Raypak 055B Troubleshooting Honeywell S8600, Electrical Electronic Ignition IID, High Voltage

Page 25

ELECTRICAL (ELECTRONIC IGNITION IID)

Intermittent Pilot System

TROUBLESHOOTING HONEYWELL S8600

WARNING

HIGH VOLTAGE

For qualified Technicians ONLY

NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater.

START

TURN GAS SUPPLY OFF. TURN THERMOSTAT (CONTROLLER) TO CALL FOR HEAT

POWER TO MODULE

(24 V NOMINAL)

YES

SPARK ACROSS

IGNITER/SENSOR GAP

YES

TURN GAS SUPPLY ON

PILOT BURNER LIGHTS?

YES

SPARK STOPS WHEN

PILOT IS LIT?

YES

MAIN BURNER LIGHTS?

YES

SYSTEM RUNS UNTIL CALL FOR HEAT ENDS?

YES

 

 

 

NOTE: Before troubleshooting, familiarize yourself with the start-up and checkout

 

 

 

 

procedure.

 

 

 

 

 

 

 

 

 

Check line voltage power, low voltage transformer, limit controller, thermostat

 

NO

 

 

 

(controller) and wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pull ignition lead and check spark at module.

 

 

 

 

 

NO

 

 

 

 

 

 

Spark Okay?

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

Check ignition cable, ground wiring, ceramic insulator and gap, and correct.

 

 

 

Check boot of the ignition cable for signs of melting or buckling. Take protective

 

 

 

 

 

action to shield cable and boot from excessive temperatures.

 

 

 

 

 

 

 

NO

 

Check that all manual gas valves are open, supply tubing and pressures are good,

 

 

 

 

 

 

 

and pilot burner orifice is not blocked.

 

 

 

 

 

 

 

 

 

Check electrical connections between module and pilot operator on gas control.

 

 

 

 

Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay,

 

 

 

 

 

replace gas control; if not, replace module.

 

 

 

 

 

 

 

 

 

NOTE: If S8600H goes into lockout, reset system. Lockout is used on L.P.G. models.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

Check continuity of ignition cable and ground wire.

 

 

 

 

 

 

Clean flame rod.

 

 

 

 

Check electrical connections between flame rod and module.

 

 

 

 

Check for cracked ceramic flame rod insulator.

 

 

 

 

Check that pilot flame covers flame rod and is steady and blue.

 

 

 

 

Adjust pilot flame.

 

 

 

 

If problem persists, replace module.

 

 

 

 

 

 

 

 

 

 

Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.

 

NO

 

Check electrical connections between module and gas control. If okay, replace

 

 

 

 

 

 

 

gas valve or gas control operator, i.e. pilot gas valve, flow switch etc.

 

 

 

 

 

 

 

 

 

NOTE: IF S8600H goes into lockout, reset system.

 

 

 

 

 

NO

 

 

 

 

 

Check continuity of ignition cable and ground wire.

 

 

 

 

 

 

 

 

 

 

NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though

 

 

 

 

 

 

operation is normal at the time of checkout.

 

 

 

 

Check that pilot flame covers flame rod and is steady and blue.

 

 

 

 

If checks are okay, replace module.

 

CALL FOR HEAT ENDS

SYSTEM SHUTS OFF?

YES

TROUBLESHOOTING

ENDS

NO

 

Check for proper thermostat (controller) operation.

 

 

 

Remove MV lead at module; if valve closes, recheck temperature controller and

 

 

 

 

 

wiring; if not, replace gas valve.

Repeat procedure until trouble free operation is obtained.

