GE 60-960-95 Planning the Installation, Central Station Reporting, UL Canada Listed Installations

Page 8
Operation

Note

For UL 1635 installations, Entry Delay plus Dialer Abort Delay must not exceed 60 seconds.

Function

Operation

 

 

Cancel Alarm

Enter Code Only (or 1 + CODE)

 

 

Abort Annunciation

Enabled

 

 

Cancel Report Annunciation

Enabled

 

 

UL 1635 Digital Alarm Communicator System

Same as UL 1023 & 985 plus:

AC Failure set to on

Comm Failure set to on

RF Tx Timeout set to 4 hours

Low CPU Battery set to on

Phone Number must be programmed

Next Phone Test set to 1

Phone Test Freq. set to 1

High Level Rpts set to on

Low Level Rpts set to on

Central Station Reporting

The panel has been tested with the following central station receivers using SIA and Contact ID reporting formats:

CS-5000 Central Station Receiver

Sur-Gard Central Station Receiver with models SG-DRL2A and SG-CPM2

UL Canada Listed Installations

This section describes the requirements for CUL (UL Canada) Listed installations.

Canadian Standards CSA Certified Accessories

Residential Burglary Alarm System Unit (ULC-S309)

Basic system as described for “UL 1023 Listed Installations” plus:

Hardwire Magnetic Contact (1035-N or 1075-N) or Wireless Learn Mode Door/Window Sensor (60-362)

Siren Timeout set to 5 minutes or more

Residential Fire Warning System Control Unit (ULC-S545-M89)

Basic system as described for “UL 985 Listed Installations” plus:

Hardwire Smoke Detector: System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400, 2400TH learned into Sensor Group 26, or Sentrol (ESL) models 429AT, 521B, or 521BXT learned into sensor group 26

Wireless Smoke Sensor 60-506-319.5 or 60-848-02-95 learned into sensor group 26

Immediate Beeps set to on

Note

For 24-hour backup, exter- nal power drain is limited to 90 mA (during normal standby condition) using a

4.0AH battery, or 190 mA continuous using a 7.0 AH battery.

RF TX Timeout set to 4 hours (if system includes wireless smoke sensors)

California State Fire Marshall Listed Installations

Same as Household Fire Warning System (UL 985), plus:

SMOKE VERIFY must be set to off

Planning the Installation

This section describes system capabilities to help you get familiar with the system. “Appendix A” provides planning sheets with tables that let you record the hardware and programming con- figuration of the system. Fill in all necessary information ahead of time to help prepare for sys- tem installation.

When planning the installation, keep in mind that the panel has the following capabilities (depen- dent upon devices used):

Up to 16 SuperBus 2000 Devices (maximum of 4 RF receivers)

