Desa VN1800ITA, VN1800D, VN3000D Checking GAS Connections, Pressure Testing Heater GAS Connections

Page 16

CHECKING GAS CONNECTIONS

Continued

16

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Figure 14).

2.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to manual shutoff valve (see Figure 15). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

PRESSURE TESTING HEATER GAS CONNECTIONS

1.Open manual shutoff valve (see Figure 14).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from manual shutoff valve to control valve (see Figure 15). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 17 through 24). Check the rest of the internal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 20 [models VN1800ITA and VN2550ITA] or page 24 [models VN1800D and VN3000D]).

8.Replace front panel.

Open

Manual

Shutoff

Valve

Closed

Figure 14 - Manual Shutoff Valve

Control Valve Location

Gas Meter

Manual

Shutoff

Valve

Figure 15 - Checking Gas Joints

101822

Image 16
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASContents Safety Information Combustion and Ventilation, pages 5 through Product Local Codes Unpacking Product FeaturesIdentification Fresh AIR For CombustionVentilation Producing Adequate VentilationDetermining FRESH-AIR Flow for Heater Location Fresh AIR for Combustion and VentilationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Ventilation Air from OutdoorsInstalling To Wall Installation ItemsCheck GAS Type Locating HeaterThermostat Sensing Bulb Models VN1800ITA and VN2550ITA OnlyLocating Thermostat Sensing Bulb Attaching Thermostat Sensing BulbInstalling Heater to Wall Mounting BracketRemoving Front Panel Of Heater Methods For Attaching Mounting Bracket To WallMarking Screw Locations Attaching Mounting Bracket To WallInstalling Bottom Mounting Screws Placing Heater On Mounting BracketConnecting to GAS Supply Pressure Testing GAS Supply Piping System Checking GASConnections Servicing. Correct all leaks at oncePressure Testing Heater GAS Connections Checking GAS ConnectionsOperating Heater Operating Heater Lighting InstructionsHeater To Select Heating LevelShutting Off Heater Shutting Off Burner Only pilot stays litExplosion may result causing property damage, personal OperatingIf you do not follow these instructions exactly, a fire or Injury or loss of lifeModels VN1800D and VN3000D LOW MED High Inspecting Burner Pilot Flame PatternBurner Flame Pattern If burner flame pattern is incorrect, as shown in FigureCleaning and Maintenance Trouble Shooting ODS/PILOT and Burner OrificeCabinet Air PassagewaysObserved Possible Remedy Problem Cause TROUBLE- ShootingTrouble Shooting See CleaningIf you smell gas Shut off gas supplyDo not try to light any appliance Ing statement atService Publications Hints Technical ServiceVN1800D VN3000D Replacement Parts AccessoriesIllustrated Parts Breakdown Model VN1800ITAParts List Model VN2550ITA Parts List Model VN1800D Control Position Label Hardware Assembly Model VN3000D Parts List Warranty Information Keep this Warranty