24

Image 25
Contents What to do if YOU Smell GAS VersaContents START-UP Procedures For Your Safety Read Before OperatingBefore START-UP Burners WaterLighting Instructions Millivolt SystemTo Turn OFF GAS to Appliance Operating Instructions Electronic Ignition SystemsWater Pressure Switch Maintenance Care ProceduresAfter START-UP Visual InspectionPool & SPA Water Chemistry Basic Tips if Heater will not FireCold Weather Operation Winterizing the SPA HeaterInstallation Instructions General SpecificationReceiving Equipment Outdoor Heaters ALL HeatersVenting Connections Indoor HeatersStep Vent Piping Model GAS Supply ConnectionsGAS Pressure Regulator Robertshaw MVFlow Rates Plumbing for Water Connections LocationCompanion Flange Connections Automatic Chlorinators and Chemical FeedersPressure Relief Valve Installation Auxiliary Bypass Valve AdjustmentElectrical Wiring Millivolt System Electronic Intermittent Ignition Device System IIDFig. #9240 Wiring Diagram KEYWiring Diagram Millivolt Units With Solid State Thermostat Wiring Diagram Millivolt Units With Mechanical ThermostatWiring Diagram 152178 Model 055 IID Temperature Controls CONTROLS/ADJUSTMENTS/REPLACEMENTSPressure Switch Servicing InstructionsHigh Limits Pressure Switch Adjustment Flame ROLL-OUT Safety SwitchTWO Speed Pumps High Limit RemovalBurner Drawer Removal Pilot Removal and CleaningGAS Valve Removal Main Burner and Orifice RemovalUnitherm Governor U.G. Replacement Desooting ProcedureCombustion Chamber Removal Control Immersion Well ReplaceTrouble Shooting Guide Liming Bypassing too much water Measured and Estimated Resistance Match Within 20 Percent Electrical Solid State Thermostat MillivoltElectrical Electronic Ignition IID Troubleshooting Honeywell S8600High Voltage Voltage Between 21.5-28.5 Electrical Solid State Thermostat IIDRAYPAK, INC Agoura Road Westlake VILLAGE, CA Replacement Parts List13-P 14-P 15-P IIDPage Page Warranty Conditions

055B specifications

The Raypak 055B is a high-performance pool and spa heater recognized for its efficiency, reliability, and advanced technologies tailored to meet the needs of consumers. Its compact design and powerful heating capabilities ensure that users enjoy warm water conditions regardless of the outdoor temperature.

One of the main features of the Raypak 055B is its exceptional heating output. With a power rating that can efficiently heat both pools and spas, this model is designed for performance. The heater's efficient heat exchanger is constructed from copper that enhances the transfer of heat, allowing for rapid heating while optimizing energy use. This results in lower utility bills and a smaller environmental footprint.

The Raypak 055B incorporates innovative technology that enhances user experience. It features a digital display that allows for precise temperature control and easy adjustments. Users can set the desired temperature and monitor energy usage, ensuring they achieve the perfect balance between comfort and efficiency. The built-in diagnostic system helps users troubleshoot any issues quickly, maintaining the heater's performance and prolonging its lifespan.

Another significant characteristic of the Raypak 055B is its reliability. The heater is designed with a durable, rust-resistant cabinet that protects the internal components from the elements. This rugged construction makes the Raypak 055B an excellent choice for outdoor installations, ensuring longevity and reliable operation year-round.

The advanced airflow design in the Raypak 055B ensures a safe and efficient operation. The heater is equipped with a standard fan that aids in efficient operation while minimizing noise. Additionally, its low NOx emissions technology meets strict environmental regulations, making it an environmentally friendly option.

The Raypak 055B also includes an innovative ignition system for enhanced safety and convenience. The direct spark ignition eliminates the need for a standing pilot light, reducing gas consumption and further improving efficiency. The unit's freeze protection feature prevents damage during harsh winter conditions, ensuring that users can rely on it throughout the seasons.

In conclusion, the Raypak 055B stands out as a top choice for pool and spa heating solutions. With its combination of efficiency, durability, and advanced technology, it meets the demands of modern consumers looking for comfort without compromising on performance or sustainability. Whether you need to heat a residential pool or a commercial spa, the Raypak 055B is engineered to deliver exceptional results.