Samsung AR24HVSDEWKXMG Connecting the assembly cable, Cable specification, Connecting the cable

Page 44

Connecting the assembly cable

Cable specification

Model

Power cable

Interconnection cable

Type GL

 

 

 

 

18/24

3G x 2.5 mm², H07RN-F

3G x 1.0 mm², H07RN-F

25 A

2 x 0.75 mm², H05RN-F

 

 

 

 

 

 

 

• Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to the power supply, it must be incorporated in a wire with a contact opening of ≥3 mm.

Use shield cable (Category 5; less than 50pF/m) for noisy environmental site.

Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord. (Code designation IEC: 60245 IEC 66/CENELEC: H07RN-F, IEC: 60245 IEC 57/CENELEC: H05RN-F)

Connecting the cable

Electrical work

(1)For electrical and earth works, comply with the‘technical standards of electrical installations’and the the‘wiring regulations’of the Local wiring regulations.

(2)Tighten the terminal block screw to 1.2~1.8 N•m (1.2~1.8 kgf•cm).

(3)Precautions when connecting terminal blocks of the indoor unit

Before connecting, make sure the connecting part of the terminal socket is facing upwards.

Upside down

The terminal

There is no ring

socketis damaged.

terminalto cover the wire.

 

There must be no space between the terminal and the screw when connected.

- Any remaining space may become a fire hazard due to overheating of the electrical contact.

 

 

Either the screw is not fitted

The terminal socket

properly or there is a space between

is upside down.

the screw and the ring terminal.

• For the terminal block wiring, use a wire with a ring terminal socket only.

Regular wires without a ring terminal socket may become a fire hazard due to overheating of the electrical contact during

a wiring work.

When you install the unit, make first refrigerant connections and then electrical connections. Connect the air conditioner to grounding system before performing the electrical connection. If unit is uninstalled, first disconnect electrical cables, then refrigerant connections.

If the outdoor unit is more than 5 meters away from the indoor unit, you must extend the cable. The maximum length of the cable is 30(18/24) meters.

English-44

MG_BETTER_INV_A3050_IB&IM_EN_DB68-05191A_UX.indd 44

2/17/2015 2:49:54 PM

Image 44
Contents Air Conditioner DB68-05191A-02Features of your new air conditioner Contents Safety precautions English-4English-5 01epPr arationFor Using English-6English-7 Do not place objects or devices under the indoor unit English-8For Cleaning English-9English-10 Checking before useOperation ranges Technical Specifications English-11Wi-Fi indicator Timer / Auto Clean indicator Checking the name of the partsMain parts DisplayEnglish-13 Checking the remote controllerRemote controller buttons Remote controller display Low Battery warningStoring the remote controller Inserting the batteriesBasic function English-16 Press the button to adjust the temperaturePress the button to set the desired fan speed Adjusting the air flow direction Remote controller displayRemote controller displayEnglish-17 Vertical air flow Horizontal air flowSetting the On/Off timer Setting the On timerWhen the air conditioner is off FfPress the Timer button select On press the or button Setting the Off timer English-19Er03mti ButtonEnglish-20 Additional options available in modeMode When the air conditioner is operating in Cool mode Step cooling functionEnglish-21 Press the Options buttonUsing the Fast function Using the Comfort functionWhen the air conditioner is operating in Cool/Heat mode English-22Using the Single user function English-23English-24 Using the Quiet functionMake the Quiet indicator blink and press the SET button Using the Virus Doctor function When the air conditioner is operatingWhen the air conditioner is not in operation Make the indicator blink and press the SET buttonChecking the power consumption Using the Auto clean functionLighting in Auto clean mode Make the Clean indicator blink and press the SET buttonSetting the Beep sound Resetting the Filter clean reminderSetting the Display option English-27Using the Smart A/C application English-28Cleaning the air conditioner Cleaning the indoor unitCleaning the outdoor unit heat exchanger English-29Cleaning the Air filter Removing the Air filterEnglish-30 Remove the Air filter from the main bodyTop of the Air filter into the main body.. ➀ Reassembling the Air filterEnglish-31 Maintaining the air conditioner English-32Troubleshooting TemperatureAdjustment is not English-33Button or disconnect the power plug/switch Check the Drains have been cleared Regular MaintenanceError is indicated Heard when refrigerant flow movement changes. It is normal07stin llan atio General informationEnglish-35 Choosing the installation location Installing the unitPower supply line, fuse or circuit breaker Indoor unitWhere sulfide gas exists Outdoor UnitEnglish-37 Reduce noise and vibrationWhen installing more than 1 outdoor unit When the air outlet is towards the wallEnglish-38  Figure DescriptionAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case English-39Fixing the installation plate Optional accessoriesTools required for installation General Tools Tools for test operationsAssembling the hanger screw English-41This QR code for detail video of indoor unit installation Removing the screwsRemoving the Cover panel Before mounting the indoor unit English-42Assembling the Cover panel After mounting the indoor unit English-43Connecting the assembly cable Cable specificationConnecting the cable English-44English-45 Extend the assembly cable if necessaryEach wire is labeled with the corresponding terminal number English-46 Smooth the cut edgesCut off the remaining foam insulation TorqueEvacuating the indoor unit Cutting or extending the pipeEnglish-47 Unscrew the caps at the end of each pipeEnglish-48 Correct InclinedCracked Flare nutDrain hose installation English-49Change the direction only when it is necessary Changing direction of the drain hoseEnglish-50 Check for leakage on both side of the drain outletEvacuating the connected pipes English-51Outer Torque Outdoor unit Indoor unitAdding Refrigerant English-52Cylinder with siphon If you use a pipe longer than 5 mPerforming the gas leak tests English-53Outdoor unit installed on the wall by rack Fixing the outdoor unit in placeEnglish-54 660 340Smart Install mode English-55English-56 Off / Blinking / OnFinal check and trial operation English-57Packing and unpacking guide English-58How to connect your extended power cables English-59Apply heat to the contraction tube to contract it Atio After tube contraction work is completed, wrap it withQuestions or COMMENTS? 021-8255 CE