Refrigerant Charging

Air purge(at the time of new installation only)

Close the gas pipe side valve by turning it clockwise.

Connect the pressure gauge to the low pressure side service valve, and then open the gas pipe side valve again.

Connect it to the refrigerant filling tank.

Start cooling operation.

Check the pressure of the pressure gauge. Check whether the low pressure side is within the range of 4.5~5.6kg/cm2G

(outside temperature 35°C).

Open the tank and refill the refrigerant until arriving at the proper pressure.

(Refill the refrigerant slowly checking the pressure.)

OUTDOOR UNIT

Gas pipe side

Liquid pipe side

Stop operation.

Close the gas pipe side valve, and loosen the pressure gauge connected.

Then open the gas pipe side valve again.

Tighten the cap of each valve using a specified tool.

Always use R22 refrigerant to avoid damage of the unit or an explosion.

Must keep the quantity of refrigerant by using a balance. Do not use a manometer or not depend on your experiences.

E-30

AP50Q1C_IBIM_E 32202-2.indd 30

2010-07-14 오후 4:42:17

Image 30
Contents Air Conditioner Safety Precautions Contents View of the Unit Indoor UnitRemote Control-Buttons Inserting the Remote Control BatteriesOperating Preparation ForCooling Your Room Heating Your Room Select the fan speed by pressingSelecting the Automatic Operating Mode Changing the Room Temperature Quickly To adjust the temperature, press Operating to the Long DistanceRemoving Excess Humidity Airing Your Room Adjusting the Air Flow Direction Vertically Adjusting the Air Flow Direction HorizontallyWhen To Cancel the Off Timer Setting the Off TimerOther Function Operating RecommendationsTopic Recommendation Temperature and Humidity Ranges If the air conditioner is used at ThenCleaning Your Air Conditioner Solving Common Problems Problem Explanation/SolutionTechnical Specifications Power SupplyDrain plug Cable tie Putty Piping Pipe band Accessory Parts ListPart Name Cover hole ScrewSelection of Installation Place Indoor UnitOutdoor Unit Electrical Work When using NFB No Fuse Breaker When using ELB Earth Leakage Circuit BreakerAP50Q1C Series When connecting 3Phase 3wires 220V AC AP55Q1C/AP55Q1D SeriesInstallation Procedures Pipe Bending Connection of Refrigerant PipingFlare Processing Tightening of Connection PartsConnecting the Pipe Drilling a Hole in the WallDrain Hose Air Purge Refrigerant Charging Check and Test Operation CheckTest Operation Packing and Unpacking Guide Outdoor unit How to connect your extended power cables Wire tube power cable Connection sleeveQuestions or COMMENTS?