outlet Termination Venting ConfigurationsInstallation Natural Draft Vertical Venting CategoryMaterial Min SizeHorizontal Through-the-Wall Venting Category Horizontal Through-the-Wall Venting CategoryMaterial Vent Length Controls Outdoor InstallationFreeze Protection Models 399B-899B Heater Sequence of OperationExternal Lights Color Indication Page Models 989B-2339B Models 1529B-2339B Only Operating Control High Limit Manual ResetFlow Switch Ignition ModuleLow Water Cut-Off Optional High and Low Gas Pressure SwitchesWiring Diagram Models 399B-1259B Wiring Diagram Models 1529B-2339B Pre Start-up START-UPMain Burner Adjustment Blower AdjustmentStart-Up Pilot Turn-Down Test Safety InspectionLeak Test Procedure Dual-Seat Gas Valves Follow-UpLeak Test Post Start-Up CheckLighting Instructions OperationTo Turn Off Gas To Appliance Step TroubleshootingSuggested Minimum Maintenance Schedule MaintenancePreventive Maintenance Schedule As Required WeeklySemi-Annually AnnuallyInside Air Contamination AppendixLimited Parts Warranty Delta Limited Types H and WH START-UP Checklist for FAN-ASSISTED Raypak Products

399B-2339B specifications

The Raypak 399B-2339B is a notable pool heater that stands out in the competitive market of heating solutions, particularly aimed at residential and commercial swimming pools and spas. Designed for efficiency and reliability, the Raypak 399B-2339B integrates advanced technology to deliver a comfortable swimming experience, safeguarding users against fluctuating outdoor temperatures.

One of the primary features of the Raypak 399B-2339B is its robust design, built to withstand the rigors of outdoor environments. With a durable cabinet made from corrosion-resistant materials, it ensures longevity and resistance to various weather conditions. This heater boasts a compact footprint, making it an ideal choice for properties with limited installation space.

A standout characteristic of this model is its energy efficiency. The Raypak 399B-2339B utilizes a high-efficiency gas burner, allowing it to heat water quickly while consuming less fuel. This efficiency not only reduces operational costs but also aligns with environmentally conscious practices, making it an appealing choice for eco-friendly users.

Equipped with innovative technologies, this heater offers both digital controls and diagnostic capabilities. The user-friendly digital display allows for precise temperature control and easy monitoring of the heater's performance. Additionally, the built-in diagnostics feature alerts users to any operational issues, ensuring timely maintenance and minimizing downtime.

The Raypak 399B-2339B is compatible with both natural gas and propane, providing versatility in energy sources. This adaptability can be particularly beneficial for those seeking to switch fuel types or utilize available resources. Moreover, its low NOx emissions make it compliant with stringent environmental regulations, contributing to cleaner air and a healthier ecosystem.

In terms of heating capacity, the Raypak 399B-2339B boasts a powerful output, efficiently heating large bodies of water. This performance makes it suitable for various applications, from residential pools to commercial aquatic centers, ensuring that swimming enjoyment is never compromised due to cold water.

The unit also features a built-in water hydraulics system that optimizes water circulation, preventing overheating and prolonging the lifespan of the heater. Furthermore, the Raypak engineering team has ensured that the installation process is straightforward, with clear guidelines and necessary plumbing fittings provided.

In summary, the Raypak 399B-2339B is a top-tier pool heater that offers durability, energy efficiency, advanced technology, and versatile fuel compatibility. Its high performance and user-friendly features make it a reliable investment for anyone looking to enhance their swimming experience.