Safety information on outdoor unit power supply
ffPower cable must be hard chloroprene synthetic rubber or better, which is certified with safety certification (60245 KS IEC 66).
Type of outdoor unit power supply
ffComply with tightening torque to make sure that the screws do not get loose.
ENGLISH
Screw | Torque | ||
|
| ||
kgf•cm | N•m | ||
| |||
|
|
| |
M4 | 25~40 | 2.5~4.0 | |
|
|
|
Outdoor unit
Communication cable
Cable clamp
Electrical parts (Power part)
L | N | Cabinet panel |
|
| Earth |
|
| OFF |
Earth |
|
|
Indoor/outdoor unit communication cable
Indoor/outdoor unit power cable
ffBefore connecting, compressed part of the terminal should face upward.
Installed back to front. | Compressed part is cut. Ring terminal is detached. |
ffAfter tightening, there should be no gap between a terminal and a screw.
Cable clamp | Earth |
Power cable
•The figure of an outdoor unit may be different depending on models.
Terminal is tightened | A screw is not tightened firmly or there is a gap |
back to front. | between a screw and ring terminal. |
• When connecting the cables to the outdoor unit, reversing the connection of power and communication cable
CAUTION | or connecting the earth wire incorrectly, electric leakage or product malfunction may occur. |
|
•Do not cut or modify the supplied cable and install it.
•There is no front and back for the communication cable, so it can be switched.
•Use solderless ring terminal to connect the power cable to the power terminal block. If you connect stranded or solid wires without solderless ring terminal, heat may generate from the connected part and cause fire.