Important information regulation regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.
Do not vent gases into the atmosphere.
1.Please fill in with indelible ink,
the factory refrigerant charge of the product,
the additional refrigerant amount charged in the field and
+the total refrigerant charge. on the refrigerant charge label supplied with the product.
a. Factory refrigerant charge of the product: see unit name plate
b.Additional refrigerant amount charged in the field (Refer to the above information for the quantity of refrigerant replenishment.)
c.Total refrigerant charge
d.Refrigerant cylinder and manifold for charging
Refrigerant type | GWP value |
R410A | 1975 |
GWP=Global Warming Potential
Contains fluorinated greenhouse gases covered by the Kyoto Protocol.
Indoor unit
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| ||
|
|
|
|
|
|
| |||
|
|
|
|
|
| d |
| |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
a |
|
|
|
|
|
|
| ||
|
|
| Outdoor unit | ||||||
= ( |
|
| ) kg |
|
|
| |||
|
|
|
| ||||||
= ( |
|
| ) kg += ( |
| ) kg | ||||
|
|
| |||||||
b |
|
|
|
| c |
ENGLISH
• The
Charging the refrigerant under conditions of liquid by using a liquid pipe
R410A is a mixed type of refrigerant. It is necessary for recharging under conditions of liquid. When recharging refrigerant from the refrigerant cylinder to the equipment, follow the instructions below.
1.Before recharging, check whether the cylinder has a siphon or not. There are two ways to recharge the refrigerant.
Cylinder with siphon | Cylinder without siphon |
siphon
Charge the refrigerant standing the | Charge the refrigerant turning the cylinder |
cylinder upright. | upside down. |
• If R410A refrigerant is charged with gas, the composition of the charged refrigerant changes and the
characteristics of the equipment vary.
•During the measuring operation of refrigerant quantity added use an electronic balance.
If cylinder doesn’t have syphon, upset it.
37