GE 60-960-95 Total System Wire Length Allowed, Minimum Device Current Draw, Max. Wire Length

Page 12
Table 2: Total System Wire Length Allowed

Table 1: Maximum Device Wire Length and Current Draw (Continued)

Device

Max. Wire Length

Max. mA

to Panel

Draw

 

 

 

 

8Z Hardwire Zone Expander SnapCard

N/A

230 mA*

 

 

 

4 Output SnapCard

N/A

130 mA*

 

 

 

SuperBus 2000 8Z Input Module

22 ga.—1,800 ft.

35 mA

18 ga.—4,000 ft.

 

 

 

 

 

SuperBus 2000 4-Relay Output Module

22 ga.—350 ft.

180 mA

18 ga.—900 ft.

 

 

 

 

 

SuperBus 2000 Energy Saver Module

22 ga.—1,600 ft.

20 mA

18 ga.—4,000 ft.

 

 

 

 

 

 

Standard Power:

 

 

22 ga.—15 ft.

1600 mA

SuperBus 2000 Cellular Backup Module

18 ga.—40 ft.

 

 

 

High Power

 

 

 

 

22 ga.—10 ft.

1900 mA

 

18 ga.—30 ft.

 

 

 

 

SuperBus 2000 Automation Module

22 ga.—1,500 ft.

35 mA

18 ga.—4,000 ft.

 

 

 

 

 

SuperBus 2000 Wireless Gateway Module

22 ga.—40 ft.

1600 mA

18 ga.—90 ft.

 

 

 

 

 

Interrogator 200

22 ga.—3,200 ft.

10 mA

18 ga.—4,500 ft.

 

 

 

 

 

Interrogator AVM

22 ga.—110 ft.

300 mA

18 ga.—260 ft.

 

 

 

 

 

*Maximum current draw for the SnapCards does not include the load which may be applied to their auxiliary DC supply.

Table 2 describes the total system wire lengths allowed when installing systems using unshielded or shielded cable.

Table 2: Total System Wire Length Allowed

Wire Type

Total System Wire

 

 

18-gauge, unshielded

4,500 ft.

18-gauge, shielded

3,000 ft.

 

 

22-gauge, unshielded

3,500 ft.

22-gauge, shielded

2,200 ft.

 

 

Table 3 describes the minimum current draw of each device when the panel is operating only from the backup battery. For 24-hour backup, the total current draw of all SnapCards connected to the panel and devices connected to +12V BUS (panel terminal 4) is limited to 190 mA (during normal standby condition) using a 7.0 AH battery.

Table 3: Minimum Device Current Draw

 

Device

Min. mA Draw

 

 

SuperBus 2000 2x16 LCD Alphanumeric Touchpad

15 mA

 

 

SuperBus 2000 2x20 LCD Alphanumeric Touchpad

15 mA

 

 

SuperBus 2000 2x20 VFD Alphanumeric Touchpad

15 mA

 

 

SuperBus 2000 Fixed Display Touchpad

11 mA

 

 

4 Input/2 Output SnapCard

20 mA

 

 

8Z Hardwire Zone Expander SnapCard

38 mA

 

 

4 Output SnapCard

1 mA

 

 

 

SuperBus 2000

8Z Input Module

18 mA

 

 

 

SuperBus 2000

4-Relay Output Module

12 mA

 

 

 

SuperBus 2000

Energy Saver Module

20 mA

 

 

 

SuperBus 2000

Cellular Backup Module

90 mA

 

 

 

