Samsung AQV12PWAX, AQV12PSBX manual Installing and connecting the assembly pipe of the indoor unit

Page 30
10.Connect the grounding conductor to the grounding terminals.

Connecting the assembly cable

• End of the wire must be circular.

• After connecting the cables, make sure terminal numbers on the indoor/outdoor unit matches.

Screws on terminal block must not be unscrewed with the torque less than 12kgf•cm.

10.Connect the grounding conductor to the grounding terminals.

11.Close the terminal board cover by tightening the screw carefully.

• In Russia and Europe, consult with the supply authority to determine the supply system impedance before

installation.

• Connect the wires firmly so that wires can not be pulled out easily. (If they are loose, it could cause burn-out of the wires.)

Connect the wires according to color codes, referring to the wiring diagram.

The power cable and the interconnection cable should be selected according to the specification in page 28.

Installing and connecting the assembly pipe of the indoor unit

Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.

There are 2 refrigerant pipes of different diameters:

The smaller one is for the liquid refrigerant

The larger one is for the gas refrigerant

A short pipe is already fitted to the air conditioner. You may need to extend the pipe using the assembly pipe (optional).

The connection procedure for the refrigerant pipe varies

 

 

according to the exit position of the pipe when facing the wall:

A

B

• Right(A)

 

 

• Left(B)

 

C

• Underside(C)

 

 

 

• Rear

 

 

1.Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor unit unless you connect the pipe directly from the rear.

2.Smooth the cut edges.

3.Remove the protection caps of the pipes and connect the assembly pipe to each pipe. Tighten the nuts first with your hands, and then with a torque wrench, applying the following torque:

Outer Diameter

Torque (kgf•cm)

 

 

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

• If you want to shorten or extend the pipes, refer to page 31~32.

30

Image 30
Contents Page Cost Efficient System Features of your new air conditionerCool Summer Offer Look for EverywhereImportant safety symbols and precautions Safety precautionsUSING PARTS FOR INSTALLATIONDo not pull the power cord, when unplugging the power plug FOR USINGFOR POWER SUPPLY Do not touch the power plug or the circuit breaker with wet handsDo not place objects or devices under the indoor unit FOR CLEANINGDo not clean the inside of the air conditioner by yourself Do not operate the appliance with wet handsModel RJ Checking before useOperation ranges Maintaining your air conditionerMain parts Power buttonChecking the name of the parts DisplayRemote controller display Smart Saver Checking the remote controllerRemote controller buttons On TimerStoring the remote controller Remote controller displayBattery changing time Turbo indicatorCool Basic functionAuto HeatPress the button to set the operating mode button to adjust the temperaturePress the button to turn on the air conditioner Press thePress the Air swingbutton on the remote controller Adjusting the air flow directionUsing the Turbo function Press the Turbo button on the remote controller during Cool modemode When the air conditioner is on and in cool/heat mode1. Press the button on the remote controller Temperature and fan speed changes in mode1. Press the On Timer/Off Timer button Setting the On/Off timerSetting On timer Setting Off timer Additional options available in On timer modeIf the air conditioner is off Using the Smart Saver functionIf the air conditioner is on Combining On Timer and Off TimerPress the Auto Clean button When the air conditioner is turned off Using the Quiet functionUsing the Auto Clean function When the air conditioner is turned onCleaning the outdoor unit heat exchanger Cleaning the air conditionerCleaning the indoor unit Opening the panelOpen the panel and put the Air filter out Cleaning the air filterRemoving the Air filter Dry the Air filter in a ventilated areaMaintaining the air conditioner Periodical checksSOLUTION TroubleshootingPROBLEM not work at allflow movement changes. It is normal Error is indicatedNoise is generated the outdoor unitINSTALLATION PARTS General informationIncluded Models Power supply line, fuse or circuit breaker Choosing the installation locationInstalling the unit Indoor unitOutdoor Unit Space Requirements for Outdoor Unit When installing 1 outdoor unitWhen installing more than 1 outdoor unit Top viewAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case Tools required for installation General Tools Fixing the installation plateOptional accessories Tools for test operationsConnecting the cable Connecting the assembly cableCable specification Power cableof the electrical contact during a wiring work 11. Close the terminal board cover by tightening the screw carefully Installing and connecting the assembly pipe of the indoor unit10. Connect the grounding conductor to the grounding terminals 2. Smooth the cut edges4. Cut off the remaining foam insulation Purging the indoor unitCutting or extending the pipe 6. Pass the pipe through the hole in the wallOuter Diameter 4. Put a flare nut slightly into the pipe and modify the flareDepth A Outer Diameter DInstalling and connecting the drain hose of the indoor unit Drain hose installation1. Detach the rubber cap with the plier Installing and connecting the drain hose of the indoor unitChanging direction of the drain hose 2. Detach the drain hose by pulling it and turning to the left2. Connect a drain hose to the drain plug InstallAA ing and connecting the drain hose of the outdoor unitPurging the connected pipes 3. Ensure that condensation draining is adequateIf you use a pipe longer than 5m gas service port as seen in the pictureAdding Refrigerant If you use a pipe shorter than 5m1. Please fill in with indelible ink Important information regulation regarding the refrigerant usedCylinder with siphon 1975To check for gas leaks on the indoor unit PerfoAA rming the gas leak testsTo check for gas leaks on the outdoor unit Leak test with nitrogen before opening valvesFixinAA g the indoor unit in place Outdoor unit installed on the wall by rack6. Attach the pipe to the wall using clamps optional Fixing the outdoor unit in placeFinalAA Check and Trial Operation 1. Press the Power button and check the following4. Press the Power button to stop the operation Check the followings5. Apply heat to the contraction tube to contract it The compression dimension should beand compress another two points in the same location 6. After tube contraction work is completed, wrap it with the2. Take off the Cover PCB Sub PCB installationoptional1. Turn the power off and take off the front panel of the indoor unit 3. Attach the Sub PCB to the right side of the Panel-frameENGLISH CALL QUESTIONS OR COMMENTS?COUNTRY EEE Yönetmeliğine Uygundur This EEE is compliant with RoHSimagine the possibilities user & installation manualAir Conditioner AQV07P Series AQV09P Series AQV12P Series AQV18P Series
Related manuals
Manual 41 pages 25.73 Kb Manual 41 pages 25.56 Kb Manual 41 pages 6.72 Kb Manual 45 pages 23.92 Kb Manual 41 pages 27.43 Kb Manual 43 pages 36.93 Kb Manual 43 pages 57.93 Kb Manual 41 pages 20.41 Kb Manual 21 pages 39.04 Kb Manual 21 pages 44.89 Kb Manual 21 pages 49.66 Kb Manual 21 pages 36.79 Kb Manual 21 pages 55.58 Kb Manual 45 pages 44.27 Kb Manual 43 pages 7.81 Kb Manual 43 pages 10.58 Kb Manual 45 pages 17.94 Kb Manual 43 pages 52.7 Kb