FinalAA Check and Trial Operation

FinalAA Check and Trial Operation

To complete the installation, perform the following checks and tests to ensure that the air conditioner operates correctly.

Check the followings:

• Strength of the installation site

• Tightness of pipe connection to detect gas leak

• Electric wiring connection

Heat-resistant insulation of the pipe

Drainage

Grounding conductor connection

Correct operation (follow the steps below)

1.Press the Power Check the followings: button and check the following:

The indicator on the indoor unit lights up.

The airflow blade opens and the fan gears up for operation.

2.Press the Mode button to select Cool or Heat mode.

In Cool mode, use Temp + or - button and set the temperature at 16°C.

In Heat mode, use Temp + or - button and set the temperature at 30°C.

• Approximately 3~5 minutes later, outdoor unit will start to operate and the Cool or Warm air will blow out.

• After 12 minutes of stationary condition check the indoor unit air treatment:

Cooling mode (indoor unit check) Inlet air temp. - Outlet air temp : From 10°K to 12°K ( indicative delta T)

Heating mode (indoor unit check) Outlet air temp. - Inlet air temp : From 11°K to 14°K (indicative delta T)

In heating mode, the indoor fan motor can remain off to avoid cold air blown into conditioned space.

3.Press the Air swing 1.Press the Power  button and check the following:2.Press the Mode button to select Cool or Heat mode. button and check the following:

The airflow blades work properly.

4.Press the Power 3.Press the Air swing  button and check the following: button to stop the operation.

• When you complete the installation successfully, hand over this manual to the user for storage in a handy and safe

place.

Pump down procedure (when removing the product)

1.Turn on the air conditioner and select Cool mode to run the compressor for 3 minutes.

2. Release the valve caps on High and Low pressure side.

3. Use L wrench to close the valve on the high pressure side.

4. Approximately 2 minutes after, close the valve on the low pressure side.

5. Stop operation of the air conditioner.

6. Disconnect the pipes.

40

Image 40
Contents Page Features of your new air conditioner Cool Summer OfferCost Efficient System Look for EverywhereSafety precautions USING PARTSImportant safety symbols and precautions FOR INSTALLATIONFOR USING FOR POWER SUPPLYDo not pull the power cord, when unplugging the power plug Do not touch the power plug or the circuit breaker with wet handsFOR CLEANING Do not clean the inside of the air conditioner by yourselfDo not place objects or devices under the indoor unit Do not operate the appliance with wet handsChecking before use Operation rangesModel RJ Maintaining your air conditionerPower button Checking the name of the partsMain parts DisplayChecking the remote controller Remote controller buttonsRemote controller display Smart Saver On TimerRemote controller display Battery changing timeStoring the remote controller Turbo indicatorBasic function AutoCool Heatbutton to adjust the temperature Press the button to turn on the air conditionerPress the button to set the operating mode Press theAdjusting the air flow direction Using the Turbo functionPress the Air swingbutton on the remote controller Press the Turbo button on the remote controller during Cool modeWhen the air conditioner is on and in cool/heat mode 1. Press the button on the remote controllermode Temperature and fan speed changes in modeSetting the On/Off timer Setting On timer Setting Off timer1. Press the On Timer/Off Timer button Additional options available in On timer modeUsing the Smart Saver function If the air conditioner is onIf the air conditioner is off Combining On Timer and Off TimerUsing the Quiet function Using the Auto Clean functionPress the Auto Clean button When the air conditioner is turned off When the air conditioner is turned onCleaning the air conditioner Cleaning the indoor unitCleaning the outdoor unit heat exchanger Opening the panelCleaning the air filter Removing the Air filterOpen the panel and put the Air filter out Dry the Air filter in a ventilated areaMaintaining the air conditioner Periodical checksTroubleshooting PROBLEMSOLUTION not work at allError is indicated Noise is generatedflow movement changes. It is normal the outdoor unitGeneral information INSTALLATION PARTSIncluded Models Choosing the installation location Installing the unitPower supply line, fuse or circuit breaker Indoor unitOutdoor Unit When installing 1 outdoor unit When installing more than 1 outdoor unitSpace Requirements for Outdoor Unit Top viewAccessories in the indoor unit case AccessoriesAccessories in the outdoor unit case Fixing the installation plate Optional accessoriesTools required for installation General Tools Tools for test operationsConnecting the assembly cable Cable specificationConnecting the cable Power cableof the electrical contact during a wiring work Installing and connecting the assembly pipe of the indoor unit 10. Connect the grounding conductor to the grounding terminals11. Close the terminal board cover by tightening the screw carefully 2. Smooth the cut edgesPurging the indoor unit Cutting or extending the pipe4. Cut off the remaining foam insulation 6. Pass the pipe through the hole in the wall4. Put a flare nut slightly into the pipe and modify the flare Depth AOuter Diameter Outer Diameter DInstalling and connecting the drain hose of the indoor unit Drain hose installationInstalling and connecting the drain hose of the indoor unit Changing direction of the drain hose1. Detach the rubber cap with the plier 2. Detach the drain hose by pulling it and turning to the leftInstallAA ing and connecting the drain hose of the outdoor unit Purging the connected pipes2. Connect a drain hose to the drain plug 3. Ensure that condensation draining is adequategas service port as seen in the picture Adding RefrigerantIf you use a pipe longer than 5m If you use a pipe shorter than 5mImportant information regulation regarding the refrigerant used Cylinder with siphon1. Please fill in with indelible ink 1975PerfoAA rming the gas leak tests To check for gas leaks on the outdoor unitTo check for gas leaks on the indoor unit Leak test with nitrogen before opening valvesOutdoor unit installed on the wall by rack 6. Attach the pipe to the wall using clamps optionalFixinAA g the indoor unit in place Fixing the outdoor unit in place1. Press the Power button and check the following 4. Press the Power button to stop the operationFinalAA Check and Trial Operation Check the followingsThe compression dimension should be and compress another two points in the same location5. Apply heat to the contraction tube to contract it 6. After tube contraction work is completed, wrap it with theSub PCB installationoptional 1. Turn the power off and take off the front panel of the indoor unit2. Take off the Cover PCB 3. Attach the Sub PCB to the right side of the Panel-frameENGLISH QUESTIONS OR COMMENTS? COUNTRYCALL EEE Yönetmeliğine Uygundur This EEE is compliant with RoHSuser & installation manual Air Conditionerimagine the possibilities AQV07P Series AQV09P Series AQV12P Series AQV18P Series
Related manuals
Manual 41 pages 25.73 Kb Manual 41 pages 25.56 Kb Manual 41 pages 6.72 Kb Manual 45 pages 23.92 Kb Manual 41 pages 27.43 Kb Manual 43 pages 36.93 Kb Manual 43 pages 57.93 Kb Manual 41 pages 20.41 Kb Manual 21 pages 39.04 Kb Manual 21 pages 44.89 Kb Manual 21 pages 49.66 Kb Manual 21 pages 36.79 Kb Manual 21 pages 55.58 Kb Manual 45 pages 44.27 Kb Manual 43 pages 7.81 Kb Manual 43 pages 10.58 Kb Manual 45 pages 17.94 Kb Manual 43 pages 52.7 Kb