Service access
Install a service platform (not supplied) to facilitate maintenance activities. Regular maintenance activities require a of minimum 1219 mm (48 in.) clearance on all sides to remove, maneuver, and install Modules and components.
1219 (48) |
1219 (48)
1219 (48) |
1219 (48)
na3526a
NOTE: Consider local soil conditions, codes, and loading when determining appropriate support footings.
To prevent short cycling of outdoor air, each EcoBreeze Frame must have a minimum of 1219 mm (48 in.) clearance on each side, totaling 2438 mm (96 in.) between Frames, and 1219 mm (48 in.) at the end of the Frame.
1219 (48)
1219 (48) |
2438 (96)
1219 (48) |
|
WALL OR OTHER OBSTRUCTION | na3677a |
|
* Dimensions are shown in millimeters with inches in parentheses.
EcoBreeze System Installation | 11 |