Raypak 055B installation instructions Electrical Solid State Thermostat Millivolt

Page 24

ELECTRICAL (SOLID STATE THERMOSTAT MILLIVOLT)

If the pool/spa/hot tub water is too cold, troubleshoot the system as follows:

Check voltage at + and - terminals.

 

 

 

 

 

 

 

 

VOLTAGE BETWEEN + 0.2 V and 0.75 V.

 

VOLTAGE OUTSIDE RANGE + 0.2 V and 0.75 V.

(Polarity is critical)

 

Check pilot generator, correct as necessary.

Set control to max. temperature. After 2-3

 

 

 

 

 

 

 

 

 

 

cycles, check water temperature.

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMPERATURE BELOW 105°F Disconnect sensor leads from circuit board. Measure sensor resistance with ohmmeter.

TEMPERATURE 105-108° F. Control ok.

NOTE: 108°F is the upper control limit.

RESISTANCE 1-14k OHMS.

Check water temperature; estimate expected sensor resistance from chart below.

RESISTANCE O OHMS (SHORT CIRCUIT) OR OPEN CIRCUIT GREATER THAN 14 K.

Check system for shorted wires or open circuits. Replace sensor if necessary.

MEASURED AND ESTIMATED RESISTANCE MATCH WITHIN 20 PERCENT.

Disconnect potentiometer leads from circuit board. Measure resistance with ohmmeter. If resistance is:

0-100 ohms at minimum setting:

9k to 11k at maximum setting,

replace circuit board. Above 11k ohms, replace

potentiometer.

0 ohms (short circuit), replace potentiometer.

Reconnect all leads and check out system.

MEASURED AND ESTIMATED RESISTANCE DON'T MATCH.

Replace sensor. Reconnect all leads and check out system.

If the pool/spa/hot tub water is too hot, troubleshoot the system as follows:

Check voltage at + and - terminals

 

 

 

 

 

VOLTAGE BETWEEN + 0.2 V and 0.75 V.

 

VOLTAGE OUTSIDE RANGE + 0.2 V and 0.75 V.

(Polarity is critical)

 

Check pilot generator, correct as necessary.

Set control to max. temperature. After 2-3

 

 

 

 

 

 

cycles, check water temperature.

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMPERATURE ABOVE 108°F Disconnect sensor leads from circuit board. Measure sensor resistance with ohmmeter.

TEMPERATURE 105-108° F. Control ok.

NOTE: 108°F is the upper control limit.

RESISTANCE 1-14k OHMS.

Check water temperature; estimate expected sen- sor resistance from chart below.

RESISTANCE ABOVE 15k OHMS (OPEN

CIRCUIT) OR SHORT CIRCUIT.

Fix loose or broken wires. Replace sensor if necessary.

MEASURED AND ESTIMATED RESISTANCE MATCH WITHIN 20 PERCENT.

Disconnect potentiometer leads from circuit board. Measure resistance with ohmmeter. If resistance is:

0-100 ohms at minimum setting;

9k to 11k at maximum setting,

replace circuit board. Above 11k ohms, replace

potentiometer.

0 ohms (short circuit), replace potentiometer.

MEASURED AND ESTIMATED RESISTANCE DON'T MATCH.

Replace sensor. Reconnect all leads and check out system.

SENSOR RESISTANCE AT VARIOUS TEMPERATURES

 

Temperature

 

 

 

 

 

 

 

 

 

 

 

(deg. F)

61

68

70

77

86

88

95

104

106

 

 

Resistance (k ohms)

