GE 60-960-95 SIA System Requirements, Shortcut #, Function, Programming, Testing, Default

Page 7
SIA System Requirements

Immediate Beeps set to on

UL 98 Options set to on

Receiver Failure set to on (if wireless devices are used)

Siren Verify set to on

RF TX Timeout set to 4 hours (if system includes a built in or SuperBus 2000 RF Receiver and wireless smoke sensors)

Sleep Time set to off

Siren Timeout set to 4 minutes or more

Two Trip Error set to off

Disable Trouble Beeps set to off

UL 1023 & 985 24-Hour Backup

For 24-hour backup, the total current draw for all connected devices is limited to 190 mA (during normal standby conditions) using a 7.0 AH battery.

Note

UL requirements take prior- ity over SIA requirements.

SIA System Requirements

SIA system requirements are the same as those described for a UL Listed Basic System on page 1, plus:

If multiple annunciation is required, use Hardwire Siren part no.13-046.

SIA Setting Requirements

The following table describes programming requirements to meet ANSI-SIA CP-01.

Shortcut #

Function

Programming

Testing

Default

Required Setting

 

 

 

Page

Page

Setting

 

 

 

 

 

Reference

Reference

 

 

 

 

 

 

 

 

 

 

 

0004

SIA False Alarm

25

63

On

On

 

Reduction

 

 

 

 

 

 

 

 

 

 

 

 

 

partition 1: 0013

Exit Extension

26

63

On

On

partition 2: 0023

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

partition 1: 0014

Auto Stay Arming

26

63

On

On

partition 2: 0024

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

partition 1: 0017

Duress Code

27

63

Disabled

Disabled

partition 2: 0027

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02005

Dialer Abort

33

63

On

On

 

 

 

 

 

 

 

 

02006

Dialer Abort Delay

33

63

30 Sec.

15-45 sec.

 

 

 

 

 

 

 

 

02007

Cancel Message

33

63

On

On

 

 

 

 

 

 

 

 

02009

Call Wait Cancel

34

63

Disabled

On if reporting to central station and

 

 

 

 

 

 

customer has call waiting service

 

 

 

 

 

 

 

 

partition 1: 0310

Entry Delay

37

63

30 sec.

30-240 sec.

partition 2: 0320

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

partition 1: 0311

Exit Delay

37

63

60 sec.

45-184 sec.

partition 2: 0321

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06014

Swinger Limit

43

63

1

1

 

 

 

 

 

 

 

 

 

1100

Smoke Verify

54

63

Off

On if smoke alarms are

 

 

 

 

 

 

programmed into system

 

 

 

 

 

 

 

 

N/A

Cross Zoning

83

63

Disabled

Enabled for zones with a high

 

 

 

 

 

 

probability of false alarms

 

 

 

 

 

 

 

 

 

The following table describes non-programmable (hard coded) system operation as required to

 

meet ANSI-SIA CP-01 and is provided only for your reference.

 

 

 

 

 

 

 

 

 

 

Function

 

Operation

 

 

 

 

 

 

 

 

 

 

 

Disarm During Entry Delay

 

Enter Code Only (or 1 + CODE)

 

 

 

 

 

 

 

 

 

