Vent Information

 

 

 

 

 

 

 

 

 

Chimney and Exhaust Connection

B. Venting Termination Requirements

 

 

1.Chimney & Connector: Use 3 or 4 inch (76-102mm) diameter type "L" or "PL" venting system. It can be vented vertically or horizontally.

2.Mobile Home: Approved for all Listed pellet vent. If using the 3 inch (76mm) vertical top vent adapter Kit or the 3 to 6 inch (76-152mm) top vent offset adapter, use Listed double wall flue connector. A Quadra-Fire outside air kit must be used with manufactured home installations.

3.Residential: The 3 inch (76mm) vertical top vent adapter kit and the 3 to 6 inch (76-152mm) top vent offset adapter are tested to use 24 gauge single wall flue connector or Listed double wall flue connector to Class A Listed metal chimneys, or masonry chimneys meeting national and/or local codes for solid fuel appliances.

4.Install vent at clearances specified by the vent manufacturer.

5.Secure exhaust venting system to the appliance with at least 3 screws. Also secure all connector pipe joints with at least 3 screws through each joint.

NOTE: All pipe must be welded seam pipe whenever possible. Seal pipe joints with high temperature silicone (500°F [260°C] minimum rated only).

CAUTION

Do not terminate vent in any enclosed or semi-enclosed area such as a carport, garage, attic, crawl space, under a sun deck or porch, narrow walkway or closely fenced area, or any location that can build up a concentration of fumes such as a stairwell, covered breezeway, etc.

1. Termination must exhaust above air inlet elevation. It is recommended that at least 60 inches (1524mm) of verti- cal pipe be installed when appliance is vented directly through a wall. This will create a natural draft, which will help prevent the possibility of smoke or odor venting into the home during a power outage. It will also keep exhaust from causing a nuisance or hazard by exposing people or shrubs to high temperatures. The safest and preferred venting method is to extend the vent vertically through the roof.

2. Distance from doors and opening windows, or gravity or ventilation air inlets into building:

a.Not less than 48 inches (1219mm) below;

b.Not less than 48 inches (1219mm) horizontally from;

c.Not less than 12 inches (305mm) above.

3.Distance from permanently closed windows:

NOTE: If burning shelled field corn, you must use approved venting specifically designed for corn. Follow the instructions from the venting manufacturer.

WARNING

Fire Hazard.

Only LISTED venting components may be used.

NO OTHER vent components may be used. Substitute or damaged vent components may impair safe operation.

a.Not less than 12 inches (305mm) below, horizontally from or above.

4. Distance between bottom of termination and grade should be 12 inches (305mm) minimum. This is con- ditional upon plants in the area, and nature of grade surface. The grade surface must be a non-combustible material (i.e., rock, dirt). The grade surface must not be lawn. Distance between bottom of termination and public walkway should be 84 inches (2134mm) minimum.

5. Distance to combustible materials must be 24 inches (610mm) minimum. This includes adjacent buildings, fences, protruding parts of the structure, roof overhang, plants and shrubs, etc.

WARNING

Vent surfaces get HOT, can cause burns if touched. Noncombustible shielding or guards may be required.

6.Termination Cap Location (Home Electrical Service)

Side-to-side clearance is to be the same as minimum clearance to vinyl inside corners.

Clearance of a termination cap below electrical service shall be the same as minimum clearance to vinyl soffits.

Clearance of a termination cap above electrical service will be 12 inches (305mm) minimum.

Location of the vent termination must not obstruct or interfere with access to the electrical service.

Page 10

7014-082D

September 1, 2008

Image 10
Contents Classic BAY 1200 Pellet Stove Hot glass will cause burnsBehind left side curtain on outside of hopper wall Testing Lab & Report NumberCB 1200 Pellet Stove Serial Number ModelTable of Contents Listing and Code Approvals Getting Started Design, Installation & Location ConsiderationsFire Safety Appliance LocationCB 1200 Pellet Stove Tools And Supplies Needed Inspect Appliance & Components and Pre-Use Check ListDimensions and Clearances Appliance DimensionsCB 1200 Pellet Stove Clearances to Combustibles UL and ULC CB 1200 Pellet Stove Hearth Pad Requirements UL and ULC Exception for Horizontal InstallationsHearth Pad Requirements Vent Information CB 1200 Pellet Stove Equivalent Feet of Pipe Pipe Selection ChartExample of 3 Elbow-Rear Vent Termination Calculaton 5Venting Systems AlcoveDegree Straight OutCB 1200 Pellet Stove Through The Wall CB 1200 Pellet Stove Vertical Through The Wall & VerticalMasonry Alternate MasonryMobile Home Appliance Set-Up Rear Installation Floor InstallationOutside Air Kit Instructions Installing the Top Vent Adapter CB 1200 Pellet Stove Top Vent Adapter InstallationRear Vent and Rear Vent to Top Vent Adapter Installation See FigureCB 1200 Pellet Stove Optional Brick Set Installation Brick Clip InstallationTop Log, Left Installing Logo Nickel OnlyCharred Areas in the Back RightTo install door Door InstallationCB 1200 Pellet Stove Thermostat Installation To adjust latchesOperating Instructions Fuel Size And Material General Operating InformationFeed Rate Adjustment Instructions Starting Your First FireFrequently Asked Questions CB 1200 Pellet Stove Ignition CyclesSymptom TroubleshootingPossible Cause Corrective Action Page Page Frequency Daily Weekly Monthly Yearly Quick Reference Maintenance Chart10Maintaining & Servicing Your Appliance Types of FuelCleaning Heat Exchanger Chambers & Drop Tube Cleaning Firepot with Cleaning Rod & Firepot ScraperCleaning Ash Pan Ash Removal from FireboxCleaning the Glass Cleaning Beneath Heat ExchangerCleaning Exhaust Path Cleaning the HopperCleaning the Top Vent Adapter Preparing Firebox for Non-Burn Season Frequency YearlyCB 1200 Pellet Stove High Ash Fuel Content Maintenance Convection Blower ReplacementInstall new blower Exhaust Blower Replacement Remove existing blowerRe-install blower to blower housing Glass Replacement Replacing Side GlassReference Materials Component Function & LocationSnap Disc #1 Convection Blower 145F Vacuum SwitchWiring Harness See .1 below Snap Disc #2 Thermostat Override 200FCleaning Rods Heat Exchanger Tubes CB 1200 Pellet Stove Component LocationsGlass Size Center 13-7/8 wide x 11 high CB 1200 Pellet Stove Exploded ViewsGlass Size Sides 8 wide x 11 high Nbr Description CB 1200 Pellet Stove CB 1200 Pellet Stove Service Parts and Accessories Item # Parts Alphabetical OrderItem # Service Parts Alphabetical Order Accessories ApplianceCB 1200 Pellet Stove Service And Maintenance Log Date of Service Performed By Description of ServiceCB 1200 Pellet Stove Homeowner’s Notes CB 1200 Pellet Stove Warranty Policy CONDITIONS, Exclusions & Limitation of LiabilityHearth & Home Technologies Limited Warranty Cont’d Contact Information