When error occurs, take necessary measures by referring to the following table. For more information on necessary measures for errors, refer to the service manual.
| Error indicator |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| LED Display |
| Error | Measures for the installer to take | |
Display |
| LED 1 | LED 2 | LED 3 | ||||
|
|
| ||||||
|
|
|
|
| / | / |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Communication | • Check the connection wire |
|
|
|
|
|
|
| error between | between the indoor and outdoor |
|
|
|
|
|
|
| units (whether the power cable or | |
|
|
|
|
|
|
| indoor and | |
|
|
|
|
|
|
| communication cable is crossed or | |
|
|
|
|
|
|
| outdoor units | not). |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Error on indoor | • Check the connection of the |
|
|
|
|
|
|
| temperature | connector. |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| sensor |
|
|
|
|
|
|
|
|
|
|
, |
|
|
|
|
|
| Error on indoor | • Check the connection of the |
|
|
|
|
|
| heat exchanger | connector. | |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Error on indoor fan | • Check the connection of the |
|
|
|
|
|
|
| motor | connector. |
|
|
|
|
|
|
| • Remove foreign substance. (Check | |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| for the cause that restrains motor.) |
|
|
|
|
|
|
|
|
|
display |
|
|
|
|
|
| EEPROM/Option | • |
and all LEDs |
|
|
|
|
| error |
| |
blink. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
, |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Refrigerant flow | • Check if the stop valve is completely |
|
|
|
|
|
|
| blocking error | open. |
|
|
|
|
|
|
| • Check if there is any blockage in the | |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| refrigerant pipe which connects the |
|
|
|
|
|
|
|
| indoor and outdoor units. |
|
|
|
|
|
|
|
| • Check for refrigerant leak. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Lack of refrigerant | • Check if a sufficient amount of |
|
|
|
|
|
|
| (for inverter | refrigerant is additionally charged |
|
| ❈ This LED pattern |
| for the pipe longer than specified in | ||||
|
|
| models only) | |||||
|
|
| piping codes and standards. | |||||
|
|
| appears when an |
| • Check for refrigerant leak between | |||
|
|
| error occurs on the |
| ||||
|
|
|
| valve and pipe connection. | ||||
|
|
| outdoor unit. |
|
| |||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
❈ : Off, : Blinking, : On
Installation
English 49