Samsung AR24JRSDBWKNMG Connecting the assembly cable, Cable specification, Connecting the cable

Page 42

Connecting the assembly cable

Cable specification

Model

Power cable

Interconnection cable

Type GL

 

 

 

 

18

3G x 2.5 mm², H05VV-F

4G x 1.5 mm², H07RN-F

25 A

24

3G x 2.5 mm², H05VV-F

4G x 2.5 mm², H07RN-F

25 A

• Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to the power supply, it must be incorporated in a wire with a contact opening of ≥3 mm.

Use shield cable (Category 5; less than 50pF/m) for noisy environmental site.

Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord. (Code designation IEC: 60227 IEC53 / CENELEC:H05VV-F, IEC: 60245 IEC 66/CENELEC: H07RN-F)

Connecting the cable

Electrical work

(1)For electrical and earth works, comply with the‘technical standards of electrical installations’and the the‘wiring regulations’of the Local wiring regulations.

(2)Tighten the terminal block screw to 1.2 ~1.8 N•m (12 ~18 kgf•cm).

(3)Precautions when connecting terminal blocks of the indoor unit.

Before connecting, make sure the connecting part of the terminal socket is facing upwards.

Upside down

The terminal

There is no ring

socketis damaged.

terminalto cover the wire.

 

There must be no space between the terminal and the screw when connected.

- Any remaining space may become a fire hazard due to overheating of the electrical contact.

 

 

Either the screw is not fitted

The terminal socket

properly or there is a space between

is upside down.

the screw and the ring terminal.

• For the terminal block wiring, use a wire with a ring terminal socket only.

Regular wires without a ring terminal socket may become a fire hazard due to overheating of the electrical contact during

a wiring work.

When you install the unit, make first refrigerant connections and then electrical connections. Connect the air conditioner to grounding system before performing the electrical connection. If unit is uninstalled, first disconnect electrical cables, then refrigerant connections.

If the outdoor unit is more than 4 meters(24) or 5 meters(18) away from the indoor unit, you must extend the cable. The maximum length of the cable is 15(18) / 20(24) meters.

English-42

MG_BETTER_ON&OFF_A3050_IB&IM_DB68-05189A.indd 42

2/17/2015 2:56:55 PM

Image 42
Contents Air Conditioner Features of your new air conditioner Contents Safety precautions English-4English-5 01epPr arationFor Using English-6English-7 Do not place objects or devices under the indoor unit English-8For Cleaning English-9Checking before use Operation rangesEnglish-10 Technical Specifications English-11Display Checking the name of the partsMain parts English-12Checking the remote controller Remote controller buttonsEnglish-13 Storing the remote controller Remote controller displayLow Battery warning Inserting the batteriesBasic function Press the button to adjust the temperature Press the button to set the desired fan speedEnglish-16 Adjusting the air flow direction English-17FfPress the Timer button select On press the or button  Setting the On/Off timerSetting the On timer English-18Er03mti Setting the Off timerEnglish-19 ButtonAdditional options available in mode ModeEnglish-20 Press the Options button Step cooling functionEnglish-21 04 optioEnglish-22 Using the Fast functionUsing the Comfort function You can set the Comfort function to provide mild coolingCancelled Using the Single user functionSingle user function is only available in Cool mode English-23Using the Virus Doctor function Make the indicator blink and press the SET buttonEnglish-24 English-25 Using the Auto clean functionChecking the usage time SettiSetting the Display option Setting the Beep soundResetting the Filter clean reminder English-26Cleaning the outdoor unit heat exchanger Cleaning the air conditionerCleaning the indoor unit English-27English-28 Cleaning the Air filterRemoving the Air filter Remove the Air filter from the main bodyReassembling the Air filter English-29Top of the Air filter into the main body.. ➀ Maintaining the air conditioner English-30Adjustment is not TroubleshootingTemperature English-31Error is indicated Button or disconnect the power plug/switchCheck the Drains have been cleared Regular Maintenance Heard when refrigerant flow movement changes. It is normalGeneral information English-3307stin llan atio Power supply line, fuse or circuit breaker Choosing the installation locationInstalling the unit Indoor unitEnglish-35 Where sulfide gas existsOutdoor Unit Reduce noise and vibrationEnglish-36 When installing more than 1 outdoor unitWhen the air outlet is towards the wall  Figure DescriptionAccessories in the outdoor unit case AccessoriesAccessories in the indoor unit case English-37Tools required for installation General Tools Fixing the installation plateOptional accessories Tools for test operationsAssembling the hanger screw English-39Removing the Cover panel Before mounting the indoor unit This QR code for detail video of indoor unit installationRemoving the screws English-40Assembling the Cover panel After mounting the indoor unit English-41Connecting the cable Connecting the assembly cableCable specification English-42Extend the assembly cable if necessary Each wire is labeled with the corresponding terminal numberEnglish-43 Cut off the remaining foam insulation English-44Smooth the cut edges TorqueEnglish-45 Evacuating the indoor unitCutting or extending the pipe Unscrew the caps at the end of each pipeEnglish-46 Correct InclinedCracked Drain hose installation English-47English-48 Change the direction only when it is necessaryChanging direction of the drain hose Check for leakage on both side of the drain outletEvacuating the connected pipes English-49Connect a drain hose to the drain plug Adding Refrigerant English-50Outer Torque English-51 Siphon Charge the refrigerant standingCylinder upright Upside down Performing the gas leak tests English-52Outdoor unit installed on the wall by rack Fixing the outdoor unit in placeEnglish-53 Smart Install mode English-54English-55 Off / Blinking / OnFinal check and trial operation English-56Packing and unpacking guide English-57Apply heat to the contraction tube to contract it How to connect your extended power cablesEnglish-58 After tube contraction work is completed, wrap it withEnglish-59 Questions or COMMENTS? 021-8255 CE