GE 60-960-95 Connecting Detection Devices to Panel Zone Inputs, Connecting 2-WireSmoke Detectors

Page 16
Connecting Detection Devices to Panel Zone Inputs

Note

The panel comes with fac- tory programmed onboard hardwire zones. Install

2k-ohm, end of line (EOL) resistors on all unused fac- tory programmed onboard hardwire zones. If you don’t want to install EOL resistors, delete any unused zones from memory. See Table 8 for onboard hardwire zone factory programming.

Connecting Detection Devices to Panel Zone Inputs

Zone inputs 1 through 8 are supervised using included 2k-ohm, end-of-line resistors at the last device on each circuit. All eight zones accept either normally open (N/O) or normally closed (N/ C) detection devices.

Connecting Intrusion Detection Devices

The graphics in Figure 7 show the typical wiring for N/C and N/O door/window intrusion detec- tion and for a Detection Systems model DS922 (part no. 13-082) motion detector. The minimum available panel voltage for hardwired PIR motion detectors is 8.5 VDC (9.5 VDC for UL listed installations).

Note

When using 2-wire smoke detectors on zone 8, the Two-Wire Smoke setting (in program mode) must be turned on before entering the LEARN SENSORS menu. See ONBOARD OPTIONSINPUTSin the section “Programming the Panel” for complete details.

Panel Terminals

+12

Zone

Zone 2 GND Zone 3

BUS

GND 7

 

 

Panel

 

 

4

Terminals

20

21

 

 

 

Normally

 

Motion

Closed

 

Detector

(N/C)

Normally Open

 

Contacts

(N/O) Contacts in

 

In Series

Parallel

 

 

2k Ohm EOL

 

 

Resistor 49-454

-+LP LN

 

 

 

2k Ohm EOL

 

 

Resistor 49-454

2k Ohm EOL Resistor 49-454

 

 

(Locate at Sensor)

Figure 7. Wiring Intrusion Detection

Connecting 2-Wire Smoke Detectors

Zone input 8 can be set up (in program mode) to accept the following 12 VDC, 2-wire smoke detectors:

System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400, 2400TH

ESL models 429AT, 521B, 521BXT—(models 521B and 521BXT require the following dip switch settings: 1-on, 2-off)

!Use only the 2-wire smoke detector models described above. Alarm signals from other detectors may not be processed correctly if the panel has lost AC power and is operat- ing only from the backup battery.

Caution

When set up for 2-wire smoke detectors, zone 8 can handle up to 10 smoke detectors with

120 uA maximum idle current per detector. Maximum total loop current allowed in an alarm con- dition is 100 mA. Connect one or more, 2-wire smoke detectors to the panel as shown in Figure 8.

