Samsung AR24KRJSRWKXMG, AR18MQJSBWKXMG, AR18MRJSBWKXMG manual Connecting the cables assembly cable

Page 39

Installation

Step 2.3 Connecting the cables (assembly cable)

Control box

Before

 

 

 

connecting

 

 

 

Correct

Upside down

Damaged

Non-circular

After

 

 

 

connecting

 

 

 

Correct

Correct

Upside down

Non-fitted

(Front view)

(Side view)

 

 

 

<Circular terminal>

 

✴✴18KR/MR✴✴ ✴✴18KQ/MQ✴✴ ✴✴24✴✴

N(1)

1

N(1)

1

2

3

N(1)

1

2

Fasten the screws for the wire holders.

Model

✴✴18KR/MR✴✴

✴✴18KQ/MQ✴✴

✴✴24✴✴

Power cable

 

 

 

(Indoor

3G X 2.5 mm², H05VV-F

unit)

 

 

 

Indoor-to-

 

3G X 2.5 mm²,

 

3G X 2.5 mm²,

H07RN-F,

4G X 2.5 mm²,

Outdoor

H07RN-F

2G x 0.75 mm²

H07RN-F

power cable

 

H05RN-F

 

 

 

 

 

 

 

 

Type GL

25A

25A

25A

 

 

 

 

When performing electrical and earthing works, be sure to comply with the 'technical standards of electrical installations' and the 'wiring regulations' in the local regulations.

Tighten the terminal block screw to 1.2-1.8 N•m (1.2-1.8 kgf•cm).

NOTE

Each wire is labelled with the corresponding terminal number.

Use shield cable (Category 5; less than 50pF/m) for noisy environmental site.

Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord. Code designation IEC: 60227 IEC53/CENELEC: H05VV-F, IEC: 60245 IEC66/CENELEC:H07RN-F,IEC: 60245 IEC 57/CENELEC: H05RN-F)

Power & Communication cable shall not exceed 30m.

CAUTION

For the terminal block wiring, use a wire with a ring terminal socket only. Regular wires without a ring terminal socket may become a hazard due to overheating of the electrical contact during installation.

If you need to extend the pipe, be sure to extend the cable, too. The maximum length of each of the cable and pipe used should not exceed 15 metres (✴✴18✴✴) and 20 metres (✴✴24✴✴).

Do not connect two or more different cables to extend the length. This connection may cause fire.

Each circular terminal must match the size of its corresponding screw in the terminal block.

After connecting the cables, make sure that terminal numbers on the indoor and outdoor units match.

Ensure that power and communication cables are separated, they must not be in the same cable.

WARNING

Connect the wires firmly so that wires cannot be pulled out easily. (If they are loose, it could cause burn-out of the wires.)

38English

Image 39 Contents
Questions or COMMENTS? DB68-06070A-01 AirconditionerContents Correct Disposal of This Product Safety Information Failing to do so may result in electric shock or fireThis may result in electric shock or fire For Power Supply This may result in children seriously injuring themselves Do not touch the circuit breakerwith wet handsThis may result in electric shock This may result in electric shock or burnsDo not touch the pipes connected with the product Do not place objects or devices under the indoor unitDo not operate the appliance with wet hands Do not drink the water from the air conditionerDo not clean the inside of the air conditioner by yourself For CleaningDisplay Operation indicatorSingle user indicator Indoor Unit OverviewInserting batteries Remote Control OverviewRemote Control Operation Controlling temperatureOperation modes Controlling air flow direction Controlling fan speedCool mode Cooling OperationStep cooling function Dehumidifying Operation Dry modeHeating Operation Heat modeQuick Smart Features Auto modeFan mode Fast function Beep sound function Comfort functionSingle user function Energy-Saving OperationTimed on/Timed off function Good’sleep function Default operation time for the good’sleep functionDo not clean the display by using alkaline detergent Cleaning at a GlanceRunning Auto clean Cleaning duration minutesCleaning the filter Troubleshooting Does not work Indicator blinksCheck whether the drains are clean. Clean them regularly To pass the error code to the service centreTechnical Specifications 35˚C24˚C Model AR24KRJSRWK/MG AR18MRJSBWK/MG AR18MQJSBWK/MG Model AR24MRJSRWK/MG Safety Information on Installation Installation of the unitGeneral information Install the unit in a place where water can drain smoothly Power supply line, fuse, or circuit breakerChoosing the installation location PreparationMinimum clearances for the outdoor unit Packing and Unpacking Indoor unitOutdoor unit Checking and preparing accessories and tools Accessories Accessories in the indoor unit packageOptional accessories Accessories in the outdoor unit package Drilling a hole through the wallTools Taping the pipes, cables, and drain hose Remove the cap screws, then the screws Indoor Unit InstallationDisassembling the installation plate Disassembling the cover panelConnecting the cables assembly cable Apply heat to the contraction tube to contract it Optional Extending the power cableCompression dimension should be Prepare the following toolsOptional Extending the drain hose Installing and connecting the drain hoseIncomplete wire Install the drain hoseOptional Changing the direction of the drain hose Depth a Shortening or extending the refrigerant pipes assembly pipe10 Fixing the installation plate When fixing the indoor unit on a wallWhen fixing the indoor unit on a window frame 12 Assembling the cover panel 11 Fixing the indoor unit to the installation plateWhen fixing the indoor unit on a gypsum board Fix the installation plate without inclining to one sideOptional Fixing the outdoor unit to a wall with a rack Outdoor Unit InstallationConnecting the cables and the refrigerant pipes Fixing the outdoor unit in placeLeave the system in the standby mode Evacuating the airCooling capacity and malfunction. Use a vacuum pump Siphon Adding refrigerantInstallation Inspection Running the Smart Install modePerforming the gas leak tests Blocking error Open Error indicatorError Measures for the installer to take Display Motor Connector Remove foreign substance. CheckPumping down refrigerant Check the following Strength of the installation siteTurn on th air conditioner and select Fast Cool mode Performing final check and trial operation
Related manuals
Manual 51 pages 22.32 Kb