GE 60-960-95 Downloader Programming, Basic System Commands, System Version Menu, system level

Page 68
System Version Menu

System Version Menu

The SYSTEM VERSION menu lets you view and identify panel hardware and software. This infor- mation is primarily used for troubleshooting purposes.

System Version (010: factory

(Default = N/A)

code, 011: system number, 012:

 

system level)

 

 

 

This menu lets you view and identify panel hardware and software version.

￿To view and identify the System Version:

1.Press A or B until the display shows SYSTEM VERSION.

2.Press # and the display shows FACTORY CODE nnn*nnnn.

3.Press B and the display shows SYSTEM NUMBER *nnnnnnn.

4.Press B again and the display shows SYSTEM LEVEL nnnn.

Downloader Programming

The panel can be programmed remotely using ToolBox. Use the information you recorded in Appendix A to inform the downloading operator of the programming requirements for this sys- tem.

ToolBox Downloader Programming

Note

ADownloader Phone Num- ber must be programmed and the user-programmable option “Downloading” must be on for remote downloader programming to work.

￿To initiate a ToolBox download session:

1.Contact your download station and ask the operator to prepare to download to the panel.

2.Make sure the system is disarmed.

3.Press 8 + system master code + 7 + 0 (any), 1 (down), or 2 (up). The display shows SYSTEM DOWNLOAD IN PROGRESS during the downloading process.

If the alphanumeric touchpad does not display SYSTEM DOWNLOAD IN PROGRESS, call the down- loader operator to verify the downloader phone number. Also, make sure ToolBox is set up prop- erly. Refer to the “Troubleshooting” section if the problem persists.

Testing the

System

Note

Before testing, it is recom- mended that you have cov- ers on all modules (mounted outside the cabinet) and the panel cabinet door closed.

The testing environment should match the system working environment.

This section describes the following:

Basic System Commands

Testing Zones/Sensors

Testing Phone Communication

Testing Central Station Communication

Testing Outputs and Sirens

Testing Light Control

Testing the Energy Saver Module

Changing Fixed Display Touchpads

Testing the Audio Verification Module

Testing Cellular Backup Communication

You should test the system after installing or servicing and after adding or removing devices from the system.

Refer to the “Troubleshooting” section if correct test results are not achieved.

Basic System Commands

Table 9 describes basic touchpad operating commands. For complete details on system operation, including user programming, refer to the system User’s Manual.

Table 9: Basic Touchpad Commands

Command

System Response

 

 

* (STATUS)

Indicates current system status

 

 

* + *

Indicates AC power and battery status

 

 

1 + CODE

Disarms system to OFF

 

 

2 + CODE

Arms system to STAY

 

 

