Raypak 399B-2339B Operation, Lighting Instructions, To Turn Off Gas To Appliance

Page 45

10.To restart system, follow lighting instructions in the Operation section.

11.Check to see that the high limit control is set above the design temperature requirements of the system.

For multiple zones: Check to make sure the flow is adjusted as required in each zone.

12.Check that the heater is cycled with the thermo- stat. Raise to the highest setting and verify that the heater goes through the normal start-up cycle. Re- duce to the lowest setting and verify that the heater goes off.

13.Observe several operating cycles for proper oper- ation.

14.Set the room thermostat or tankstat to desired temperature.

15.Review all instructions shipped with this heater with owner or maintenance person, return to enve- lope and give to owner or place the instructions inside front panel on heater.

OPERATION

Lighting Instructions

1.Before lighting, make sure you have read all of the safety information in this manual.

2.Set the thermostat to the lowest setting.

3.Turn off all electrical power to the appliance.

4.This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.

5.Remove upper front panel.

6.Turn on main manual gas valve.

7.Wait 5 minutes to clear out any gas. Then smell for gas, especially near the floor. If you then smell gas, STOP! Follow the steps in the safety informa- tion on the front cover of this manual. If you do not smell gas, go to next step.

8.Turn on all electrical power to the appliance.

9.Set thermostat to desired setting. The appliance will operate. The igniter will glow after the pre- purge time delay (15 seconds). After igniter reaches temperature (45 seconds) the main valve will open. System will try for ignition three times. If flame is not sensed, lockout will commence.

10.If the appliance will not operate, follow the instruc- tions “To Turn Off Gas To Appliance,” and call your service technician or gas supplier.

11.Replace access panel.

12.If heater fails to start, verify the following:

a.There are no loose connections or that the service switch is off.

b.High temperature limit switch is set above wa- ter temperature.

c.Thermostat is set above room temperature.

d.Gas is on at the meter and the heater.

e.Incoming gas pressure to the gas valve is NOT less than 5.0 in. WC for natural gas, 11.0 in. WC for propane gas.

To Turn Off Gas To Appliance

1.Set the thermostat to lowest setting.

2.Turn off all electrical power to the appliance if serv- ice is to be performed.

3.Remove upper front panels.

4.Turn off main manual gas valve.

5.Replace access panel.

45

Image 45
Contents Installation & Operating Instructions Page Contents Pay Attention to These Terms Installations at Elevation Before InstallationProduct Receipt Model IdentificationComponent Locations Back Component LocationsBurners per Valve Stages Fire at Stage General InformationGeneral Safety Time/Temperature Relationships in ScaldsWater Time to Produce Serious Temp Burn Installation Codes InstallationEquipment Base StackingTable D Vent/Air Inlet Termination Clearances Indoor Installations Outdoor InstallationsClearances Conventional Combustion Air Supply Combustion and Ventilation AirAll Air from Outdoors Canadian InstallationsGeneral Water PipingReversing Water Connections Relief Valve Piping Hydrostatic TestCold Water Operation Models 399B-899B Models 989B-2339BCold Water Starts Hydronic Heating Temperature & Pressure GaugePump Selection Cold Water RunPiping Pressure Drop in Feet of Head Feedwater RegulatorAir-Separation/Expansion Tank Three-Way ValvesPotable Water and Space Heating Gas SupplyGas Supply Connection ModelTable I Maximum Equivalent Pipe Length Models 399B-2339B Adjustment Models 989B-2339B Gas Supply PressureReversing Gas Supply Connection Check the Power Source Electrical Power ConnectionsField-Connected Controllers Making the Electrical ConnectionsOn-Off Wiring Connections Field Wiring ConnectionStage Wiring Connections Single Stage Tankstat Venting Support of Vent StackBarometric Damper Vent Terminal Location InstallationsVenting Installation Tips Canadian InstallationsChanging the Flue Outlet Installation Venting ConfigurationsNatural Draft Vertical Venting Category TerminationMaterial Min SizeHorizontal Through-the-Wall Venting Category Horizontal Through-the-Wall Venting CategoryMaterial Vent Length Outdoor Installation ControlsFreeze Protection Heater Sequence of Operation Models 399B-899BExternal Lights Color Indication Page Models 989B-2339B Models 1529B-2339B Only Flow Switch High Limit Manual ResetIgnition Module Operating ControlLow Water Cut-Off Optional High and Low Gas Pressure SwitchesWiring Diagram Models 399B-1259B Wiring Diagram Models 1529B-2339B Pre Start-up START-UPBlower Adjustment Main Burner AdjustmentStart-Up Leak Test Procedure Dual-Seat Gas Valves Safety InspectionFollow-Up Pilot Turn-Down TestLeak Test Post Start-Up CheckOperation Lighting InstructionsTo Turn Off Gas To Appliance Step TroubleshootingMaintenance Suggested Minimum Maintenance SchedulePreventive Maintenance Schedule Semi-Annually WeeklyAnnually As RequiredInside Air Contamination AppendixLimited Parts Warranty Delta Limited Types H and WH START-UP Checklist for FAN-ASSISTED Raypak Products

399B-2339B specifications

The Raypak 399B-2339B is a notable pool heater that stands out in the competitive market of heating solutions, particularly aimed at residential and commercial swimming pools and spas. Designed for efficiency and reliability, the Raypak 399B-2339B integrates advanced technology to deliver a comfortable swimming experience, safeguarding users against fluctuating outdoor temperatures.

One of the primary features of the Raypak 399B-2339B is its robust design, built to withstand the rigors of outdoor environments. With a durable cabinet made from corrosion-resistant materials, it ensures longevity and resistance to various weather conditions. This heater boasts a compact footprint, making it an ideal choice for properties with limited installation space.

A standout characteristic of this model is its energy efficiency. The Raypak 399B-2339B utilizes a high-efficiency gas burner, allowing it to heat water quickly while consuming less fuel. This efficiency not only reduces operational costs but also aligns with environmentally conscious practices, making it an appealing choice for eco-friendly users.

Equipped with innovative technologies, this heater offers both digital controls and diagnostic capabilities. The user-friendly digital display allows for precise temperature control and easy monitoring of the heater's performance. Additionally, the built-in diagnostics feature alerts users to any operational issues, ensuring timely maintenance and minimizing downtime.

The Raypak 399B-2339B is compatible with both natural gas and propane, providing versatility in energy sources. This adaptability can be particularly beneficial for those seeking to switch fuel types or utilize available resources. Moreover, its low NOx emissions make it compliant with stringent environmental regulations, contributing to cleaner air and a healthier ecosystem.

In terms of heating capacity, the Raypak 399B-2339B boasts a powerful output, efficiently heating large bodies of water. This performance makes it suitable for various applications, from residential pools to commercial aquatic centers, ensuring that swimming enjoyment is never compromised due to cold water.

The unit also features a built-in water hydraulics system that optimizes water circulation, preventing overheating and prolonging the lifespan of the heater. Furthermore, the Raypak engineering team has ensured that the installation process is straightforward, with clear guidelines and necessary plumbing fittings provided.

In summary, the Raypak 399B-2339B is a top-tier pool heater that offers durability, energy efficiency, advanced technology, and versatile fuel compatibility. Its high performance and user-friendly features make it a reliable investment for anyone looking to enhance their swimming experience.