gas service port as seen in the picture.

Purging the connected pipes

3. Connect the charging hose of the low-pressure side of manifold gauge to a

Manifold gauge

gas service port as seen in the picture.

 

4.Open the valve of the low pressure side of manifold gauge counterclockwise.

5.Purge the air in the connected pipes using the vacuum pump for about 15 minutes.

Make sure that pressure gauge shows -0.1MPa(-76cmHg) after about 10 minutes.

This procedure is very important to avoid a gas leak.

Close the valve of the low pressure side of manifold gauge clockwise.

Turn off the vacuum pump.

Check for 2 minutes if there is any pressure change.

Remove the hose of the low pressure side of manifold gauge.

6.Set a valve cork of liquid and gas service port to the open position.

Valve  Adding RefrigerantIf you use a pipe longer than 5m,If you use a pipe shorter than 5m,Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

Gas service port <Low pressure>

 

Vacuum

Liquid service port

Pump

<High pressure>

(Backward flowing

 

prevention)

7.Mount the valve stem nuts and the service port cap to the valve, and tighten them at the torque of 183kgf•cm with a torque wrench.

8.Check for a gas leak paying particular attention to the 3-way valve’s stem nuts and to the service port cap (Refer to page 38).

Valve stem

Stem nut

A (Gas)

B

(liquid)

Manual background Adding Refrigerant

Add refrigerant charge according to table below:

If you use a pipe longer than 5m,

‘15’g of refrigerant R410A must be added for each extra meter.

If you use a pipe shorter than 5m,

The purge time is normal.

Refer to the Service Manual for further details.

• The remaining air in the Refrigeration cycle, which contains moisture, may cause malfunction on the compressor.

• Always contact the service center or a professional installation agency for product installation.

36

Image 36
Contents Page Features of your new air conditioner Cool Summer OfferCost Efficient System Look for EverywhereSafety precautions USING PARTSImportant safety symbols and precautions FOR INSTALLATIONFOR USING FOR POWER SUPPLYDo not pull the power cord, when unplugging the power plug Do not touch the power plug or the circuit breaker with wet handsFOR CLEANING Do not clean the inside of the air conditioner by yourselfDo not place objects or devices under the indoor unit Do not operate the appliance with wet handsChecking before use Operation rangesModel RJ Maintaining your air conditionerPower button Checking the name of the partsMain parts DisplayChecking the remote controller Remote controller buttonsRemote controller display Smart Saver On TimerRemote controller display Battery changing timeStoring the remote controller Turbo indicatorBasic function AutoCool Heatbutton to adjust the temperature Press the button to turn on the air conditionerPress the button to set the operating mode Press theAdjusting the air flow direction Using the Turbo functionPress the Air swingbutton on the remote controller Press the Turbo button on the remote controller during Cool modeWhen the air conditioner is on and in cool/heat mode 1. Press the button on the remote controllermode Temperature and fan speed changes in modeSetting the On/Off timer Setting On timer Setting Off timer1. Press the On Timer/Off Timer button Additional options available in On timer modeUsing the Smart Saver function If the air conditioner is onIf the air conditioner is off Combining On Timer and Off TimerUsing the Quiet function Using the Auto Clean functionPress the Auto Clean button When the air conditioner is turned off When the air conditioner is turned onCleaning the air conditioner Cleaning the indoor unitCleaning the outdoor unit heat exchanger Opening the panelCleaning the air filter Removing the Air filterOpen the panel and put the Air filter out Dry the Air filter in a ventilated areaMaintaining the air conditioner Periodical checksTroubleshooting PROBLEMSOLUTION not work at allError is indicated Noise is generatedflow movement changes. It is normal the outdoor unitINSTALLATION PARTS General informationIncluded Models Choosing the installation location Installing the unitPower supply line, fuse or circuit breaker Indoor unitOutdoor Unit When installing 1 outdoor unit When installing more than 1 outdoor unitSpace Requirements for Outdoor Unit Top viewAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case Fixing the installation plate Optional accessoriesTools required for installation General Tools Tools for test operationsConnecting the assembly cable Cable specificationConnecting the cable Power cableof the electrical contact during a wiring work Installing and connecting the assembly pipe of the indoor unit 10. Connect the grounding conductor to the grounding terminals11. Close the terminal board cover by tightening the screw carefully 2. Smooth the cut edgesPurging the indoor unit Cutting or extending the pipe4. Cut off the remaining foam insulation 6. Pass the pipe through the hole in the wall4. Put a flare nut slightly into the pipe and modify the flare Depth AOuter Diameter Outer Diameter DInstalling and connecting the drain hose of the indoor unit Drain hose installationInstalling and connecting the drain hose of the indoor unit Changing direction of the drain hose1. Detach the rubber cap with the plier 2. Detach the drain hose by pulling it and turning to the leftInstallAA ing and connecting the drain hose of the outdoor unit Purging the connected pipes2. Connect a drain hose to the drain plug 3. Ensure that condensation draining is adequategas service port as seen in the picture Adding RefrigerantIf you use a pipe longer than 5m If you use a pipe shorter than 5mImportant information regulation regarding the refrigerant used Cylinder with siphon1. Please fill in with indelible ink 1975PerfoAA rming the gas leak tests To check for gas leaks on the outdoor unitTo check for gas leaks on the indoor unit Leak test with nitrogen before opening valvesOutdoor unit installed on the wall by rack 6. Attach the pipe to the wall using clamps optionalFixinAA g the indoor unit in place Fixing the outdoor unit in place1. Press the Power button and check the following 4. Press the Power button to stop the operationFinalAA Check and Trial Operation Check the followingsThe compression dimension should be and compress another two points in the same location5. Apply heat to the contraction tube to contract it 6. After tube contraction work is completed, wrap it with theSub PCB installationoptional 1. Turn the power off and take off the front panel of the indoor unit2. Take off the Cover PCB 3. Attach the Sub PCB to the right side of the Panel-frameENGLISH QUESTIONS OR COMMENTS? COUNTRYCALL EEE Yönetmeliğine Uygundur This EEE is compliant with RoHSuser & installation manual Air Conditionerimagine the possibilities AQV07P Series AQV09P Series AQV12P Series AQV18P Series
Related manuals
Manual 41 pages 25.73 Kb Manual 41 pages 25.56 Kb Manual 41 pages 6.72 Kb Manual 45 pages 23.92 Kb Manual 41 pages 27.43 Kb Manual 43 pages 36.93 Kb Manual 43 pages 57.93 Kb Manual 41 pages 20.41 Kb Manual 21 pages 39.04 Kb Manual 21 pages 44.89 Kb Manual 21 pages 49.66 Kb Manual 21 pages 36.79 Kb Manual 21 pages 55.58 Kb Manual 45 pages 44.27 Kb Manual 43 pages 7.81 Kb Manual 43 pages 10.58 Kb Manual 45 pages 17.94 Kb Manual 43 pages 52.7 Kb