Installing and connecting the drain hose of the indoor unit
5cm |
|
less | Ditch |
Keep a clearance of at least | Do not place the end of the |
5 cm between the end of the | drain hose in a hollow. |
drain hose and the ground. |
|
1) Correct connection
After completing the installation of the drain hose, pour water into the drain pan to check whether the hose is well drained.
2) Incorrect connection
07stin llan atio
Drain hose |
|
|
|
|
|
|
|
|
|
|
|
| |
| Pipe | Drain hose | Pipe |
• Don’t tie drain hose to the assembly pipe which may lead to water leakage.
• If the diameter of the connection hose is smaller than the product's drain hose, water leakage may occur.
Drain hose installation
1.If necessary, connect the 2 meter extension drain hose to the drain hose.
2.If you use the extension drain hose, insulate the inside of the extension drain hose with a shield.
3.Fit the drain hose into 1 of 2 drain hose holes, then fix the end of the drain hose tightly with a clamp.
• If you do not use the other drain hose hole, block it with a rubber stopper.
4.When extending the Drain Hose, hold the end of Drain Hose and Extended Hose, rotate and insert the drain hose into Extended hose for 40~45 mm. Make sure the two hoses are firmly connected, there is no water leakage.
Drain hose hole |
5.Connect the Drain Hose after using Foam Insulation to wrap the Extended Hose. Then, Use vinyl tape to wrap the each side of connection by 20 mm .
|
|
| 40~45 mm | 20 mm | 20 mm |
|
|
| or more | or more | |
Drain hose | Extension |
| Extension |
|
|
| drain hose | Drain hose |
|
| |
|
| drain hose | Vinyl Tape | Foam Insulation | |
|
|
|
|
English-47