Samsung AR18KQJSBWKXMG, AR18MQJSBWKXMG Evacuating the air, Leave the system in the standby mode

Page 47

Control box

Remove the screw for the control box cover

Remove the gas and liquid

For connecting the

service port caps

refrigerant pipes

Gas service port <Low pressure>

CAUTION

When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor first before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works with the stop valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high. It may cause explosion and injury.

1Leave the system in the standby mode.

WARNING

Do not turn on the system! This is necessary for better vacuum operation (full OPEN position of Electronic Expansion Valve).

2Connect the charging hose of the low pressure side of manifold gauge to a gas service port as seen in the picture.

Installation

 

3

Liquid service port

Valve

Connect the gas and liquid

<High pressure>

refrigerant pipes

Step 3.3 Evacuating the air

The outdoor unit is loaded with sufficient R-410A refrigerant. Do not vent R-410A into atmosphere: it is a fluorinated greenhouse gas, covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 2088. You should evacuate the air in the indoor unit and in the pipe. If air remains in the refrigerant pipes, it affects the compressor. It may cause reduction

of cooling capacity and malfunction. Use a vacuum pump.

15 minutes

4

Vacuum

Pump (Backward ￿owing prevention)

Liquid service port <Low pressure>

5

Liquid service port <High pressure>

46English

Image 47 Contents
Questions or COMMENTS? DB68-06070A-01 AirconditionerContents Correct Disposal of This Product This may result in electric shock or fire Safety InformationFailing to do so may result in electric shock or fire For Power Supply This may result in children seriously injuring themselves Do not touch the circuit breakerwith wet handsThis may result in electric shock This may result in electric shock or burnsDo not touch the pipes connected with the product Do not place objects or devices under the indoor unitDo not operate the appliance with wet hands Do not drink the water from the air conditionerDo not clean the inside of the air conditioner by yourself For CleaningDisplay Operation indicatorSingle user indicator Indoor Unit OverviewInserting batteries Remote Control OverviewOperation modes Remote Control OperationControlling temperature Controlling air flow direction Controlling fan speedStep cooling function Cool modeCooling Operation Dehumidifying Operation Dry modeHeating Operation Heat modeFan mode Quick Smart FeaturesAuto mode Fast function Beep sound function Comfort functionSingle user function Energy-Saving OperationTimed on/Timed off function Good’sleep function Default operation time for the good’sleep functionDo not clean the display by using alkaline detergent Cleaning at a GlanceRunning Auto clean Cleaning duration minutesCleaning the filter Troubleshooting Does not work Indicator blinksCheck whether the drains are clean. Clean them regularly To pass the error code to the service centre24˚C Technical Specifications35˚C Model AR24KRJSRWK/MG AR18MRJSBWK/MG AR18MQJSBWK/MG Model AR24MRJSRWK/MG General information Safety Information on InstallationInstallation of the unit Install the unit in a place where water can drain smoothly Power supply line, fuse, or circuit breakerMinimum clearances for the outdoor unit Choosing the installation locationPreparation Outdoor unit Packing and UnpackingIndoor unit Optional accessories Checking and preparing accessories and tools AccessoriesAccessories in the indoor unit package Tools Accessories in the outdoor unit packageDrilling a hole through the wall Taping the pipes, cables, and drain hose Remove the cap screws, then the screws Indoor Unit InstallationDisassembling the installation plate Disassembling the cover panelConnecting the cables assembly cable Apply heat to the contraction tube to contract it Optional Extending the power cableCompression dimension should be Prepare the following toolsOptional Extending the drain hose Installing and connecting the drain hoseIncomplete wire Install the drain hoseOptional Changing the direction of the drain hose Depth a Shortening or extending the refrigerant pipes assembly pipeWhen fixing the indoor unit on a window frame 10 Fixing the installation plateWhen fixing the indoor unit on a wall 12 Assembling the cover panel 11 Fixing the indoor unit to the installation plateWhen fixing the indoor unit on a gypsum board Fix the installation plate without inclining to one sideOptional Fixing the outdoor unit to a wall with a rack Outdoor Unit InstallationConnecting the cables and the refrigerant pipes Fixing the outdoor unit in placeCooling capacity and malfunction. Use a vacuum pump Leave the system in the standby modeEvacuating the air Siphon Adding refrigerantPerforming the gas leak tests Installation InspectionRunning the Smart Install mode Blocking error Open Error indicatorError Measures for the installer to take Display Motor Connector Remove foreign substance. CheckPumping down refrigerant Check the following Strength of the installation siteTurn on th air conditioner and select Fast Cool mode Performing final check and trial operation