Samsung AR24JRSDBWKNMG English-44, Smooth the cut edges, Cut off the remaining foam insulation

Page 44

Installing and connecting the assembly pipe of the indoor unit

Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.

There are 2 refrigerant pipes of different diameters:

The smaller one is for the liquid refrigerant

The larger one is for the gas refrigerant

A short pipe is already fitted to the air conditioner. You may

 

 

need to extend the pipe using the assembly pipe (optional).

 

 

The connection procedure for the refrigerant pipe varies

 

 

according to the exit position of the pipe when facing the wall:

A

B

• Right(A)

• Left(B)

 

C

• Underside(C)

 

 

 

• Rear

 

 

1.Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor unit unless you connect the pipe directly from the rear.

2.Smooth the cut edges.

3.Remove the protection caps of the pipes and connect the assembly

pipe to each pipe. Tighten the nuts first with your hands, and then with a torque wrench, applying the following torque:

• If you want to shorten or extend the pipes, refer to page 45~46.

4.Cut off the remaining foam insulation.

5.If necessary, bend the pipe to fit along the bottom of the indoor unit. Then pull it out through the appropriate hole.

The pipe should not project from the rear of the indoor unit.

The bending radius should be 100 mm or more.

Outer Diameter

Torque

 

 

N•m

kgf•cm

 

 

 

 

ø6.35 mm

14~18

140~180

 

 

 

ø9.52 mm

34~42

350~430

 

 

 

ø12.70 mm

49~61

500~620

 

 

 

ø15.88 mm

68~82

690~830

 

 

 

6.Pass the pipe through the hole in the wall.

7.For further details on how to connect to the outdoor unit and evacuate the air, refer to page 49~51.

• The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test;

refer to page 53 for further details.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

DO NOT WALL UP THE PIPE CONNECTION !

All refrigerant pipe connection must be easy accessible and serviceable.

English-44

MG_BETTER_ON&OFF_A3050_IB&IM_DB68-05189A.indd 44

2/17/2015 2:56:56 PM

Image 44
Contents Air Conditioner Features of your new air conditioner Contents Safety precautions English-4English-5 01epPr arationFor Using English-6English-7 Do not place objects or devices under the indoor unit English-8For Cleaning English-9English-10 Checking before useOperation ranges Technical Specifications English-11Checking the name of the parts Main partsDisplay English-12English-13 Checking the remote controllerRemote controller buttons Remote controller display Low Battery warningStoring the remote controller Inserting the batteriesBasic function English-16 Press the button to adjust the temperaturePress the button to set the desired fan speed Adjusting the air flow direction English-17Setting the On/Off timer Setting the On timerFfPress the Timer button select On press the or button  English-18Setting the Off timer English-19Er03mti ButtonEnglish-20 Additional options available in modeMode Step cooling function English-21Press the Options button 04 optioUsing the Fast function Using the Comfort functionEnglish-22 You can set the Comfort function to provide mild coolingUsing the Single user function Single user function is only available in Cool modeCancelled English-23English-24 Using the Virus Doctor functionMake the indicator blink and press the SET button Using the Auto clean function Checking the usage timeEnglish-25 SettiSetting the Beep sound Resetting the Filter clean reminderSetting the Display option English-26Cleaning the air conditioner Cleaning the indoor unitCleaning the outdoor unit heat exchanger English-27Cleaning the Air filter Removing the Air filterEnglish-28 Remove the Air filter from the main bodyTop of the Air filter into the main body.. ➀ Reassembling the Air filterEnglish-29 Maintaining the air conditioner English-30Troubleshooting TemperatureAdjustment is not English-31Button or disconnect the power plug/switch Check the Drains have been cleared Regular MaintenanceError is indicated Heard when refrigerant flow movement changes. It is normal07stin llan atio General informationEnglish-33 Choosing the installation location Installing the unitPower supply line, fuse or circuit breaker Indoor unitWhere sulfide gas exists Outdoor UnitEnglish-35 Reduce noise and vibrationWhen installing more than 1 outdoor unit When the air outlet is towards the wallEnglish-36  Figure DescriptionAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case English-37Fixing the installation plate Optional accessoriesTools required for installation General Tools Tools for test operationsAssembling the hanger screw English-39This QR code for detail video of indoor unit installation Removing the screwsRemoving the Cover panel Before mounting the indoor unit English-40 Assembling the Cover panel After mounting the indoor unit English-41Connecting the assembly cable Cable specificationConnecting the cable English-42English-43 Extend the assembly cable if necessaryEach wire is labeled with the corresponding terminal number English-44 Smooth the cut edgesCut off the remaining foam insulation TorqueEvacuating the indoor unit Cutting or extending the pipeEnglish-45 Unscrew the caps at the end of each pipeCracked English-46Correct Inclined Drain hose installation English-47Change the direction only when it is necessary Changing direction of the drain hoseEnglish-48 Check for leakage on both side of the drain outletConnect a drain hose to the drain plug Evacuating the connected pipesEnglish-49 Outer Torque Adding RefrigerantEnglish-50 Cylinder upright Upside down English-51Siphon Charge the refrigerant standing Performing the gas leak tests English-52English-53 Outdoor unit installed on the wall by rackFixing the outdoor unit in place Smart Install mode English-54English-55 Off / Blinking / OnFinal check and trial operation English-56Packing and unpacking guide English-57How to connect your extended power cables English-58Apply heat to the contraction tube to contract it After tube contraction work is completed, wrap it withEnglish-59 Questions or COMMENTS? 021-8255 CE