Raypak 399B-2339B operating instructions Heater Sequence of Operation, Models 399B-899B

Page 33

Fig. 27: Status LED Indicator Decal

External Lights

Light

Color

Indication

 

 

 

Power On

Green

24 VAC

switched on

 

 

 

 

 

Call For Heat

Amber

Thermostat is

closed

 

 

 

 

 

Burner Firing

Blue

Burner(s) are

firing

 

 

 

 

 

Service Req’d

Red

Service

required

 

 

 

 

 

Table N: Status LED Indicators

Heater Sequence of Operation

Models 399B–899B

1.The black (hot) wire lead goes directly to the main power switch. This black toggle switch is located at the middle front of the control compartment.

2.When the main power switch is placed in the “ON” position, 120 VAC is applied to the 120 VAC termi- nal block on the circuit board and the 120/24 VAC transformer is powered.

3.120 VAC is waiting at the N.O. contacts of the pump delay relay.

4.Terminals L1 and F1 of the ignition module are powered with 120VAC.

5.120 VAC power is also applied to the control power connector on the circuit board.

6.120 VAC power is waiting at relay contacts K-3 to energize the heater blower.

7.The 120/24 VAC transformer outputs 24 VAC.

8.24 VAC is sent to power terminal L1 of the low water cut-off board (optional).

9.24 VAC is applied to the red LED safety shutdown light on the front of the unit.

10.24 VAC is applied to the alarm circuit (optional). If the E-5 sales option (Alarm) is included a 5 sec- ond time delay relay will not allow the alarm to sound unless the circuit stays energized for more than 5 seconds.

11.Power is output from terminal J5-24V of the CPW board to all of the safeties. All safeties are verified to ensure that it is safe to operate the heater. The safety components wired into the diagnostic board are: Manual reset high limit, low water cut-off (optional), blocked vent switch, low gas pressure switch (optional), and high gas pressure switch (optional).

12.Once all safeties have been verified to be closed a 24 VAC signal is sent to pin P3-16 of J-5 on the CPW board.

13.24 VAC power now leaves pin P3-16 of J-5 on the CPW board and is sent to the auto-reset high limit (optional). If closed the power now goes to termi- nal P1-4 of J-5 on the CPW board.

14.Power is applied to terminal 24V of the pump delay relay to energize the timing circuit .

15.Relay K-1 (N.C.) will now be energized, and opens the N.C. contacts to disable the alarm (optional) and turn off the red safety shutdown light.

16.Pin P1-4 on the diagnostic board will now output a 24 VAC signal to pin 1 of the “standby switch”.

17.The “standby switch” (rocker switch) located at the lower left front of the control compartment is now

