Epson P)-1, HWDV080DV(N installation instructions GAS Supply, Clearances

Page 13

GAS SUPPLY (continued)

Pressure Testing of the Gas Supply System

1.To check the inlet pressure to the gas valve, a 1/8" (3 mm) N.P.T. plugged tapping, accessible for test gauge connection, must be placed immediately upstream of the gas supply connection to the appliance.

2.The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).

3.The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

Attention! If one of the above procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will result in a hazardous condition.

Checking Manifold Pressure

Both Propane and Natural have a pressure regulator attached to the gas valve. Natural gas models will have a manifold pressure of approximately 4.0" w.c. (.996 kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 5.0" w.c. (1.245 kPa) for the purpose of input adjustment to a maximum of 10.5" w.c. (2.61 kPa). Propane gas models will have a manifold pressure approximately 10.0" w.c. (2.49 kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 11.0" w.c. (2.739 kPa) for the purpose of input adjustment to a maximum of 13.0" w.c. (3.237 kPa).

A 1/8" (3 mm) N.P.T. plugged tapping, accessible for test gauge connection, is located on the side of the gas pressure regulator.

CLEARANCES

1.In selecting a location for installation, it is necessary to provide adequate accessibility clearances for servicing and proper installation.

2.Unit is supported by a wall bracket secured to the wall.

3.Theminimumclearancesfromcasingtocombustibleconstruction is 36" (914.4 mm) on top, 6" (152 mm) on each side and 4" (102 mm) from the floor or from the top surface of carpeting, tile or other floor covering and 0" (0 mm) to rear wall.

4.The minimum distance from the center of the vent cap to the nearest outside corner or obstruction is 24" (610 mm).

5. The minimum wall depth is 4 1/2" (114.3 mm) and the maximum is 12" (304.8 mm). The use of tubes not supplied by the manufacturer results in unsatisfactory performance.

The vent terminal of a direct vent appliance, with an input of 50,000 (14.6 KW) BTU per hour or less shall be located at least 9" (229 mm) from any opening through which flue gases could enter a building. The bottom of the vent terminal and the air intake shall be located at least 12" (305 mm) above grade.

The vent terminal of a direct vent appliance, with an input of 10,000 Btu per hour (3 kW) or less shall be located at least 6" (150 mm) from any air opening into a building, and such an ap- pliance with an input over 10,000 Btu per hour (3 kW) but not over 50,000 Btu per hour (14.7 kW) shall be installed with a 9" (229 mm) vent terminal clearance and the bottom of the vent ter- minal and the air intake shall be located at least 12" (305 mm) above grade.

WARNING: The nearest point of the vent cap should be a minimum horizontal distance of six (6) (1.83m) feet from any pressure regulator. In case of regulator malfunction, the six (6) foot (1.83m) distance will reduce the chance of gas entering the vent cap.

24632-0-0508

Page 13

Image 13
Contents Installation Table of Contents Included in the BOX Tools Needed Hardware PacketsSpecifications GAS SpecificationsHigh Altitude Specifications Unit Dimensions Follow State and Local codes for installation Important Safety InformationLP-GAS Warning Odor Safety Information for Users of LP-GASIntroduction Instructions to InstallerDIRECTLYBELOW. Keepclear OFALLOBSTRUC- Tions Requirements for MassachusettsTermination Clearances Description US Installations1Locating Gas Supply GAS SupplyClearances GAS SupplyLocation All Models Installation Instructions OverviewInstallation Overview Installation and AssemblyClearances to Combustibles Mounting Template for HWDV080BDV HWDV181BDV Pilot Hole Interior Installation of the Front of the Unit Cutting the Vent Tubes Marker Flue Outlet Tube Collar Exterior Installation of the Venting DIA. Vent CAP Collar Furnace Cement Screws Reassembly and Resealing VENT-AIR Intake System DIA. Vent CAP Collar Furnace Cement Screws Installation of Optional Blower KIT HW125SCB Installation of Optional Blower KIT HW125SCB Installation of Optional Blower KIT HW125SCB Pull blower cord from bottom to remove any excess wire from Before Operating Appliance Before Operating Appliance Before Operating Appliance What to do if YOU Smell GAS What to do if YOU Smell GAS Operating InstructionsTo Turn OFF GAS to Appliance Lighting InstructionsMain Burner Flame Characteristics Pilot Flame CharacteristicsOperation Frequency Faults to be Remarks Prevented Maintenance InstructionsHOW to Order Repair Parts TroubleshootingProblem Causes Solution Index no Description HWDV080 HWDV181 Parts ListBulb Clip Parts View Service Notes Service Notes Service Notes Freeburg Ave. Belleville, IL 62220 PH877-459-1583 FAX