Samsung AR18KRJSBWKNMG, AR18MQJSBWKXMG, AR18MRJSBWKXMG, AR18MRJSBWKNMG Adding refrigerant, Siphon

Page 48

3Open the valve of the low pressure side of manifold gauge anticlockwise.

4Evacuate the air in the connected pipes using the vacuum pump for about 15 minutes.

Make sure that pressure gauge shows -0.1 MPa (-76 cmHg, 5 torr) after about 10 minutes. This procedure is very important to avoid a gas leak.

Close the valve of the low pressure side of manifold gauge clockwise.

Turn off the vacuum pump.

Check for 2 minutes if there is any pressure change.

Remove the hose of the low pressure side of manifold gauge.

5Set a valve cork of liquid and gas service port to the open position.

Step 3.4 Adding refrigerant

If you use a pipe longer than the length specified in the piping codes and standards, you must add 20 g (for ✴✴18/24✴✴) of refrigerant R-410A for each extra metre. If you use a pipe shorter than the length specified in the piping codes and standards, the evacuating time is normal. Refer to the Service Manual for further details.

CAUTION

The remaining air in the Refrigeration cycle, which contains moisture, may cause malfunction of the compressor.

Always contact the service centre or a professional installation agency for product installation.

R-410A is a mixed type of refrigerant. It is necessary for recharging under conditions of liquid. When recharging refrigerant from the refrigerant cylinder to the equipment, take the following instructions:

Before recharging, check whether the cylinder has a siphon or not. There are two ways to recharge the refrigerant:

 

 

Siphon

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Charge the refrigerant

Charge the refrigerant turning

standing the cylinder upright.

the cylinder upside down.

<Cylinder with siphon>

<Cylinder without siphon>

NOTE

If R-410A refrigerant is charged with gas, the composition of the charged refrigerant changes and the characteristics of the equipment vary.

During the measuring operation of refrigerant quantity added, use electronic scales. If cylinder doesn't have siphon, upset it.

Installation

English 47

Image 48
Contents Questions or COMMENTS? Airconditioner DB68-06070A-01Contents Correct Disposal of This Product Safety Information Failing to do so may result in electric shock or fireThis may result in electric shock or fire For Power Supply Do not touch the circuit breakerwith wet hands This may result in electric shockThis may result in electric shock or burns This may result in children seriously injuring themselvesDo not place objects or devices under the indoor unit Do not operate the appliance with wet handsDo not drink the water from the air conditioner Do not touch the pipes connected with the productFor Cleaning Do not clean the inside of the air conditioner by yourselfOperation indicator Single user indicatorIndoor Unit Overview DisplayRemote Control Overview Inserting batteriesRemote Control Operation Controlling temperatureOperation modes Controlling fan speed Controlling air flow directionCool mode Cooling OperationStep cooling function Dry mode Dehumidifying OperationHeat mode Heating OperationQuick Smart Features Auto modeFan mode Fast function Comfort function Beep sound functionEnergy-Saving Operation Single user functionTimed on/Timed off function Default operation time for the good’sleep function Good’sleep functionCleaning at a Glance Running Auto cleanCleaning duration minutes Do not clean the display by using alkaline detergentCleaning the filter Troubleshooting Indicator blinks Check whether the drains are clean. Clean them regularlyTo pass the error code to the service centre Does not workTechnical Specifications 35˚C24˚C Model AR24KRJSRWK/MG AR18MRJSBWK/MG AR18MQJSBWK/MG Model AR24MRJSRWK/MG Safety Information on Installation Installation of the unitGeneral information Power supply line, fuse, or circuit breaker Install the unit in a place where water can drain smoothlyChoosing the installation location PreparationMinimum clearances for the outdoor unit Packing and Unpacking Indoor unitOutdoor unit Checking and preparing accessories and tools Accessories Accessories in the indoor unit packageOptional accessories Accessories in the outdoor unit package Drilling a hole through the wallTools Taping the pipes, cables, and drain hose Indoor Unit Installation Disassembling the installation plateDisassembling the cover panel Remove the cap screws, then the screwsConnecting the cables assembly cable Optional Extending the power cable Compression dimension should bePrepare the following tools Apply heat to the contraction tube to contract itInstalling and connecting the drain hose Incomplete wireInstall the drain hose Optional Extending the drain hoseOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe Depth a10 Fixing the installation plate When fixing the indoor unit on a wallWhen fixing the indoor unit on a window frame 11 Fixing the indoor unit to the installation plate When fixing the indoor unit on a gypsum boardFix the installation plate without inclining to one side 12 Assembling the cover panelOutdoor Unit Installation Connecting the cables and the refrigerant pipesFixing the outdoor unit in place Optional Fixing the outdoor unit to a wall with a rackLeave the system in the standby mode Evacuating the airCooling capacity and malfunction. Use a vacuum pump Adding refrigerant SiphonInstallation Inspection Running the Smart Install modePerforming the gas leak tests Error indicator Error Measures for the installer to take DisplayMotor Connector Remove foreign substance. Check Blocking error OpenCheck the following Strength of the installation site Turn on th air conditioner and select Fast Cool modePerforming final check and trial operation Pumping down refrigerant
Related manuals
Manual 52 pages 44.65 Kb