Epson P)-1, HWDV080DV(N Termination Clearances, Description US Installations1

Page 11

TERMINATION CLEARANCES

 

Description

US Installations1

 

 

A

Clearance above grade, veranda, porch, deck, or balcony

12 inches (305 mm)

 

 

B

Clearance to window or door that may be open

6 inches (152 mm)

for

appliance ≤ 10,000 Btuh (3 kW), 9 inches

 

 

(229 mm) for appliances > 10,000 Btuh (3 kW) and ≤ 50,000 Btuh

 

 

(15 kW), 12 inches (305 mm) for appliances > 50,000 Btuh (15 kW)

C

Clearance to permanently closed window

*

 

 

D

Vertical clearance to ventilated soffit located above the

*

 

 

 

terminal within a horizontal distance of 2 feet (610 mm)

 

 

 

 

from the center line of the terminal

 

 

 

E

Clearance to unventilated soffit

*

 

 

F

Clearance to outside corner

24"

 

 

G

Clearance to inside corner

24"

 

 

H

Clearance to each side of center line extended above me-

*

 

 

 

ter/regulator assembly

 

 

 

I

Clearance to service regulator vent outlet

*

 

 

J

Clearance to non-mechanical air supply inlet to building

6 inches (152 mm)

for

appliance ≤ 10,000 Btuh (3 kW), 9 inches

 

or the combustion air inlet to any other appliance.

(229 mm) for appliances > 10,000 Btuh (3 kW) and ≤ 50,000 Btuh

 

 

(15 kW), 12 inches (305 mm) for appliances > 50,000 Btuh (15 kW)

K

Clearance to a mechanical air supply inlet

3 feet (914 mm) above if within 10 feet (3.04 m) horizontally

L

Clearance above paved sidewalk or paved driveway lo-

*

 

 

 

cated on public property

 

 

 

M

Clearance under veranda, porch, deck, or balcony.

*

 

 

The minimum distance from the center of the outside vent to the nearest inside and outside corner or obstruction or overhang is 24" (457 mm).

1In accordance with current ANSI Z223.1/NFPA 54, National Fuel Gas Code

*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, one of the following shall be indicated:

a)A minimum clearance value determined by testing in accordance with section 2.19.6, or;

b)A reference to the following footnote:

“Clearance in accordance with local installation codes and the requirements of the gas supplier.”

24632-0-0508

Page 11

Image 11
Contents Installation Table of Contents Included in the BOX Tools Needed Hardware PacketsHigh Altitude Specifications GAS SpecificationsSpecifications Unit Dimensions Follow State and Local codes for installation Important Safety InformationLP-GAS Warning Odor Safety Information for Users of LP-GASIntroduction Instructions to InstallerDIRECTLYBELOW. Keepclear OFALLOBSTRUC- Tions Requirements for MassachusettsTermination Clearances Description US Installations1Locating Gas Supply GAS SupplyClearances GAS SupplyLocation All Models Installation Instructions OverviewInstallation Overview Installation and AssemblyClearances to Combustibles Mounting Template for HWDV080BDV HWDV181BDV Pilot Hole Interior Installation of the Front of the Unit Cutting the Vent Tubes Marker Flue Outlet Tube Collar Exterior Installation of the Venting DIA. Vent CAP Collar Furnace Cement Screws Reassembly and Resealing VENT-AIR Intake System DIA. Vent CAP Collar Furnace Cement Screws Installation of Optional Blower KIT HW125SCB Installation of Optional Blower KIT HW125SCB Installation of Optional Blower KIT HW125SCB Pull blower cord from bottom to remove any excess wire from Before Operating Appliance Before Operating Appliance Before Operating Appliance What to do if YOU Smell GAS What to do if YOU Smell GAS Operating InstructionsTo Turn OFF GAS to Appliance Lighting InstructionsMain Burner Flame Characteristics Pilot Flame CharacteristicsOperation Frequency Faults to be Remarks Prevented Maintenance InstructionsProblem Causes Solution TroubleshootingHOW to Order Repair Parts Index no Description HWDV080 HWDV181 Parts ListBulb Clip Parts View Service Notes Service Notes Service Notes Freeburg Ave. Belleville, IL 62220 PH877-459-1583 FAX