Raypak 399B-2339B operating instructions Weekly, Semi-Annually, As Required

Page 48

Weekly

For low-pressure heaters, test low-water cut-off device. (With at least one stage of the appliance on, depress the low water cut-off test button, appliance should shut-off and ignition fault light should come on. Depress reset button to reset).

Monthly

1.Check flue, vent, stack, or outlet dampers.

2.Test fan air pressure. (See “Blower Adjustment” on page 42.)

3.Test high and low gas pressure interlocks (if equipped). (See “Safety Inspection” on page 43.)

Semi-Annually

1.Recalibrate all indicating and recording gauges.

2.Check flame failure detection system components. (See “Pilot Turn-Down Test Procedure,” page 43.)

3.Check firing rate control by checking the manifold pressure. (See “Main Burner Adjustment” on page 42.)

4.Check piping and wiring of all interlocks and shut- off valves.

Annually

1.Test flame failure detection system and pilot turn- down. (See “Pilot Turn-Down Test Procedure,” page 43.)

2.Test high limit and operating temperature. (See “Post Start-Up Check,” page 44.)

3.Check flame sensors.

4.Conduct a combustion test at full fire. Carbon di- oxide should be 7.5 to 8.5% at full fire for natural gas, and between 9.2 to 9.8% for propane gas (Carbon monoxide should be < 150 ppm).

5.Check coils for 60 cycle hum or buzz. Check for leaks at all valve fittings using a soapy water solu- tion. Test other operating parts of all safety shut-off and control valves and increase or decrease set- tings (depending on the type of control) until the safety circuit opens. Reset to original setting after each device is tested.

6.Perform leakage test on gas valves. (See Fig. 36.)

7.Test air switch in accordance with manufacturer’s instructions. (Turn panel switch to the “On” posi- tion until blower is proven, then turn the switch to “Off”.

8.Inspect and clean burners as necessary.

As Required

1.Recondition or replace low water cut-off device (if equipped).

2.Check drip leg and gas strainers.

3.Perform flame failure detection and pilot turn- down tests.

4.Check igniter. (Resistance reading should be 42- 70 ohms at ambient temperature.)

5.Check flame signal strength. (Flame signal should be greater than 1 microamp).

6.Test safety/safety relief valves in accordance with ASME Heater and Pressure Vessel Code Sections VI and VII.

48

Image 48
Contents Installation & Operating Instructions Page Contents Pay Attention to These Terms Before Installation Installations at ElevationProduct Receipt Model IdentificationComponent Locations Component Locations BackGeneral Information Burners per Valve Stages Fire at StageGeneral Safety Time/Temperature Relationships in ScaldsWater Time to Produce Serious Temp Burn Installation Installation CodesEquipment Base StackingTable D Vent/Air Inlet Termination Clearances Indoor Installations Outdoor InstallationsClearances Combustion and Ventilation Air Conventional Combustion Air SupplyCanadian Installations All Air from OutdoorsWater Piping GeneralReversing Water Connections Relief Valve Piping Hydrostatic TestCold Water Operation Models 399B-899B Models 989B-2339BCold Water Starts Temperature & Pressure Gauge Hydronic HeatingPump Selection Cold Water RunPressure Drop in Feet of Head Feedwater Regulator PipingAir-Separation/Expansion Tank Three-Way ValvesGas Supply Potable Water and Space HeatingGas Supply Connection ModelTable I Maximum Equivalent Pipe Length Models 399B-2339B Adjustment Models 989B-2339B Gas Supply PressureReversing Gas Supply Connection Electrical Power Connections Check the Power SourceField-Connected Controllers Making the Electrical ConnectionsField Wiring Connection On-Off Wiring ConnectionsStage Wiring Connections Single Stage Tankstat Venting Support of Vent StackBarometric Damper Installations Vent Terminal LocationVenting Installation Tips Canadian InstallationsChanging the Flue Outlet Venting Configurations InstallationNatural Draft Vertical Venting Category TerminationSize Material MinHorizontal Through-the-Wall Venting Category Horizontal Through-the-Wall Venting CategoryMaterial Vent Length Outdoor Installation ControlsFreeze Protection Heater Sequence of Operation Models 399B-899BExternal Lights Color Indication Page Models 989B-2339B Models 1529B-2339B Only High Limit Manual Reset Flow SwitchIgnition Module Operating ControlHigh and Low Gas Pressure Switches Low Water Cut-Off OptionalWiring Diagram Models 399B-1259B Wiring Diagram Models 1529B-2339B START-UP Pre Start-upBlower Adjustment Main Burner AdjustmentStart-Up Safety Inspection Leak Test Procedure Dual-Seat Gas ValvesFollow-Up Pilot Turn-Down TestPost Start-Up Check Leak TestOperation Lighting InstructionsTo Turn Off Gas To Appliance Troubleshooting StepMaintenance Suggested Minimum Maintenance SchedulePreventive Maintenance Schedule Weekly Semi-AnnuallyAnnually As RequiredAppendix Inside Air ContaminationLimited Parts Warranty Delta Limited Types H and WH START-UP Checklist for FAN-ASSISTED Raypak Products

399B-2339B specifications

The Raypak 399B-2339B is a notable pool heater that stands out in the competitive market of heating solutions, particularly aimed at residential and commercial swimming pools and spas. Designed for efficiency and reliability, the Raypak 399B-2339B integrates advanced technology to deliver a comfortable swimming experience, safeguarding users against fluctuating outdoor temperatures.

One of the primary features of the Raypak 399B-2339B is its robust design, built to withstand the rigors of outdoor environments. With a durable cabinet made from corrosion-resistant materials, it ensures longevity and resistance to various weather conditions. This heater boasts a compact footprint, making it an ideal choice for properties with limited installation space.

A standout characteristic of this model is its energy efficiency. The Raypak 399B-2339B utilizes a high-efficiency gas burner, allowing it to heat water quickly while consuming less fuel. This efficiency not only reduces operational costs but also aligns with environmentally conscious practices, making it an appealing choice for eco-friendly users.

Equipped with innovative technologies, this heater offers both digital controls and diagnostic capabilities. The user-friendly digital display allows for precise temperature control and easy monitoring of the heater's performance. Additionally, the built-in diagnostics feature alerts users to any operational issues, ensuring timely maintenance and minimizing downtime.

The Raypak 399B-2339B is compatible with both natural gas and propane, providing versatility in energy sources. This adaptability can be particularly beneficial for those seeking to switch fuel types or utilize available resources. Moreover, its low NOx emissions make it compliant with stringent environmental regulations, contributing to cleaner air and a healthier ecosystem.

In terms of heating capacity, the Raypak 399B-2339B boasts a powerful output, efficiently heating large bodies of water. This performance makes it suitable for various applications, from residential pools to commercial aquatic centers, ensuring that swimming enjoyment is never compromised due to cold water.

The unit also features a built-in water hydraulics system that optimizes water circulation, preventing overheating and prolonging the lifespan of the heater. Furthermore, the Raypak engineering team has ensured that the installation process is straightforward, with clear guidelines and necessary plumbing fittings provided.

In summary, the Raypak 399B-2339B is a top-tier pool heater that offers durability, energy efficiency, advanced technology, and versatile fuel compatibility. Its high performance and user-friendly features make it a reliable investment for anyone looking to enhance their swimming experience.