Schneider Electric ACECFR20200SE, ACECFR20101SE, ACECFR40200SE Environment Piping/plumbing diagram

Page 13

Environment

NOTE: Locating the EcoBreeze system near areas of increased airborne debris may result in more frequent service intervals.

Piping/plumbing diagram

WATER RETURN GUTTER

X

FIELD

CONNECTIONS

na3453a

X

 

OPTIONAL SAND FILTER CONNECTIONS

Item Description

Item Description

Clear T-strainer

Two-way motorized valve*

Quick connect coupling

Water treatment module  Automatic vent

Pressure relief valve

Conductivity sensors

Water level sensors

Pump suction vent valve

Water sample service valve

Pump suction isolation valve

Redundant water pumps

Drain line cap

Check valves

Pump line drain solenoid valve

Basin overflow

Supply water piping drain solenoid valve**

Basin drain valve

Water supply A & B pressure switches***

Supply water A & B solenoid valves**

Blow down valve

Basin water supply pipe

Piping to other modules

Spray nozzles

Module water pressure switch

*Controlled from module

**Use electric schematic #APC-CFR-02 to confirm valve wiring connections

***Make sure the pressure switches are set to 7 psi

EcoBreeze System Installation

9

Image 13
Contents EcoBreeze System Installation ManualSchneider Electric IT Corporation Legal Disclaimer Contents Electrical Connections Mechanical ConnectionsGeneral Information SafetyInspecting the Equipment Storing the equipment before installationModel identification label location Model IdentificationFrames ModulesHazard of Electric Shock Access Door and Panel OperationDescription Quantity 20 ft 40 ft Component IdentificationItem Description EcoBreeze Frame and ModulesRemote display interface Module frontSite Preparation Incoming power supply requirements DuctworkWater supply FoundationEnvironment Piping/plumbing diagram Refrigeration Wall or Other Obstruction Service accessFrame Weights and DimensionsLifting and Rigging InstallationPosition the EcoBreeze Mechanical ConnectionsUnwrap the equipment Remove the tension rods Lower Module drop-down box Water supply connection Drain AIR GAP Electrical Connections Hazard to Equipment and Personnel Power supply to EcoBreeze FrameDDC Panel 126 K4 N4 G4 198 193 195 190 196 197Building Management System Page Page Worldwide Customer Support