Schneider Electric ACECFR40201SE, ACECFR20101SE, ACECFR20200SE Building Management System

Page 29

Building Management System

The Modbus interface allows the EcoBreeze System to communicate with a building management system (BMS).

The Modbus connection is available in two locations on the Modbus hub:

RJ-45 In port

3-wire on terminal block

For an RJ-45 connection, wire as follows:

Pin 4

D(A)

Pin 5

D(B)

Pin 8

Ground

For a direct 3-wire connection, connect to the corresponding contacts on the green terminal block on the side of the Modbus hub. No connection is necessary to the 0V contact.

 

WIRING CONTACTS

 

DDC PANEL

 

 

ENCLOSURE

 

FOR DIRECT 3-WIRE

RJ-45 IN PORT

 

 

 

CONNECTION

 

 

 

 

1MOD

 

 

D(B)

 

 

 

D(A)

 

 

 

1MOD

 

 

na3660a

0 V

 

 

 

 

 

EcoBreeze System Installation

25

Image 29
Contents EcoBreeze System Installation ManualSchneider Electric IT Corporation Legal Disclaimer Contents Electrical Connections Mechanical ConnectionsGeneral Information SafetyInspecting the Equipment Storing the equipment before installationModel identification label location Model IdentificationFrames ModulesHazard of Electric Shock Access Door and Panel OperationDescription Quantity 20 ft 40 ft Component IdentificationItem Description EcoBreeze Frame and ModulesRemote display interface Module frontSite Preparation Incoming power supply requirements DuctworkWater supply FoundationEnvironment Piping/plumbing diagram Refrigeration Wall or Other Obstruction Service accessFrame Weights and DimensionsLifting and Rigging InstallationPosition the EcoBreeze Mechanical ConnectionsUnwrap the equipment Remove the tension rods Lower Module drop-down box Water supply connection Drain AIR GAP Electrical Connections Hazard to Equipment and Personnel Power supply to EcoBreeze FrameDDC Panel 126 K4 N4 G4 198 193 195 190 196 197Building Management System Page Page Worldwide Customer Support