GAS SUPPLY
Locating Gas Supply
The gas line can enter the unit either through the floor or outside wall. The gas line opening should be made at this time. Location of the opening will be determined by the position of floor joists and the valve and union used for servicing.
Recommended Gas Pipe Diameter
Pipe Length | Schedule 40 Pipe | Tubing, Type L | ||
| Inside Diameter | Outside Diameter | ||
| Nat. | L.P. | Nat. | L.P. |
1/2” | 3/8” | 1/2” | 3/8” | |
12.7 mm | 9.5 mm | 12.7 mm | 9.5 mm | |
1/2” | 1/2” | 5/8” | 1/2” | |
12.7 mm | 12.7 mm | 15.9 mm | 12.7 mm | |
1/2” | 1/2” | 3/4” | 1/2” | |
12.7 mm | 12.7 mm | 19 mm | 12.7 mm | |
3/4” | 1/2” | 7/8” | 3/4” | |
19 mm | 12.7 mm | 22.2 mm | 19 mm |
Note: Never use plastic pipe. Check to confirm whether your local codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
—ANS Z21.24ApplianceConnectors of Corrugated MetalTubing and Fittings
—ANS Z21.45 Assembled Flexible Appliance Connectors of Other Than
The above connectors may be used if acceptable by the authority having jurisdiction. The state of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length.
Figure 1
Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.
Never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing. It is required by the National Fuel Gas Code that a drip line be installed near the gas inlet. This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect.
FLEXIBLE GAS LINE CONNECTION
GAS SUPPLY |
| NPT NIPPLE | REGULATOR | |
TEE HANDLE | ||||
|
| |||
| FLEX TUBE |
|
FLARE SHUT OFF VALVE | FLARE FITTING | VALVE |
RIGID GAS LINE CONNECTION
CLOSE NIPPLE | 3/8 NIPPLE |
TEE HANDLE | REGULATOR |
|
SHUT OFF VALVE
VALVE
NPT GAS SUPPLY | NPT UNION |
Method of Installing a Tee Fitting Sediment Trap
Figure 2
Page 12 |