INSTALLATION | |
Continued |
|
CAUTION: Use only new, | |
black iron or steel pipe. | Inter- |
be used in certain areas. Check | |
your local codes. Use pipe of | |
large enough diameter to allow | |
proper gas volume to heater. If | |
pipe is too small, undue loss of | |
volume will occur. |
|
Typical Inlet Pipe Diameter - 3/8" (9.5 mm) | |
or greater |
|
Installation must include equipment shutoff valve, | |
union and plugged 1/8" NPT tap. Locate NPT tap | |
within reach for test gauge hook up. NPT tap must | |
be upstream from heater (see Figure 14). | |
IMPORTANT: Install an equipment shutoff valve | |
in an accessible location. The equipment shutoff | |
valve is for turning on or shutting off the gas to | |
the appliance. |
|
Pressure | Heater |
Regulator | Cabinet |
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
Install sediment trap in supply line as shown in Figure 14. Locate sediment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.
IMPORTANT: Hold the pressure regulator with wrench when connecting it to gas piping and/or fittings. Do not over tighten pipe connection to regulator. The regulator body could be damaged.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct
Gauge Connection*
3/8" NPT Pipe Nipple
Tee Joint
Reducer Bushing to 1/8" NPT
1/8" NPT
Plug Tap
Ground Joint
Union
Equipment
Shutoff
Valve *
all leaks at once.
WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detec- tion fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.
Test
TrapSediment
Tee Joint
Pipe
Nipple
Cap
3"
(7.6 cm)
Min. Natural Gas
From Gas Meter (4" W.C. to 10.5" W.C. Pressure)
Propane/LP
CAUTION: For propane/LP gas, make sure external regula- tor has been installed between propane/LP supply and heater. See guidelines under Connect-
From External Regulator
(11" W.C. to 14" W.C.
Pressure)
Figure 14 - Gas Connection
*A CSA
ing to Gas Supply, page 11.