63

Concord Ultra

Image 68
Contents Installation Instructions Concord Ultra6HFXULW\ 466-2061Rev CNotices FCC Part 15 Information to the UserFCC Part 15 Class B ACTA PartContents Planning the InstallationInstalling the System About This ManualTesting the System Programming the PanelTroubleshooting Special Installation Requirements UL Listed InstallationsTesting DefaultRequired Setting SIA System RequirementsPlanning the Installation UL Canada Listed InstallationsCentral Station Reporting FunctionSupervised Wireless Siren Standard PanelSuperBus 2000 Touchpads SnapCardsSuperBus 2000 Cellular Backup Module SuperBus 2000 Wireless Gateway ModuleSuperBus 2000 8Z Input Module HIM SuperBus 2000 4-RelayOutput Module HOMTotal System Power and Wire Length Guidelines PowerWire Length Determine the Panel LocationTable 2: Total System Wire Length Allowed Max. Wire LengthWire Type Total System WireTable 3: Minimum Device Current Draw Table 4: Wire RequirementsMounting the Panel Installing Antennas Identify Panel ComponentsConnecting the Panel to Earth Ground Installing Optional SnapCardsFigure 4. Installing the Antennas Figure 5. Connecting the Panel to Earth GroundConnecting 2-WireSmoke Detectors Connecting Detection Devices to Panel Zone InputsConnecting Intrusion Detection Devices Connecting Speakers Connecting 4-WireSmoke DetectorsTable 5 Panel Minimum Available Power 15-WattSpeakerConnecting Piezo Sirens Hardwire Interior SpeakerInterior Sirens Installing Supervised Wireless SirensExterior Sirens 1.Power up the panel see “Powering Up the Panel” Installing SuperBus 2000 Modules SuperBus 2000 Phone Interface/Voice ModuleWiring-Speaker SuperBus 2000 Energy Saver ModuleSuperBus 2000 Cellular Backup Module SuperBus 2000 Automation ModuleSuperBus 2000 8Z Input Module SuperBus 2000 4-RelayOutput ModuleSuperBus 2000 Wireless Gateway Module Setting Device Address on SuperBus 2000 DevicesInstalling an RJ-31XPhone Jack Figure 21. Connecting the SuperBus to the PanelConnecting the AC Power Transformer Powering Up the Panel Programmingthe Panel Entering Program ModeTouchpad Button Programming Functions Moving Through Program Mode Tiers and MenusTable 6: Touchpad Button Functions Figure 26. Tier 1 Program MenusProgramming Tier 1 Menu Items Using Shortcut Numbers Installer CodeSecurity-GlobalDefault = Security-GlobalDefault =Access Code Lock SIA False Alarm ReductionSecurity-GlobalDefault = none Security-GlobalDefault = onSecurity-Partition 1-2Default = on Security-Partition 1-2Default = onSecurity-Partition 1-2Default = on Quick Exit partition 1: 0012, partition 2:Keyswitch Sensor partition 1: 0015, partition 2: Keyswitch Style partition 1: 0016, partition 2:Security-Partition 1-2Default = none Security-Partition 1-2Default = transitionPhones-CSPhone 1-3Defaults: CS RPTS OFF/ON current setting, pressPhones-CSPhone 1-3Defaults: CS RPTS OFF/ON current setting, pressphone 3: phone 3:Phones-CSPhone 1-3Defaults: CS Phones-PagerPhone 1-5Default = nonePhones-PagerPhone 1-5Default = on Phones-PagerPhone 1-5Default = off0153, pager 4: 0163, pager 5: 0154, pager 4: 0164, pager 5:Latchkey Rpts pager 1: 0135, pager 2: 0145, pager 0155, pager 4: 0165, pager 5:Auto Test Reset Phones-DownloaderPhone Default = nonePhone Options-GlobalDefault = on Phone Options-GlobalDefault = offCancel Message Phone Options-GlobalDefault = onPhone Options-GlobalDefault = on Phone Options-GlobalDefault = onCall Wait Cancel Remote Access partition 1: 0211, parPhone Options-GlobalDefault = 15 sec Phone Options-GlobalDefault = nonePhone Options-Partition 1-2Default = on Phone Options-Partition1 only Default = nonePhone Options-Partition 1-2Default = on Phone Options-Partition 1-2Default = offPhone Access Key partition 1: 0216, partition 2: Timers MenuRF Tx Timeout Phone Options-Partition 1-2Default = #Activity Timeout Timers-GlobalDefault = 7 daysTimers-GlobalDefault 4 sec Timers-GlobalDefault = 24 hoursSiren Timeout partition 1: 0313, partition Timers-Partition 1-2Default = 4 minTimers-Partition 1-2Default = 4 min Timers-Partition 1-2Default = 22:00 10:00 pmdisplay shows HOUSE CODE nn-x current setting Touchpad Options-GlobalDefault = noneTouchpad Options-Partition 1-2Default = on Touchpad Options-Partition 1-2Default = onBack In Service Touchpad Options-Partition 1-2Default = offTouchpad Options-Partition 1-2Default = off Reporting-GlobalDefault = offLow CPU Battery Battery RestoralTwo Trip Error Reporting-GlobalDefault = onReporting-GlobalDefault = off Reporting-GlobalDefault = offReporting-GlobalDefault = off Reporting-GlobalDefault = weeklyReporting-GlobalDefault = Reporting-GlobalDefault = offReporting-Partition 1-2Default = off Reporting-Partition 1-2Default = offReporting-Partition 1-2Default = off Reporting-Partition 1-2Default = offReporting-Partition 1-2Default = off Reporting-Partition 1-2Default = offFreeze Alarm partition 1: 06107, partition 2: Alarm Verify partition 1: 06108, partition 2:Disable Trouble Beeps Reporting-Partition 1-2Default = offSiren Options-GlobalDefault = off Siren Options-GlobalDefault =Siren Options-GlobalDefault = off Siren Options-Partition1 Default = offLearn Sensors Table 7: How to Trip SensorsSensors Default = none Sensors Default = none Sensors Default = noneSensors Default = none Sensor TextAccess Timeout Audio Verification-Partition1 Default = offAudio Verification-Partition1 Default = Audio Verification-Partition1 Default = offAccess Code Accessory Modules MenuAudio Verification-Partition1 Default = 02 sec This setting determines how long AVM accessDevice ID Partition AssignOutput Programming Status BeepsKey Beeps Freeze TempTemperature Cellular SystemAcc. Modules--SnapCards-OutputText Default = none Output Text output 1: 10110, output 2:output 3 10112, output Onboard Options MenuTwo Wire Smoke Onboard Options-InputsDefault = offrent setting Onboard Options-InputsDefault = offOnboard Options-Output Text-Output1, 2 Default Exiting Programming ModeEntering User Programming Mode Output Text Output 1-1120,OutputTime and Date Default = 00:00 Time and Date Default = 01/01/00User Codes-Reg.User Codes-UserNNN Default = none TimeDirect Bypassing 030nnn1 where nnn=user number Remote Access 030nnn2 where nnn=user numberPartition Jump 030nnn3 where nnn=user number System Tests 030nnn4 where nnn=user numberLatchkey Report 030nnn5 where nnn=user number User Codes-PartitionMaster Code Default = noneUser Codes-SystemMaster Code Default = Options Default = onVolume Set Up Schedules MenuOptions Default = Options Default =Set Up Schedules 05XXY, where Default = 00:00Attach Schedules To Events Default = off XX=schedule 00 thru 15 and3.Press A or B until the desired light appears Attach Schedules To Events Default = off Energy Saver Default = 50FEnergy Saver Default = 90F Attach Lights To Sensors Default =Basic System Commands Default = N/ATable 9: Basic Touchpad Commands Downloader ProgrammingTable 9 Basic Touchpad Commands Continued Testing Zones/SensorsIf a Wireless Sensor Does Not Test Testing Phone Communication Testing Central Station/Pager CommunicationTable 10: Pager System Event Codes Table 11: Pager Sensor/Zone Code and NumbersTesting Outputs and Sirens Testing Light ControlTesting the Energy Saver Module ESM Table 12: System Alarm SoundsAdjusting Touchpad Display Contrast Testing Cellular Backup Communication Table 13: Current Phone Settings2.Check for proper panel and transformer wiring System indicates Sensor/Touchpad nn low battery Central station/pager is not receiving reportsSystem doesn’t go into alarm when zone is tripped Smoke sensor beeps once every 44 seconds Cellular backup report does not occur Module doesn’t communicate with alarm.com Table A1: Wireless Devices Appendix A System Planning WorksheetsTable A2: Hardwire Devices Table A3: Zone and Sensor AssignmentsTable A3: Zone and Sensor Assignments Continued Table A3 Zone and Sensor Assignments Continued Concord UltraTable A4 System Settings Index and Record Setting reference defaultSetting Shortcut NoException Reports phones Off Phone Test On Appendix B Reference Tables Table B1: Sensor Group Characteristics Continued Cross-ZoningTable B2: Item Numbers and Sensor Text Table B3: System Event Trigger Numbers Table B4: Sensor Group Event Trigger NumbersSystem Event DescriptionTable B4 Sensor Group Event Trigger Numbers Table B5: Sensor Number Event Trigger NumbersSensor Group Trigger NoTable B5: Sensor Number Event Trigger Numbers SensorTable B6: System Feature Event Trigger Numbers Table B5: Sensor Number Event Trigger NumbersTable B6: System Feature Event Trigger Numbers Table B7: Response CharacteristicsFeature Response CharacteristicsNotes for Table B8: Response Numbers Concord Ultra#* # * # To Enter Programming Mode: 8 + Installer orConcord Ultra Dealer Code + 0 +Tier 2 Menus Continued #* # * # * # * # * #Concord Ultra #* # Timers#* # * # Concord UltraConcord Ultra #* # Concord UltraSIA False Alarm Software VersionDownloader Code Central Station ReportsExit Delay Dialer Abort DelayDisarming DownloaderConcord Ultra Optional SuperBus 2000 Module Connections