Check and test operation
1.Supply power to the air conditioner.
2.Turn on the air conditioner.
3. While pressing and holding the Set/Cancel button on the remote controller, press the Power button for 3 seconds to display the temperature of indoor heat exchanger.
4.Press the Turbo button on the remote controller to operate in turbo mode for 10 minutes.
5.Check if the indoor unit is operating normally.
6. While pressing and holding the Set/Cancel button on the remote controller, press the Power button for 3 seconds to display the temperature of indoor heat exchanger.
7. When checking above step 1~6 is done, tell the user how to use the air conditioner.
ENGLISH
Pump down procedure (When removing the product)
1.Press the Power button on the indoor unit control panel for 5 seconds to enter the Pump down mode and operate the compressor for over 5 minutes. Or, Press the Set/Cancel, Mode and Temp - button on the remote controller simultaneously to enter the Pump down mode and operate the compressor for over 5 minutes.
2.Remove the High/Low pressure side valve cap.
3.Use the L wrench to completely close the valve on the high pressure side.
4.After 2 minutes, completely close the valve on the low pressure side.
5.Press the Power button on the indoor unit control panel for 5 seconds to deactivate the Pump down mode. Or, Press the Set/Cancel, Mode and Temp - button on the remote controller simultaneously to deactivate the Pump down mode.
6.Disconnect the pipe.
53
칠레향 FAC MEMORY 냉난방_IBIM_EN_03892A(5).indd 53 |