Installation Procedures

1.Open the front panel, and remove the flare nut.

2.Bend the connection pipe to an appropriate length using the spring bender depending upon the installation place.

-Allowable pipe length : Maximum 25m

-Allowable pipe drop distance : Maximum 15m

-Make no more than ten bending points on the pipe

When the pipe length is in excess of the standard pipe length of 5m, add the refrigerant (R22) of 75g(AP50Q1C Series) / 80g(AP55Q1C/AP55Q1D Series) for each additional 1m.

Additional Refrigerant

Example:15m pipe length, additional refrigerant to be charged is

(15m-5m)X75g/m=750g(AP50Q1C Series), (15m-5m)X80g/m=800g(AP55Q1C/AP55Q1D Series)

If the pipe is lengthened, the performance of the unit is degraded, and the service life is shortened. Therefore, the pipe length should be as short as possible (less than 25m).

Indoor unit

than15m

Outdoor

Less

unit

 

 

 

Indoor unit

 

 

Outdoor

 

 

 

 

unit

 

 

 

15m

Indoor unit

Fix the pipe

 

 

 

 

 

 

thanLess6m

 

 

Lessthan

 

 

S-TRAP

 

 

 

 

 

 

Outdoor

Fix the pipe

(Every 6m)

 

 

 

 

 

 

unit

 

 

3.Install the high pressure pipe to the heat exchanger liquid pipe, and the low pressure pipe to the heat exchanger gas pipe respectively using the flare nut, taking care not to cause any leakage of refrigerant.

4.Be sure to insulate the pipe with appropriate insulation material.

5.Insert the drain hose into the drain pipe, and connect them by tying them to the cable tie to prevent any water leakage.

6.After completion of the installation, check the connecting area for any gas leakage.

7.Wind a finish tape when the wiring of the refrigerant pipe, the unit, and the drain piping are completed.

Indoor unit

Outdoor unit

checking area

checking area

 

E-26

AP50Q1C_IBIM_E 32202-2.indd 26

2010-07-14 오후 4:42:15

Image 26
Contents Air Conditioner Safety Precautions Contents View of the Unit Indoor UnitRemote Control-Buttons Inserting the Remote Control BatteriesOperating Preparation ForCooling Your Room Heating Your Room Select the fan speed by pressingSelecting the Automatic Operating Mode Changing the Room Temperature Quickly To adjust the temperature, press Operating to the Long DistanceRemoving Excess Humidity Airing Your Room When Adjusting the Air Flow Direction VerticallyAdjusting the Air Flow Direction Horizontally To Cancel the Off Timer Setting the Off TimerTopic Recommendation Other FunctionOperating Recommendations Temperature and Humidity Ranges If the air conditioner is used at ThenCleaning Your Air Conditioner Solving Common Problems Problem Explanation/SolutionTechnical Specifications Power SupplyDrain plug Cable tie Putty Piping Pipe band Accessory Parts ListPart Name Cover hole ScrewOutdoor Unit Selection of Installation PlaceIndoor Unit Electrical Work AP50Q1C Series When using NFB No Fuse BreakerWhen using ELB Earth Leakage Circuit Breaker When connecting 3Phase 3wires 220V AC AP55Q1C/AP55Q1D SeriesInstallation Procedures Pipe Bending Connection of Refrigerant PipingFlare Processing Tightening of Connection PartsDrain Hose Connecting the PipeDrilling a Hole in the Wall Air Purge Refrigerant Charging Check and Test Operation CheckTest Operation Packing and Unpacking Guide Outdoor unit How to connect your extended power cables Wire tube power cable Connection sleeveQuestions or COMMENTS?