7

Concord Ultra

Image 12
Contents Installation Instructions Concord Ultra6HFXULW\ 466-2061Rev CNotices FCC Part 15 Information to the UserFCC Part 15 Class B ACTA PartContents Planning the InstallationInstalling the System About This ManualTesting the System Programming the PanelTroubleshooting Special Installation Requirements UL Listed InstallationsTesting DefaultRequired Setting SIA System RequirementsPlanning the Installation UL Canada Listed InstallationsCentral Station Reporting FunctionSupervised Wireless Siren Standard PanelSuperBus 2000 Touchpads SnapCardsSuperBus 2000 Cellular Backup Module SuperBus 2000 Wireless Gateway ModuleSuperBus 2000 8Z Input Module HIM SuperBus 2000 4-RelayOutput Module HOMTotal System Power and Wire Length Guidelines PowerWire Length Determine the Panel LocationTable 2: Total System Wire Length Allowed Max. Wire LengthWire Type Total System WireTable 4: Wire Requirements Mounting the PanelTable 3: Minimum Device Current Draw Installing Antennas Identify Panel ComponentsConnecting the Panel to Earth Ground Installing Optional SnapCardsFigure 4. Installing the Antennas Figure 5. Connecting the Panel to Earth GroundConnecting Detection Devices to Panel Zone Inputs Connecting Intrusion Detection DevicesConnecting 2-WireSmoke Detectors Connecting Speakers Connecting 4-WireSmoke DetectorsTable 5 Panel Minimum Available Power 15-WattSpeakerConnecting Piezo Sirens Hardwire Interior SpeakerInstalling Supervised Wireless Sirens Exterior SirensInterior Sirens 1.Power up the panel see “Powering Up the Panel” Installing SuperBus 2000 Modules SuperBus 2000 Phone Interface/Voice ModuleWiring-Speaker SuperBus 2000 Energy Saver ModuleSuperBus 2000 Cellular Backup Module SuperBus 2000 Automation ModuleSuperBus 2000 8Z Input Module SuperBus 2000 4-RelayOutput ModuleSuperBus 2000 Wireless Gateway Module Setting Device Address on SuperBus 2000 DevicesInstalling an RJ-31XPhone Jack Figure 21. Connecting the SuperBus to the PanelConnecting the AC Power Transformer Powering Up the Panel Programmingthe Panel Entering Program ModeTouchpad Button Programming Functions Moving Through Program Mode Tiers and MenusTable 6: Touchpad Button Functions Figure 26. Tier 1 Program MenusProgramming Tier 1 Menu Items Using Shortcut Numbers Installer CodeSecurity-GlobalDefault = Security-GlobalDefault =Access Code Lock SIA False Alarm ReductionSecurity-GlobalDefault = none Security-GlobalDefault = onSecurity-Partition 1-2Default = on Security-Partition 1-2Default = onSecurity-Partition 1-2Default = on Quick Exit partition 1: 0012, partition 2:Keyswitch Sensor partition 1: 0015, partition 2: Keyswitch Style partition 1: 0016, partition 2:Security-Partition 1-2Default = none Security-Partition 1-2Default = transitionPhones-CSPhone 1-3Defaults: CS RPTS OFF/ON current setting, pressPhones-CSPhone 1-3Defaults: CS RPTS OFF/ON current setting, pressphone 3: phone 3:Phones-CSPhone 1-3Defaults: CS Phones-PagerPhone 1-5Default = nonePhones-PagerPhone 1-5Default = on Phones-PagerPhone 1-5Default = off0153, pager 4: 0163, pager 5: 0154, pager 4: 0164, pager 5:Latchkey Rpts pager 1: 0135, pager 2: 0145, pager 0155, pager 4: 0165, pager 5:Auto Test Reset Phones-DownloaderPhone Default = nonePhone Options-GlobalDefault = on Phone Options-GlobalDefault = offCancel Message Phone Options-GlobalDefault = onPhone Options-GlobalDefault = on Phone Options-GlobalDefault = onCall Wait Cancel Remote Access partition 1: 0211, parPhone Options-GlobalDefault = 15 sec Phone Options-GlobalDefault = nonePhone Options-Partition 1-2Default = on Phone Options-Partition1 only Default = nonePhone Options-Partition 1-2Default = on Phone Options-Partition 1-2Default = offPhone Access Key partition 1: 0216, partition 2: Timers MenuRF Tx Timeout Phone Options-Partition 1-2Default = #Activity Timeout Timers-GlobalDefault = 7 daysTimers-GlobalDefault 4 sec Timers-GlobalDefault = 24 hoursSiren Timeout partition 1: 0313, partition Timers-Partition 1-2Default = 4 minTimers-Partition 1-2Default = 4 min Timers-Partition 1-2Default = 22:00 10:00 pmdisplay shows HOUSE CODE nn-x current setting Touchpad Options-GlobalDefault = noneTouchpad Options-Partition 1-2Default = on Touchpad Options-Partition 1-2Default = onBack In Service Touchpad Options-Partition 1-2Default = offTouchpad Options-Partition 1-2Default = off Reporting-GlobalDefault = offLow CPU Battery Battery RestoralTwo Trip Error Reporting-GlobalDefault = onReporting-GlobalDefault = off Reporting-GlobalDefault = offReporting-GlobalDefault = off Reporting-GlobalDefault = weeklyReporting-GlobalDefault = Reporting-GlobalDefault = offReporting-Partition 1-2Default = off Reporting-Partition 1-2Default = offReporting-Partition 1-2Default = off Reporting-Partition 1-2Default = offReporting-Partition 1-2Default = off Reporting-Partition 1-2Default = offFreeze Alarm partition 1: 06107, partition 2: Alarm Verify partition 1: 06108, partition 2:Disable Trouble Beeps Reporting-Partition 1-2Default = offSiren Options-GlobalDefault = off Siren Options-GlobalDefault =Siren Options-GlobalDefault = off Siren Options-Partition1 Default = offTable 7: How to Trip Sensors Sensors Default = noneLearn Sensors Sensors Default = none Sensors Default = noneSensors Default = none Sensor TextAccess Timeout Audio Verification-Partition1 Default = offAudio Verification-Partition1 Default = Audio Verification-Partition1 Default = offAccess Code Accessory Modules MenuAudio Verification-Partition1 Default = 02 sec This setting determines how long AVM accessDevice ID Partition AssignOutput Programming Status BeepsKey Beeps Freeze TempTemperature Cellular SystemAcc. Modules--SnapCards-OutputText Default = none Output Text output 1: 10110, output 2:output 3 10112, output Onboard Options MenuTwo Wire Smoke Onboard Options-InputsDefault = offrent setting Onboard Options-InputsDefault = offOnboard Options-Output Text-Output1, 2 Default Exiting Programming ModeEntering User Programming Mode Output Text Output 1-1120,OutputTime and Date Default = 00:00 Time and Date Default = 01/01/00User Codes-Reg.User Codes-UserNNN Default = none TimeDirect Bypassing 030nnn1 where nnn=user number Remote Access 030nnn2 where nnn=user numberPartition Jump 030nnn3 where nnn=user number System Tests 030nnn4 where nnn=user numberLatchkey Report 030nnn5 where nnn=user number User Codes-PartitionMaster Code Default = noneUser Codes-SystemMaster Code Default = Options Default = onVolume Set Up Schedules MenuOptions Default = Options Default =Set Up Schedules 05XXY, where Default = 00:00Attach Schedules To Events Default = off XX=schedule 00 thru 15 and3.Press A or B until the desired light appears Attach Schedules To Events Default = off Energy Saver Default = 50FEnergy Saver Default = 90F Attach Lights To Sensors Default =Basic System Commands Default = N/ATable 9: Basic Touchpad Commands Downloader ProgrammingTesting Zones/Sensors If a Wireless Sensor Does Not TestTable 9 Basic Touchpad Commands Continued Testing Phone Communication Testing Central Station/Pager CommunicationTable 10: Pager System Event Codes Table 11: Pager Sensor/Zone Code and NumbersTesting Outputs and Sirens Testing Light ControlTesting the Energy Saver Module ESM Table 12: System Alarm SoundsAdjusting Touchpad Display Contrast Testing Cellular Backup Communication Table 13: Current Phone Settings2.Check for proper panel and transformer wiring System indicates Sensor/Touchpad nn low battery Central station/pager is not receiving reportsSystem doesn’t go into alarm when zone is tripped Smoke sensor beeps once every 44 seconds Cellular backup report does not occur Module doesn’t communicate with alarm.com Table A1: Wireless Devices Appendix A System Planning WorksheetsTable A2: Hardwire Devices Table A3: Zone and Sensor AssignmentsTable A3: Zone and Sensor Assignments Continued Table A3 Zone and Sensor Assignments Continued Concord UltraTable A4 System Settings Index and Record Setting reference defaultSetting Shortcut NoException Reports phones Off Phone Test On Appendix B Reference Tables Table B1: Sensor Group Characteristics Continued Cross-ZoningTable B2: Item Numbers and Sensor Text Table B3: System Event Trigger Numbers Table B4: Sensor Group Event Trigger NumbersSystem Event DescriptionTable B4 Sensor Group Event Trigger Numbers Table B5: Sensor Number Event Trigger NumbersSensor Group Trigger NoTable B5: Sensor Number Event Trigger Numbers SensorTable B6: System Feature Event Trigger Numbers Table B5: Sensor Number Event Trigger NumbersTable B6: System Feature Event Trigger Numbers Table B7: Response CharacteristicsFeature Response CharacteristicsNotes for Table B8: Response Numbers Concord Ultra#* # * # To Enter Programming Mode: 8 + Installer orConcord Ultra Dealer Code + 0 +#* # * # * # * # * # Concord UltraTier 2 Menus Continued #* # Timers#* # * # Concord UltraConcord Ultra #* # Concord UltraSIA False Alarm Software VersionDownloader Code Central Station ReportsExit Delay Dialer Abort DelayDisarming DownloaderConcord Ultra Optional SuperBus 2000 Module Connections