11

Concord Ultra

Image 16
Contents Installation Instructions Concord Ultra6HFXULW\ 466-2061Rev CNotices FCC Part 15 Information to the UserFCC Part 15 Class B ACTA PartContents Planning the InstallationInstalling the System About This ManualTesting the System Programming the PanelTroubleshooting Special Installation Requirements UL Listed InstallationsTesting DefaultRequired Setting SIA System RequirementsPlanning the Installation UL Canada Listed InstallationsCentral Station Reporting FunctionSupervised Wireless Siren Standard PanelSuperBus 2000 Touchpads SnapCardsSuperBus 2000 Cellular Backup Module SuperBus 2000 Wireless Gateway ModuleSuperBus 2000 8Z Input Module HIM SuperBus 2000 4-RelayOutput Module HOMTotal System Power and Wire Length Guidelines PowerWire Length Determine the Panel LocationTable 2: Total System Wire Length Allowed Max. Wire LengthWire Type Total System WireMounting the Panel Table 4: Wire RequirementsTable 3: Minimum Device Current Draw Installing Antennas Identify Panel ComponentsConnecting the Panel to Earth Ground Installing Optional SnapCardsFigure 4. Installing the Antennas Figure 5. Connecting the Panel to Earth GroundConnecting Intrusion Detection Devices Connecting Detection Devices to Panel Zone InputsConnecting 2-WireSmoke Detectors Connecting Speakers Connecting 4-WireSmoke DetectorsTable 5 Panel Minimum Available Power 15-WattSpeakerConnecting Piezo Sirens Hardwire Interior SpeakerExterior Sirens Installing Supervised Wireless SirensInterior Sirens 1.Power up the panel see “Powering Up the Panel” Installing SuperBus 2000 Modules SuperBus 2000 Phone Interface/Voice ModuleWiring-Speaker SuperBus 2000 Energy Saver ModuleSuperBus 2000 Cellular Backup Module SuperBus 2000 Automation ModuleSuperBus 2000 8Z Input Module SuperBus 2000 4-RelayOutput ModuleSuperBus 2000 Wireless Gateway Module Setting Device Address on SuperBus 2000 DevicesInstalling an RJ-31XPhone Jack Figure 21. Connecting the SuperBus to the PanelConnecting the AC Power Transformer Powering Up the Panel Programmingthe Panel Entering Program ModeTouchpad Button Programming Functions Moving Through Program Mode Tiers and MenusTable 6: Touchpad Button Functions Figure 26. Tier 1 Program MenusProgramming Tier 1 Menu Items Using Shortcut Numbers Installer CodeSecurity-GlobalDefault = Security-GlobalDefault =Access Code Lock SIA False Alarm ReductionSecurity-GlobalDefault = none Security-GlobalDefault = onSecurity-Partition 1-2Default = on Security-Partition 1-2Default = onSecurity-Partition 1-2Default = on Quick Exit partition 1: 0012, partition 2:Keyswitch Sensor partition 1: 0015, partition 2: Keyswitch Style partition 1: 0016, partition 2:Security-Partition 1-2Default = none Security-Partition 1-2Default = transitionPhones-CSPhone 1-3Defaults: CS RPTS OFF/ON current setting, pressPhones-CSPhone 1-3Defaults: CS RPTS OFF/ON current setting, pressphone 3: phone 3:Phones-CSPhone 1-3Defaults: CS Phones-PagerPhone 1-5Default = nonePhones-PagerPhone 1-5Default = on Phones-PagerPhone 1-5Default = off0153, pager 4: 0163, pager 5: 0154, pager 4: 0164, pager 5:Latchkey Rpts pager 1: 0135, pager 2: 0145, pager 0155, pager 4: 0165, pager 5:Auto Test Reset Phones-DownloaderPhone Default = nonePhone Options-GlobalDefault = on Phone Options-GlobalDefault = offCancel Message Phone Options-GlobalDefault = onPhone Options-GlobalDefault = on Phone Options-GlobalDefault = onCall Wait Cancel Remote Access partition 1: 0211, parPhone Options-GlobalDefault = 15 sec Phone Options-GlobalDefault = nonePhone Options-Partition 1-2Default = on Phone Options-Partition1 only Default = nonePhone Options-Partition 1-2Default = on Phone Options-Partition 1-2Default = offPhone Access Key partition 1: 0216, partition 2: Timers MenuRF Tx Timeout Phone Options-Partition 1-2Default = #Activity Timeout Timers-GlobalDefault = 7 daysTimers-GlobalDefault 4 sec Timers-GlobalDefault = 24 hoursSiren Timeout partition 1: 0313, partition Timers-Partition 1-2Default = 4 minTimers-Partition 1-2Default = 4 min Timers-Partition 1-2Default = 22:00 10:00 pmdisplay shows HOUSE CODE nn-x current setting Touchpad Options-GlobalDefault = noneTouchpad Options-Partition 1-2Default = on Touchpad Options-Partition 1-2Default = onBack In Service Touchpad Options-Partition 1-2Default = offTouchpad Options-Partition 1-2Default = off Reporting-GlobalDefault = offLow CPU Battery Battery RestoralTwo Trip Error Reporting-GlobalDefault = onReporting-GlobalDefault = off Reporting-GlobalDefault = offReporting-GlobalDefault = off Reporting-GlobalDefault = weeklyReporting-GlobalDefault = Reporting-GlobalDefault = offReporting-Partition 1-2Default = off Reporting-Partition 1-2Default = offReporting-Partition 1-2Default = off Reporting-Partition 1-2Default = offReporting-Partition 1-2Default = off Reporting-Partition 1-2Default = offFreeze Alarm partition 1: 06107, partition 2: Alarm Verify partition 1: 06108, partition 2:Disable Trouble Beeps Reporting-Partition 1-2Default = offSiren Options-GlobalDefault = off Siren Options-GlobalDefault =Siren Options-GlobalDefault = off Siren Options-Partition1 Default = offSensors Default = none Table 7: How to Trip SensorsLearn Sensors Sensors Default = none Sensors Default = noneSensors Default = none Sensor TextAccess Timeout Audio Verification-Partition1 Default = offAudio Verification-Partition1 Default = Audio Verification-Partition1 Default = offAccess Code Accessory Modules MenuAudio Verification-Partition1 Default = 02 sec This setting determines how long AVM accessDevice ID Partition AssignOutput Programming Status BeepsKey Beeps Freeze TempTemperature Cellular SystemAcc. Modules--SnapCards-OutputText Default = none Output Text output 1: 10110, output 2:output 3 10112, output Onboard Options MenuTwo Wire Smoke Onboard Options-InputsDefault = offrent setting Onboard Options-InputsDefault = offOnboard Options-Output Text-Output1, 2 Default Exiting Programming ModeEntering User Programming Mode Output Text Output 1-1120,OutputTime and Date Default = 00:00 Time and Date Default = 01/01/00User Codes-Reg.User Codes-UserNNN Default = none TimeDirect Bypassing 030nnn1 where nnn=user number Remote Access 030nnn2 where nnn=user numberPartition Jump 030nnn3 where nnn=user number System Tests 030nnn4 where nnn=user numberLatchkey Report 030nnn5 where nnn=user number User Codes-PartitionMaster Code Default = noneUser Codes-SystemMaster Code Default = Options Default = onVolume Set Up Schedules MenuOptions Default = Options Default =Set Up Schedules 05XXY, where Default = 00:00Attach Schedules To Events Default = off XX=schedule 00 thru 15 and3.Press A or B until the desired light appears Attach Schedules To Events Default = off Energy Saver Default = 50FEnergy Saver Default = 90F Attach Lights To Sensors Default =Basic System Commands Default = N/ATable 9: Basic Touchpad Commands Downloader ProgrammingIf a Wireless Sensor Does Not Test Testing Zones/SensorsTable 9 Basic Touchpad Commands Continued Testing Phone Communication Testing Central Station/Pager CommunicationTable 10: Pager System Event Codes Table 11: Pager Sensor/Zone Code and NumbersTesting Outputs and Sirens Testing Light ControlTesting the Energy Saver Module ESM Table 12: System Alarm SoundsAdjusting Touchpad Display Contrast Testing Cellular Backup Communication Table 13: Current Phone Settings2.Check for proper panel and transformer wiring System indicates Sensor/Touchpad nn low battery Central station/pager is not receiving reportsSystem doesn’t go into alarm when zone is tripped Smoke sensor beeps once every 44 seconds Cellular backup report does not occur Module doesn’t communicate with alarm.com Table A1: Wireless Devices Appendix A System Planning WorksheetsTable A2: Hardwire Devices Table A3: Zone and Sensor AssignmentsTable A3: Zone and Sensor Assignments Continued Table A3 Zone and Sensor Assignments Continued Concord UltraTable A4 System Settings Index and Record Setting reference defaultSetting Shortcut NoException Reports phones Off Phone Test On Appendix B Reference Tables Table B1: Sensor Group Characteristics Continued Cross-ZoningTable B2: Item Numbers and Sensor Text Table B3: System Event Trigger Numbers Table B4: Sensor Group Event Trigger NumbersSystem Event DescriptionTable B4 Sensor Group Event Trigger Numbers Table B5: Sensor Number Event Trigger NumbersSensor Group Trigger NoTable B5: Sensor Number Event Trigger Numbers SensorTable B6: System Feature Event Trigger Numbers Table B5: Sensor Number Event Trigger NumbersTable B6: System Feature Event Trigger Numbers Table B7: Response CharacteristicsFeature Response CharacteristicsNotes for Table B8: Response Numbers Concord Ultra#* # * # To Enter Programming Mode: 8 + Installer orConcord Ultra Dealer Code + 0 +Concord Ultra #* # * # * # * # * #Tier 2 Menus Continued #* # Timers#* # * # Concord UltraConcord Ultra #* # Concord UltraSIA False Alarm Software VersionDownloader Code Central Station ReportsExit Delay Dialer Abort DelayDisarming DownloaderConcord Ultra Optional SuperBus 2000 Module Connections