 Important information regulation regarding the refrigerant used

1.Please fill in with indelible ink, Important information regulation regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.

Do not vent gases into the atmosphere.

1.Please fill in with indelible ink,

the factory refrigerant charge of the product,

the additional refrigerant amount charged in the field and

+the total refrigerant charge. on the refrigerant charge label supplied with the product.

a. Factory refrigerant charge of the product: see unit name plate

b.Additional refrigerant amount charged in the field (Refer to the above information for the quantity of refrigerant replenishment.)

c.Total refrigerant charge

d.Refrigerant cylinder and manifold for charging

Refrigerant type

GWP value

R410A

1975

GWP=Global Warming Potential

Contains fluorinated greenhouse gases covered by the Kyoto Protocol.

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a

 

 

 

 

 

 

 

 

 

 

Outdoor unit

= (

 

 

) kg

 

 

 

 

 

 

 

= (

 

 

) kg += (

 

) kg

 

 

 

b

 

 

 

 

c

ENGLISH1975

• The filled-out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop valve cover).

Cylinder with siphon Charging the refrigerant under conditions of liquid by using a liquid pipe

R410A is a mixed type of refrigerant. It is necessary for recharging under conditions of liquid. When recharging refrigerant from the refrigerant cylinder to the equipment, follow the instructions below.

1.Before recharging, check whether the cylinder has a siphon or not. There are two ways to recharge the refrigerant.

Cylinder with siphon

Cylinder without siphon

Manual background siphon

Charge the refrigerant standing the

Charge the refrigerant turning the cylinder

cylinder upright.

upside down.

• If R410A refrigerant is charged with gas, the composition of the charged refrigerant changes and the

characteristics of the equipment vary.

During the measuring operation of refrigerant quantity added use an electronic balance.

If cylinder doesn’t have syphon, upset it.

37

Image 37
Contents Page Cool Summer Offer Features of your new air conditionerCost Efficient System Look for EverywhereUSING PARTS Safety precautionsImportant safety symbols and precautions FOR INSTALLATIONFOR POWER SUPPLY FOR USINGDo not pull the power cord, when unplugging the power plug Do not touch the power plug or the circuit breaker with wet handsDo not clean the inside of the air conditioner by yourself FOR CLEANINGDo not place objects or devices under the indoor unit Do not operate the appliance with wet handsOperation ranges Checking before useModel RJ Maintaining your air conditionerChecking the name of the parts Power buttonMain parts DisplayRemote controller buttons Checking the remote controllerRemote controller display Smart Saver On TimerBattery changing time Remote controller displayStoring the remote controller Turbo indicatorAuto Basic functionCool HeatPress the button to turn on the air conditioner button to adjust the temperaturePress the button to set the operating mode Press theUsing the Turbo function Adjusting the air flow directionPress the Air swingbutton on the remote controller Press the Turbo button on the remote controller during Cool mode1. Press the button on the remote controller When the air conditioner is on and in cool/heat modemode Temperature and fan speed changes in modeSetting On timer Setting Off timer Setting the On/Off timer1. Press the On Timer/Off Timer button Additional options available in On timer modeIf the air conditioner is on Using the Smart Saver functionIf the air conditioner is off Combining On Timer and Off TimerUsing the Auto Clean function Using the Quiet functionPress the Auto Clean button When the air conditioner is turned off When the air conditioner is turned onCleaning the indoor unit Cleaning the air conditionerCleaning the outdoor unit heat exchanger Opening the panelRemoving the Air filter Cleaning the air filterOpen the panel and put the Air filter out Dry the Air filter in a ventilated areaPeriodical checks Maintaining the air conditionerPROBLEM TroubleshootingSOLUTION not work at allNoise is generated Error is indicatedflow movement changes. It is normal the outdoor unitGeneral information INSTALLATION PARTSIncluded Models Installing the unit Choosing the installation locationPower supply line, fuse or circuit breaker Indoor unitOutdoor Unit When installing more than 1 outdoor unit When installing 1 outdoor unitSpace Requirements for Outdoor Unit Top viewAccessories in the indoor unit case AccessoriesAccessories in the outdoor unit case Optional accessories Fixing the installation plateTools required for installation General Tools Tools for test operationsCable specification Connecting the assembly cableConnecting the cable Power cableof the electrical contact during a wiring work 10. Connect the grounding conductor to the grounding terminals Installing and connecting the assembly pipe of the indoor unit11. Close the terminal board cover by tightening the screw carefully 2. Smooth the cut edgesCutting or extending the pipe Purging the indoor unit4. Cut off the remaining foam insulation 6. Pass the pipe through the hole in the wallDepth A 4. Put a flare nut slightly into the pipe and modify the flareOuter Diameter Outer Diameter DDrain hose installation Installing and connecting the drain hose of the indoor unitChanging direction of the drain hose Installing and connecting the drain hose of the indoor unit1. Detach the rubber cap with the plier 2. Detach the drain hose by pulling it and turning to the leftPurging the connected pipes InstallAA ing and connecting the drain hose of the outdoor unit2. Connect a drain hose to the drain plug 3. Ensure that condensation draining is adequateAdding Refrigerant gas service port as seen in the pictureIf you use a pipe longer than 5m If you use a pipe shorter than 5mCylinder with siphon Important information regulation regarding the refrigerant used1. Please fill in with indelible ink 1975To check for gas leaks on the outdoor unit PerfoAA rming the gas leak testsTo check for gas leaks on the indoor unit Leak test with nitrogen before opening valves6. Attach the pipe to the wall using clamps optional Outdoor unit installed on the wall by rackFixinAA g the indoor unit in place Fixing the outdoor unit in place4. Press the Power button to stop the operation 1. Press the Power button and check the followingFinalAA Check and Trial Operation Check the followingsand compress another two points in the same location The compression dimension should be5. Apply heat to the contraction tube to contract it 6. After tube contraction work is completed, wrap it with the1. Turn the power off and take off the front panel of the indoor unit Sub PCB installationoptional2. Take off the Cover PCB 3. Attach the Sub PCB to the right side of the Panel-frameENGLISH COUNTRY QUESTIONS OR COMMENTS?CALL EEE Yönetmeliğine Uygundur This EEE is compliant with RoHSAir Conditioner user & installation manualimagine the possibilities AQV07P Series AQV09P Series AQV12P Series AQV18P Series
Related manuals
Manual 41 pages 25.73 Kb Manual 41 pages 25.56 Kb Manual 41 pages 6.72 Kb Manual 45 pages 23.92 Kb Manual 41 pages 27.43 Kb Manual 43 pages 36.93 Kb Manual 43 pages 57.93 Kb Manual 41 pages 20.41 Kb Manual 21 pages 39.04 Kb Manual 21 pages 44.89 Kb Manual 21 pages 49.66 Kb Manual 21 pages 36.79 Kb Manual 21 pages 55.58 Kb Manual 45 pages 44.27 Kb Manual 43 pages 7.81 Kb Manual 43 pages 10.58 Kb Manual 45 pages 17.94 Kb Manual 43 pages 52.7 Kb