Schneider Electric ACECFR40200SE, ACECFR20101SE, ACECFR20200SE Remove the tension rods

Page 20

Remove the tension rods

SUPPLY

BLOWER

ACCESS

COIL

ACCESS

SUPPLY

BLOWER

ACCESS

COIL

ACCESS

SUPPLY

BLOWER

ACCESS

COIL ACCESS

SUPPLY BLOWER ACCESS

COIL

ACCESS

na3450a

WARNING

DAMAGE TO EQUIPMENT OR PERSONNEL

Loosen the nuts on the ends of the tension rods to relieve tension before removing tension rod brackets.

Do not remove the tension rods until EcoBreeze Frame is placed and secured on its supports.

Move the EcoBreeze Frame directly from the truck to its permanent foundation or supports. If it must be stored temporarily, it must be placed on a flat and level surface to avoid damage.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Tension rods are installed diagonally across each Module bay to provide support during shipping.

1.Release tension on the rods by loosening the nuts on the ends of the tension rods.

2.Using an M12 wrench, remove the eight bolts securing the tension rod brackets.

3.Remove the tension rods and brackets.

16

EcoBreeze System Installation

Image 20
Contents Installation Manual EcoBreeze SystemSchneider Electric IT Corporation Legal Disclaimer Contents Mechanical Connections Electrical ConnectionsSafety General InformationStoring the equipment before installation Inspecting the EquipmentModel Identification Model identification label locationFrames ModulesAccess Door and Panel Operation Hazard of Electric ShockComponent Identification Description Quantity 20 ft 40 ftEcoBreeze Frame and Modules Item DescriptionModule front Remote display interfaceIncoming power supply requirements Ductwork Site PreparationWater supply FoundationEnvironment Piping/plumbing diagram Refrigeration Service access Wall or Other ObstructionWeights and Dimensions FrameInstallation Lifting and RiggingMechanical Connections Position the EcoBreezeUnwrap the equipment Remove the tension rods Lower Module drop-down box Water supply connection Drain AIR GAP Electrical Connections Power supply to EcoBreeze Frame Hazard to Equipment and PersonnelDDC Panel K4 N4 G4 198 193 195 190 196 197 126Building Management System Page Page Worldwide Customer Support