Concord Ultra

2

Image 7
Contents 466-2061Rev C Installation InstructionsConcord Ultra 6HFXULW\ACTA Part NoticesFCC Part 15 Information to the User FCC Part 15 Class BAbout This Manual ContentsPlanning the Installation Installing the SystemProgramming the Panel Testing the SystemTroubleshooting UL Listed Installations Special Installation RequirementsSIA System Requirements TestingDefault Required SettingFunction Planning the InstallationUL Canada Listed Installations Central Station ReportingSnapCards Supervised Wireless SirenStandard Panel SuperBus 2000 TouchpadsSuperBus 2000 4-RelayOutput Module HOM SuperBus 2000 Cellular Backup ModuleSuperBus 2000 Wireless Gateway Module SuperBus 2000 8Z Input Module HIMDetermine the Panel Location Total System Power and Wire Length GuidelinesPower Wire LengthTotal System Wire Table 2: Total System Wire Length AllowedMax. Wire Length Wire TypeMounting the Panel Table 4: Wire RequirementsTable 3: Minimum Device Current Draw Identify Panel Components Installing AntennasFigure 5. Connecting the Panel to Earth Ground Connecting the Panel to Earth GroundInstalling Optional SnapCards Figure 4. Installing the AntennasConnecting Intrusion Detection Devices Connecting Detection Devices to Panel Zone InputsConnecting 2-WireSmoke Detectors 15-WattSpeaker Connecting SpeakersConnecting 4-WireSmoke Detectors Table 5 Panel Minimum Available PowerHardwire Interior Speaker Connecting Piezo SirensExterior Sirens Installing Supervised Wireless SirensInterior Sirens 1.Power up the panel see “Powering Up the Panel” SuperBus 2000 Phone Interface/Voice Module Installing SuperBus 2000 ModulesSuperBus 2000 Energy Saver Module Wiring-SpeakerSuperBus 2000 4-RelayOutput Module SuperBus 2000 Cellular Backup ModuleSuperBus 2000 Automation Module SuperBus 2000 8Z Input ModuleFigure 21. Connecting the SuperBus to the Panel SuperBus 2000 Wireless Gateway ModuleSetting Device Address on SuperBus 2000 Devices Installing an RJ-31XPhone JackConnecting the AC Power Transformer Entering Program Mode Powering Up the PanelProgramming the PanelFigure 26. Tier 1 Program Menus Touchpad Button Programming FunctionsMoving Through Program Mode Tiers and Menus Table 6: Touchpad Button FunctionsProgramming Tier 1 Menu Items Security-GlobalDefault = Using Shortcut NumbersInstaller Code Security-GlobalDefault =Security-GlobalDefault = on Access Code LockSIA False Alarm Reduction Security-GlobalDefault = noneQuick Exit partition 1: 0012, partition 2: Security-Partition 1-2Default = onSecurity-Partition 1-2Default = on Security-Partition 1-2Default = onSecurity-Partition 1-2Default = transition Keyswitch Sensor partition 1: 0015, partition 2:Keyswitch Style partition 1: 0016, partition 2: Security-Partition 1-2Default = noneRPTS OFF/ON current setting, press Phones-CSPhone 1-3Defaults: CSRPTS OFF/ON current setting, press Phones-CSPhone 1-3Defaults: CSphone 3: phone 3:Phones-PagerPhone 1-5Default = off Phones-CSPhone 1-3Defaults: CSPhones-PagerPhone 1-5Default = none Phones-PagerPhone 1-5Default = on0155, pager 4: 0165, pager 5: 0153, pager 4: 0163, pager 5:0154, pager 4: 0164, pager 5: Latchkey Rpts pager 1: 0135, pager 2: 0145, pagerPhone Options-GlobalDefault = off Auto Test ResetPhones-DownloaderPhone Default = none Phone Options-GlobalDefault = onPhone Options-GlobalDefault = on Cancel MessagePhone Options-GlobalDefault = on Phone Options-GlobalDefault = onPhone Options-GlobalDefault = none Call Wait CancelRemote Access partition 1: 0211, par Phone Options-GlobalDefault = 15 secPhone Options-Partition 1-2Default = off Phone Options-Partition 1-2Default = onPhone Options-Partition1 only Default = none Phone Options-Partition 1-2Default = onPhone Options-Partition 1-2Default = # Phone Access Key partition 1: 0216, partition 2:Timers Menu RF Tx TimeoutTimers-GlobalDefault = 24 hours Activity TimeoutTimers-GlobalDefault = 7 days Timers-GlobalDefault 4 secTimers-Partition 1-2Default = 22:00 10:00 pm Siren Timeout partition 1: 0313, partitionTimers-Partition 1-2Default = 4 min Timers-Partition 1-2Default = 4 minTouchpad Options-Partition 1-2Default = on display shows HOUSE CODE nn-x current settingTouchpad Options-GlobalDefault = none Touchpad Options-Partition 1-2Default = onReporting-GlobalDefault = off Back In ServiceTouchpad Options-Partition 1-2Default = off Touchpad Options-Partition 1-2Default = offReporting-GlobalDefault = on Low CPU BatteryBattery Restoral Two Trip ErrorReporting-GlobalDefault = weekly Reporting-GlobalDefault = offReporting-GlobalDefault = off Reporting-GlobalDefault = offReporting-Partition 1-2Default = off Reporting-GlobalDefault =Reporting-GlobalDefault = off Reporting-Partition 1-2Default = offReporting-Partition 1-2Default = off Reporting-Partition 1-2Default = offReporting-Partition 1-2Default = off Reporting-Partition 1-2Default = offReporting-Partition 1-2Default = off Freeze Alarm partition 1: 06107, partition 2:Alarm Verify partition 1: 06108, partition 2: Disable Trouble BeepsSiren Options-Partition1 Default = off Siren Options-GlobalDefault = offSiren Options-GlobalDefault = Siren Options-GlobalDefault = offSensors Default = none Table 7: How to Trip SensorsLearn Sensors Sensor Text Sensors Default = noneSensors Default = none Sensors Default = noneAudio Verification-Partition1 Default = off Access TimeoutAudio Verification-Partition1 Default = off Audio Verification-Partition1 Default =This setting determines how long AVM access Access CodeAccessory Modules Menu Audio Verification-Partition1 Default = 02 secStatus Beeps Device IDPartition Assign Output ProgrammingCellular System Key BeepsFreeze Temp TemperatureOnboard Options Menu Acc. Modules--SnapCards-OutputText Default = noneOutput Text output 1: 10110, output 2: output 3 10112, outputOnboard Options-InputsDefault = off Two Wire SmokeOnboard Options-InputsDefault = off rent settingOutput Text Output 1-1120,Output Onboard Options-Output Text-Output1, 2 DefaultExiting Programming Mode Entering User Programming ModeTime Time and Date Default = 00:00Time and Date Default = 01/01/00 User Codes-Reg.User Codes-UserNNN Default = noneSystem Tests 030nnn4 where nnn=user number Direct Bypassing 030nnn1 where nnn=user numberRemote Access 030nnn2 where nnn=user number Partition Jump 030nnn3 where nnn=user numberOptions Default = on Latchkey Report 030nnn5 where nnn=user numberUser Codes-PartitionMaster Code Default = none User Codes-SystemMaster Code Default =Options Default = VolumeSet Up Schedules Menu Options Default =XX=schedule 00 thru 15 and Set Up Schedules 05XXY, whereDefault = 00:00 Attach Schedules To Events Default = off3.Press A or B until the desired light appears Attach Lights To Sensors Default = Attach Schedules To Events Default = offEnergy Saver Default = 50F Energy Saver Default = 90FDownloader Programming Basic System CommandsDefault = N/A Table 9: Basic Touchpad CommandsIf a Wireless Sensor Does Not Test Testing Zones/SensorsTable 9 Basic Touchpad Commands Continued Table 11: Pager Sensor/Zone Code and Numbers Testing Phone CommunicationTesting Central Station/Pager Communication Table 10: Pager System Event CodesTable 12: System Alarm Sounds Testing Outputs and SirensTesting Light Control Testing the Energy Saver Module ESMAdjusting Touchpad Display Contrast Table 13: Current Phone Settings Testing Cellular Backup Communication2.Check for proper panel and transformer wiring Central station/pager is not receiving reports System indicates Sensor/Touchpad nn low batterySystem doesn’t go into alarm when zone is tripped Smoke sensor beeps once every 44 seconds Cellular backup report does not occur Module doesn’t communicate with alarm.com Appendix A System Planning Worksheets Table A1: Wireless DevicesTable A3: Zone and Sensor Assignments Table A2: Hardwire DevicesTable A3: Zone and Sensor Assignments Continued Concord Ultra Table A3 Zone and Sensor Assignments ContinuedShortcut No Table A4 System Settings Index and RecordSetting reference default SettingException Reports phones Off Phone Test On Appendix B Reference Tables Cross-Zoning Table B1: Sensor Group Characteristics ContinuedTable B2: Item Numbers and Sensor Text Description Table B3: System Event Trigger NumbersTable B4: Sensor Group Event Trigger Numbers System EventTrigger No Table B4 Sensor Group Event Trigger NumbersTable B5: Sensor Number Event Trigger Numbers Sensor GroupSensor Table B5: Sensor Number Event Trigger NumbersTable B5: Sensor Number Event Trigger Numbers Table B6: System Feature Event Trigger NumbersResponse Characteristics Table B6: System Feature Event Trigger NumbersTable B7: Response Characteristics FeatureConcord Ultra Notes for Table B8: Response NumbersDealer Code + 0 + #* # * #To Enter Programming Mode: 8 + Installer or Concord UltraConcord Ultra #* # * # * # * # * #Tier 2 Menus Continued Concord Ultra #* #Timers #* # * #Concord Ultra Concord Ultra #* #Central Station Reports SIA False AlarmSoftware Version Downloader CodeDownloader Exit DelayDialer Abort Delay DisarmingConcord Ultra Optional SuperBus 2000 Module Connections