3

Concord Ultra

Image 8
Contents Installation Instructions Concord Ultra6HFXULW\ 466-2061Rev CNotices FCC Part 15 Information to the UserFCC Part 15 Class B ACTA PartContents Planning the InstallationInstalling the System About This ManualTesting the System Programming the PanelTroubleshooting Special Installation Requirements UL Listed InstallationsTesting DefaultRequired Setting SIA System RequirementsPlanning the Installation UL Canada Listed InstallationsCentral Station Reporting FunctionSupervised Wireless Siren Standard PanelSuperBus 2000 Touchpads SnapCardsSuperBus 2000 Cellular Backup Module SuperBus 2000 Wireless Gateway ModuleSuperBus 2000 8Z Input Module HIM SuperBus 2000 4-RelayOutput Module HOMTotal System Power and Wire Length Guidelines PowerWire Length Determine the Panel LocationTable 2: Total System Wire Length Allowed Max. Wire LengthWire Type Total System WireTable 3: Minimum Device Current Draw Table 4: Wire RequirementsMounting the Panel Installing Antennas Identify Panel ComponentsConnecting the Panel to Earth Ground Installing Optional SnapCardsFigure 4. Installing the Antennas Figure 5. Connecting the Panel to Earth GroundConnecting 2-WireSmoke Detectors Connecting Detection Devices to Panel Zone InputsConnecting Intrusion Detection Devices Connecting Speakers Connecting 4-WireSmoke DetectorsTable 5 Panel Minimum Available Power 15-WattSpeakerConnecting Piezo Sirens Hardwire Interior SpeakerInterior Sirens Installing Supervised Wireless SirensExterior Sirens 1.Power up the panel see “Powering Up the Panel” Installing SuperBus 2000 Modules SuperBus 2000 Phone Interface/Voice ModuleWiring-Speaker SuperBus 2000 Energy Saver ModuleSuperBus 2000 Cellular Backup Module SuperBus 2000 Automation ModuleSuperBus 2000 8Z Input Module SuperBus 2000 4-RelayOutput ModuleSuperBus 2000 Wireless Gateway Module Setting Device Address on SuperBus 2000 DevicesInstalling an RJ-31XPhone Jack Figure 21. Connecting the SuperBus to the PanelConnecting the AC Power Transformer Powering Up the Panel Programmingthe Panel Entering Program ModeTouchpad Button Programming Functions Moving Through Program Mode Tiers and MenusTable 6: Touchpad Button Functions Figure 26. Tier 1 Program MenusProgramming Tier 1 Menu Items Using Shortcut Numbers Installer CodeSecurity-GlobalDefault = Security-GlobalDefault =Access Code Lock SIA False Alarm ReductionSecurity-GlobalDefault = none Security-GlobalDefault = onSecurity-Partition 1-2Default = on Security-Partition 1-2Default = onSecurity-Partition 1-2Default = on Quick Exit partition 1: 0012, partition 2:Keyswitch Sensor partition 1: 0015, partition 2: Keyswitch Style partition 1: 0016, partition 2:Security-Partition 1-2Default = none Security-Partition 1-2Default = transitionPhones-CSPhone 1-3Defaults: CS RPTS OFF/ON current setting, pressPhones-CSPhone 1-3Defaults: CS RPTS OFF/ON current setting, pressphone 3: phone 3:Phones-CSPhone 1-3Defaults: CS Phones-PagerPhone 1-5Default = nonePhones-PagerPhone 1-5Default = on Phones-PagerPhone 1-5Default = off0153, pager 4: 0163, pager 5: 0154, pager 4: 0164, pager 5:Latchkey Rpts pager 1: 0135, pager 2: 0145, pager 0155, pager 4: 0165, pager 5:Auto Test Reset Phones-DownloaderPhone Default = nonePhone Options-GlobalDefault = on Phone Options-GlobalDefault = offCancel Message Phone Options-GlobalDefault = onPhone Options-GlobalDefault = on Phone Options-GlobalDefault = onCall Wait Cancel Remote Access partition 1: 0211, parPhone Options-GlobalDefault = 15 sec Phone Options-GlobalDefault = nonePhone Options-Partition 1-2Default = on Phone Options-Partition1 only Default = nonePhone Options-Partition 1-2Default = on Phone Options-Partition 1-2Default = offPhone Access Key partition 1: 0216, partition 2: Timers MenuRF Tx Timeout Phone Options-Partition 1-2Default = #Activity Timeout Timers-GlobalDefault = 7 daysTimers-GlobalDefault 4 sec Timers-GlobalDefault = 24 hoursSiren Timeout partition 1: 0313, partition Timers-Partition 1-2Default = 4 minTimers-Partition 1-2Default = 4 min Timers-Partition 1-2Default = 22:00 10:00 pmdisplay shows HOUSE CODE nn-x current setting Touchpad Options-GlobalDefault = noneTouchpad Options-Partition 1-2Default = on Touchpad Options-Partition 1-2Default = onBack In Service Touchpad Options-Partition 1-2Default = offTouchpad Options-Partition 1-2Default = off Reporting-GlobalDefault = offLow CPU Battery Battery RestoralTwo Trip Error Reporting-GlobalDefault = onReporting-GlobalDefault = off Reporting-GlobalDefault = offReporting-GlobalDefault = off Reporting-GlobalDefault = weeklyReporting-GlobalDefault = Reporting-GlobalDefault = offReporting-Partition 1-2Default = off Reporting-Partition 1-2Default = offReporting-Partition 1-2Default = off Reporting-Partition 1-2Default = offReporting-Partition 1-2Default = off Reporting-Partition 1-2Default = offFreeze Alarm partition 1: 06107, partition 2: Alarm Verify partition 1: 06108, partition 2:Disable Trouble Beeps Reporting-Partition 1-2Default = offSiren Options-GlobalDefault = off Siren Options-GlobalDefault =Siren Options-GlobalDefault = off Siren Options-Partition1 Default = offLearn Sensors Table 7: How to Trip SensorsSensors Default = none Sensors Default = none Sensors Default = noneSensors Default = none Sensor TextAccess Timeout Audio Verification-Partition1 Default = offAudio Verification-Partition1 Default = Audio Verification-Partition1 Default = offAccess Code Accessory Modules MenuAudio Verification-Partition1 Default = 02 sec This setting determines how long AVM accessDevice ID Partition AssignOutput Programming Status BeepsKey Beeps Freeze TempTemperature Cellular SystemAcc. Modules--SnapCards-OutputText Default = none Output Text output 1: 10110, output 2:output 3 10112, output Onboard Options MenuTwo Wire Smoke Onboard Options-InputsDefault = offrent setting Onboard Options-InputsDefault = offOnboard Options-Output Text-Output1, 2 Default Exiting Programming ModeEntering User Programming Mode Output Text Output 1-1120,OutputTime and Date Default = 00:00 Time and Date Default = 01/01/00User Codes-Reg.User Codes-UserNNN Default = none TimeDirect Bypassing 030nnn1 where nnn=user number Remote Access 030nnn2 where nnn=user numberPartition Jump 030nnn3 where nnn=user number System Tests 030nnn4 where nnn=user numberLatchkey Report 030nnn5 where nnn=user number User Codes-PartitionMaster Code Default = noneUser Codes-SystemMaster Code Default = Options Default = onVolume Set Up Schedules MenuOptions Default = Options Default =Set Up Schedules 05XXY, where Default = 00:00Attach Schedules To Events Default = off XX=schedule 00 thru 15 and3.Press A or B until the desired light appears Attach Schedules To Events Default = off Energy Saver Default = 50FEnergy Saver Default = 90F Attach Lights To Sensors Default =Basic System Commands Default = N/ATable 9: Basic Touchpad Commands Downloader ProgrammingTable 9 Basic Touchpad Commands Continued Testing Zones/SensorsIf a Wireless Sensor Does Not Test Testing Phone Communication Testing Central Station/Pager CommunicationTable 10: Pager System Event Codes Table 11: Pager Sensor/Zone Code and NumbersTesting Outputs and Sirens Testing Light ControlTesting the Energy Saver Module ESM Table 12: System Alarm SoundsAdjusting Touchpad Display Contrast Testing Cellular Backup Communication Table 13: Current Phone Settings2.Check for proper panel and transformer wiring System indicates Sensor/Touchpad nn low battery Central station/pager is not receiving reportsSystem doesn’t go into alarm when zone is tripped Smoke sensor beeps once every 44 seconds Cellular backup report does not occur Module doesn’t communicate with alarm.com Table A1: Wireless Devices Appendix A System Planning WorksheetsTable A2: Hardwire Devices Table A3: Zone and Sensor AssignmentsTable A3: Zone and Sensor Assignments Continued Table A3 Zone and Sensor Assignments Continued Concord UltraTable A4 System Settings Index and Record Setting reference defaultSetting Shortcut NoException Reports phones Off Phone Test On Appendix B Reference Tables Table B1: Sensor Group Characteristics Continued Cross-ZoningTable B2: Item Numbers and Sensor Text Table B3: System Event Trigger Numbers Table B4: Sensor Group Event Trigger NumbersSystem Event DescriptionTable B4 Sensor Group Event Trigger Numbers Table B5: Sensor Number Event Trigger NumbersSensor Group Trigger NoTable B5: Sensor Number Event Trigger Numbers SensorTable B6: System Feature Event Trigger Numbers Table B5: Sensor Number Event Trigger NumbersTable B6: System Feature Event Trigger Numbers Table B7: Response CharacteristicsFeature Response CharacteristicsNotes for Table B8: Response Numbers Concord Ultra#* # * # To Enter Programming Mode: 8 + Installer orConcord Ultra Dealer Code + 0 +Tier 2 Menus Continued #* # * # * # * # * #Concord Ultra #* # Timers#* # * # Concord UltraConcord Ultra #* # Concord UltraSIA False Alarm Software VersionDownloader Code Central Station ReportsExit Delay Dialer Abort DelayDisarming DownloaderConcord Ultra Optional SuperBus 2000 Module Connections