14.92

12.49

11.88

10.00

8.06

7.69

6.53

5.33

5.10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

23

Image 24
Contents Versa What to do if YOU Smell GASContents For Your Safety Read Before Operating START-UP ProceduresBefore START-UP Burners WaterMillivolt System Lighting InstructionsTo Turn OFF GAS to Appliance Electronic Ignition Systems Operating InstructionsMaintenance Care Procedures Water Pressure SwitchAfter START-UP Visual InspectionBasic Tips if Heater will not Fire Pool & SPA Water ChemistryCold Weather Operation Winterizing the SPA HeaterGeneral Specification Installation InstructionsReceiving Equipment ALL Heaters Outdoor HeatersIndoor Heaters Venting ConnectionsStep Vent Piping GAS Supply Connections ModelGAS Pressure Regulator Robertshaw MVPlumbing for Water Connections Location Flow RatesCompanion Flange Connections Automatic Chlorinators and Chemical FeedersAuxiliary Bypass Valve Adjustment Pressure Relief Valve InstallationElectrical Wiring Millivolt System Electronic Intermittent Ignition Device System IIDWiring Diagram KEY Fig. #9240Wiring Diagram Millivolt Units With Mechanical Thermostat Wiring Diagram Millivolt Units With Solid State ThermostatWiring Diagram 152178 Model 055 IID CONTROLS/ADJUSTMENTS/REPLACEMENTS Temperature ControlsPressure Switch Servicing InstructionsPressure Switch Adjustment Flame ROLL-OUT Safety Switch High LimitsTWO Speed Pumps High Limit RemovalPilot Removal and Cleaning Burner Drawer RemovalGAS Valve Removal Main Burner and Orifice RemovalDesooting Procedure Unitherm Governor U.G. ReplacementCombustion Chamber Removal Control Immersion Well ReplaceTrouble Shooting Guide Liming Bypassing too much water Electrical Solid State Thermostat Millivolt Measured and Estimated Resistance Match Within 20 PercentTroubleshooting Honeywell S8600 Electrical Electronic Ignition IIDHigh Voltage Electrical Solid State Thermostat IID Voltage Between 21.5-28.5Replacement Parts List RAYPAK, INC Agoura Road Westlake VILLAGE, CAIID 13-P 14-P 15-PPage Page Warranty Conditions

055B specifications

The Raypak 055B is a high-performance pool and spa heater recognized for its efficiency, reliability, and advanced technologies tailored to meet the needs of consumers. Its compact design and powerful heating capabilities ensure that users enjoy warm water conditions regardless of the outdoor temperature.

One of the main features of the Raypak 055B is its exceptional heating output. With a power rating that can efficiently heat both pools and spas, this model is designed for performance. The heater's efficient heat exchanger is constructed from copper that enhances the transfer of heat, allowing for rapid heating while optimizing energy use. This results in lower utility bills and a smaller environmental footprint.

The Raypak 055B incorporates innovative technology that enhances user experience. It features a digital display that allows for precise temperature control and easy adjustments. Users can set the desired temperature and monitor energy usage, ensuring they achieve the perfect balance between comfort and efficiency. The built-in diagnostic system helps users troubleshoot any issues quickly, maintaining the heater's performance and prolonging its lifespan.

Another significant characteristic of the Raypak 055B is its reliability. The heater is designed with a durable, rust-resistant cabinet that protects the internal components from the elements. This rugged construction makes the Raypak 055B an excellent choice for outdoor installations, ensuring longevity and reliable operation year-round.

The advanced airflow design in the Raypak 055B ensures a safe and efficient operation. The heater is equipped with a standard fan that aids in efficient operation while minimizing noise. Additionally, its low NOx emissions technology meets strict environmental regulations, making it an environmentally friendly option.

The Raypak 055B also includes an innovative ignition system for enhanced safety and convenience. The direct spark ignition eliminates the need for a standing pilot light, reducing gas consumption and further improving efficiency. The unit's freeze protection feature prevents damage during harsh winter conditions, ensuring that users can rely on it throughout the seasons.

In conclusion, the Raypak 055B stands out as a top choice for pool and spa heating solutions. With its combination of efficiency, durability, and advanced technology, it meets the demands of modern consumers looking for comfort without compromising on performance or sustainability. Whether you need to heat a residential pool or a commercial spa, the Raypak 055B is engineered to deliver exceptional results.