33

Image 33
Contents Installation & Operating Instructions Page Contents Pay Attention to These Terms Installations at Elevation Before InstallationProduct Receipt Model IdentificationComponent Locations Back Component LocationsBurners per Valve Stages Fire at Stage General InformationGeneral Safety Time/Temperature Relationships in ScaldsWater Time to Produce Serious Temp Burn Installation Codes InstallationEquipment Base StackingTable D Vent/Air Inlet Termination Clearances Indoor Installations Outdoor InstallationsClearances Conventional Combustion Air Supply Combustion and Ventilation AirAll Air from Outdoors Canadian InstallationsGeneral Water PipingReversing Water Connections Relief Valve Piping Hydrostatic TestCold Water Operation Models 399B-899B Models 989B-2339BCold Water Starts Hydronic Heating Temperature & Pressure GaugePump Selection Cold Water RunPiping Pressure Drop in Feet of Head Feedwater RegulatorAir-Separation/Expansion Tank Three-Way ValvesPotable Water and Space Heating Gas SupplyGas Supply Connection ModelTable I Maximum Equivalent Pipe Length Models 399B-2339B Adjustment Models 989B-2339B Gas Supply PressureReversing Gas Supply Connection Check the Power Source Electrical Power ConnectionsField-Connected Controllers Making the Electrical ConnectionsOn-Off Wiring Connections Field Wiring ConnectionStage Wiring Connections Single Stage Tankstat Venting Support of Vent StackBarometric Damper Vent Terminal Location InstallationsVenting Installation Tips Canadian InstallationsChanging the Flue Outlet Installation Venting ConfigurationsNatural Draft Vertical Venting Category TerminationMaterial Min SizeHorizontal Through-the-Wall Venting Category Horizontal Through-the-Wall Venting CategoryMaterial Vent Length Outdoor Installation ControlsFreeze Protection Heater Sequence of Operation Models 399B-899BExternal Lights Color Indication Page Models 989B-2339B Models 1529B-2339B Only Flow Switch High Limit Manual ResetIgnition Module Operating ControlLow Water Cut-Off Optional High and Low Gas Pressure SwitchesWiring Diagram Models 399B-1259B Wiring Diagram Models 1529B-2339B Pre Start-up START-UPBlower Adjustment Main Burner AdjustmentStart-Up Leak Test Procedure Dual-Seat Gas Valves Safety InspectionFollow-Up Pilot Turn-Down TestLeak Test Post Start-Up CheckOperation Lighting InstructionsTo Turn Off Gas To Appliance Step TroubleshootingMaintenance Suggested Minimum Maintenance SchedulePreventive Maintenance Schedule Semi-Annually WeeklyAnnually As RequiredInside Air Contamination AppendixLimited Parts Warranty Delta Limited Types H and WH START-UP Checklist for FAN-ASSISTED Raypak Products

399B-2339B specifications

The Raypak 399B-2339B is a notable pool heater that stands out in the competitive market of heating solutions, particularly aimed at residential and commercial swimming pools and spas. Designed for efficiency and reliability, the Raypak 399B-2339B integrates advanced technology to deliver a comfortable swimming experience, safeguarding users against fluctuating outdoor temperatures.

One of the primary features of the Raypak 399B-2339B is its robust design, built to withstand the rigors of outdoor environments. With a durable cabinet made from corrosion-resistant materials, it ensures longevity and resistance to various weather conditions. This heater boasts a compact footprint, making it an ideal choice for properties with limited installation space.

A standout characteristic of this model is its energy efficiency. The Raypak 399B-2339B utilizes a high-efficiency gas burner, allowing it to heat water quickly while consuming less fuel. This efficiency not only reduces operational costs but also aligns with environmentally conscious practices, making it an appealing choice for eco-friendly users.

Equipped with innovative technologies, this heater offers both digital controls and diagnostic capabilities. The user-friendly digital display allows for precise temperature control and easy monitoring of the heater's performance. Additionally, the built-in diagnostics feature alerts users to any operational issues, ensuring timely maintenance and minimizing downtime.

The Raypak 399B-2339B is compatible with both natural gas and propane, providing versatility in energy sources. This adaptability can be particularly beneficial for those seeking to switch fuel types or utilize available resources. Moreover, its low NOx emissions make it compliant with stringent environmental regulations, contributing to cleaner air and a healthier ecosystem.

In terms of heating capacity, the Raypak 399B-2339B boasts a powerful output, efficiently heating large bodies of water. This performance makes it suitable for various applications, from residential pools to commercial aquatic centers, ensuring that swimming enjoyment is never compromised due to cold water.

The unit also features a built-in water hydraulics system that optimizes water circulation, preventing overheating and prolonging the lifespan of the heater. Furthermore, the Raypak engineering team has ensured that the installation process is straightforward, with clear guidelines and necessary plumbing fittings provided.

In summary, the Raypak 399B-2339B is a top-tier pool heater that offers durability, energy efficiency, advanced technology, and versatile fuel compatibility. Its high performance and user-friendly features make it a reliable investment for anyone looking to enhance their swimming experience.