Performing the gas leak tests

Make sure to check for gas leaks before completing the installation process (connecting the assembly pipe and hose between indoor unit and outdoor unit, insulating the cables, hose and pipe, and fixing the indoor unit to the installation plate).

A C D

B

07stin llan atio

Test part for outdoor unit

Tightening torque for body cap (Refer to the table)

Spindle

Charging core

R-22: Diameter of the screw - 7/16-20UNF

R-410A: Diameter of the screw - 1/2-20UNF

Tightening torque for charging port cap (Refer to the table)

Test part for indoor unit

Before inspecting the leakage, use a torque wrench to close the cap for the service valve. (Comply with a tightening torque for each size of the diameter,and tighten the cap firmly to prevent any leakage.).

To check for any possible leakage, insert inert gas into the pipes connected to indoor/outdoor units and check the connection part of the indoor/outdoor units with soap lather or liquid for leakage test.

Outer

Tightening torque

Diameter

Body cap (N•m)

Charging port cap

(mm)

(N•m)

 

ø 6.35

20 ~ 25

 

ø 9.52

20 ~ 25

 

ø12.70

25 ~ 30

10 ~ 12

ø15.88

30 ~ 35

 

ø19.05

35 ~ 40

 

To check for gas leaks on the outdoor unit,

( 1 N•m = 10 kgf•cm )

Check the valve A and B using a leak detector.

 

To check for gas leaks on the indoor unit,

 

Check the flare nut C and D using a leak detector.

 

Leak test with nitrogen (before opening valves)

In order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the R-410A.

Leak test (after opening valves)

Before opening valves, discharge all the nitrogen from the system and create vacuum according to page 51~52. After opening valves, check leaks using a leak detector for refrigerant.

Pump down (before disconnecting the refrigerant connections for unit repair, removal or disposal) Pump-down is an operation intended to collect all the system refrigerant in the outdoor unit.

This operation must be carried out before disconnecting the refrigerant tubing in order to avoid refrigerant loss to the atmosphere.

Shut off the liquid valve with the Allen wrench.

Turn the system on in cooling with fan operating at high velocity.

(Compressor will immediately start, provided 3 minutes have elapsed since the last stop).

After 2 minutes of operation, shut the suction valve with the same wrench.

Turn the system off and switch mains supply off.

Disconnect tubing. After disconnection, protect valves and tubing ends from dust.

Compressor damage may occur if run at a negative suction pressure.

English-53

MG_BETTER_INV_A3050_IB&IM_EN_DB68-05191A_UX.indd 53

2/17/2015 2:50:28 PM

Image 53
Contents DB68-05191A-02 Air ConditionerFeatures of your new air conditioner Contents English-4 Safety precautions01epPr aration English-5English-6 For UsingEnglish-7 English-8 Do not place objects or devices under the indoor unitEnglish-9 For CleaningEnglish-10 Checking before useOperation ranges English-11 Technical SpecificationsChecking the name of the parts Wi-Fi indicator Timer / Auto Clean indicatorMain parts DisplayEnglish-13 Checking the remote controllerRemote controller buttons Low Battery warning Remote controller displayStoring the remote controller Inserting the batteriesBasic function English-16 Press the button to adjust the temperaturePress the button to set the desired fan speed Remote controller displayRemote controller display Adjusting the air flow directionEnglish-17 Vertical air flow Horizontal air flowSetting the On timer Setting the On/Off timerWhen the air conditioner is off FfPress the Timer button select On press the or button English-19 Setting the Off timerEr03mti ButtonEnglish-20 Additional options available in modeMode Step cooling function When the air conditioner is operating in Cool modeEnglish-21 Press the Options buttonUsing the Comfort function Using the Fast functionWhen the air conditioner is operating in Cool/Heat mode English-22English-23 Using the Single user functionEnglish-24 Using the Quiet functionMake the Quiet indicator blink and press the SET button When the air conditioner is operating Using the Virus Doctor functionWhen the air conditioner is not in operation Make the indicator blink and press the SET buttonUsing the Auto clean function Checking the power consumptionLighting in Auto clean mode Make the Clean indicator blink and press the SET buttonResetting the Filter clean reminder Setting the Beep soundSetting the Display option English-27English-28 Using the Smart A/C applicationCleaning the indoor unit Cleaning the air conditionerCleaning the outdoor unit heat exchanger English-29Removing the Air filter Cleaning the Air filterEnglish-30 Remove the Air filter from the main bodyTop of the Air filter into the main body.. ➀ Reassembling the Air filterEnglish-31 English-32 Maintaining the air conditionerTemperature TroubleshootingAdjustment is not English-33Check the Drains have been cleared Regular Maintenance Button or disconnect the power plug/switchError is indicated Heard when refrigerant flow movement changes. It is normal07stin llan atio General informationEnglish-35 Installing the unit Choosing the installation locationPower supply line, fuse or circuit breaker Indoor unitOutdoor Unit Where sulfide gas existsEnglish-37 Reduce noise and vibrationWhen the air outlet is towards the wall When installing more than 1 outdoor unitEnglish-38  Figure DescriptionAccessories in the indoor unit case AccessoriesAccessories in the outdoor unit case English-39Optional accessories Fixing the installation plateTools required for installation General Tools Tools for test operationsEnglish-41 Assembling the hanger screwRemoving the screws This QR code for detail video of indoor unit installationRemoving the Cover panel Before mounting the indoor unit English-42English-43 Assembling the Cover panel After mounting the indoor unitCable specification Connecting the assembly cableConnecting the cable English-44English-45 Extend the assembly cable if necessaryEach wire is labeled with the corresponding terminal number Smooth the cut edges English-46Cut off the remaining foam insulation TorqueCutting or extending the pipe Evacuating the indoor unitEnglish-47 Unscrew the caps at the end of each pipeCorrect Inclined English-48Cracked Flare nutEnglish-49 Drain hose installationChanging direction of the drain hose Change the direction only when it is necessaryEnglish-50 Check for leakage on both side of the drain outletEnglish-51 Evacuating the connected pipesOuter Torque Outdoor unit Indoor unitEnglish-52 Adding RefrigerantCylinder with siphon If you use a pipe longer than 5 mEnglish-53 Performing the gas leak testsFixing the outdoor unit in place Outdoor unit installed on the wall by rackEnglish-54 660 340English-55 Smart Install modeOff / Blinking / On English-56English-57 Final check and trial operationEnglish-58 Packing and unpacking guideEnglish-59 How to connect your extended power cablesApply heat to the contraction tube to contract it Atio After tube contraction work is completed, wrap it with021-8255 CE Questions or COMMENTS?