Bryant 355CAV installation instructions

Page 5

Install this furnace only in a location and position as specified in LOCATION and INSTALLATION sections of these instructions.

Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the Combustion Air and Vent piping sections of these instructions.

Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for detection of leaks to check all connections as specified in the GAS PIPING section of these instructions.

Always install the furnace to operate within the furnace’s intended rise range with a duct system which has an external static pressure within the allowable range as specified in the SET TEMPERATURE RISE section of these instructions.

When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by ducts sealed to the furnace casing and terminating outside the space containing the furnace.

A gas-fired furnace for installation in a residential garage must be installed as specified in the Hazardous Locations section of these instructions and Fig. 5.

The furnace may be used for construction heat provided that the furnace installation and operation complies with the first CAUTION in the LOCATION section of these instructions.

This gas furnace may be used for construction heat provided that:

SThe furnace is permanently installed with all electrical wiring, piping, air filters, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and ter- minated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.

SThe furnace is controlled by a thermostat. It may not be “hot wired” to provide heat continuously to the struc- ture without thermostatic control.

SClean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the en- trainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.

SThe temperature of the return air to the furnace is main- tained between 55_F (13_C) and 80_F (27_C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instruc- tions.

SThe air temperature rise is within the rated rise range on the furnace rating plate, and the firing rate has been set to the nameplate value.

SThe filters used to clean the circulating air during the construction process must be either changed or thor- oughly cleaned prior to occupancy.

SThe furnace, ductwork and filters are cleaned as neces- sary to remove drywall dust and construction debris from all HVAC system components after construction is completed.

SAfter construction is complete, verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s in- structions.

If this furnace is installed with a direct-vent (combustion air and flue) system, a factory accessory termination kit must be installed. In a direct-vent system, all air for combustion is taken directly from the outside atmosphere and all flue products are discharged to the outside atmosphere. See furnace and factory accessory termination kit instructions for proper installation.

These furnaces are shipped with the following materials to assist in proper furnace installation. These materials are shipped in the main blower compartment.

Installer Packet Includes:

 

Installation, Start--- up, and Operating Instructions

 

Service and Maintenance Instructions

 

User’s Information Manual

 

Warranty Certificate

 

Loose Parts Bag includes:

Quantity

Collector Box or Condensate trap extension tube

1

Inducer housing drain tube

1

1/2--- in CPVC street elbow

2

Drain tube coupling

1

Drain tube coupling grommet

1

Gas line grommet

1

Vent pipe grommet

1

Combustion--- air pipe grommet

1

Gas line entry hole filler plug

1

Power entry hole filler plug

2

Condensate trap hole filler plug

3

Vent and combustion--- air intake hole filler plug

2

Combustion--- air pipe perforated disk assembly

1

 

 

355CAV

5

Image 5
Contents Installation Instructions Required Notice for Massachusetts Installations Safety Considerations Table of ContentsEnvironmental Hazard Dimensions In. / mm355CAV Clearances to Combustibles Codes and Standards Electrostatic Discharge ESD PrecautionsIntroduction Unit Damage HazardProperty Damage Hazard ApplicationsUpflow Application Condensate Trap Tubing Alternate Upflow Orientation Condensate Trap Alternate Upflow OrientationCarbon Monoxide Poisoning Hazard Condensate Trap Freeze Protection Upper Inducer Housing Drain ConnectionCondensate Trap Field Drain Attachment Condensate Trap Location Downflow ApplicationsHorizontal Left SUPPLY-AIR Discharge Applications Horizontal Left Tube ConfigurationCombustion AIR Intake Vent Unit Operation Hazard Property DamageConstruct a Working Platform Condenste Trap Field Drain Attachment Horizontal Right SUPPLY-AIR Discharge ApplicationsLocation Prohibit Installation on BackFIRE, EXPLOSION, Injury or Death Hazard Fire or Death HazardHazardous Locations Installation in Upflow or Downflow Applications InstallationInstallation in Horizontal Applications Leveling Legs If DesiredFurnace, Plenum, and Subbase Installed on a Angle AIR Ducts Unit MAY not Operate Fire HazardFIRE, Carbon Monoxide and Poisoning Hazard Fire or Explosion Hazard Gas PipingRemoving Bottom Closure Panel Electrical Shock Hazard WiringElectrical Shock and Fire Hazard Disconnect Switch and FurnaceRemoval of Existing Furnaces from Common Vent Systems AccessoriesFire or Electrical Shock Hazard Fire and Explosion Hazard AIR for Combustion and VentilationPipe Fittings Cement Description Marked on Primers Combustion-Air and Vent Pipe DiameterFurnace Control Direct Vent Termination Clearance Ventilated Combustion Air Vent Termination Clearance Vent Pipe Termination for Ventilated Combustion Air System Unit Corrosion Hazard Combustion AIR PipeCombustion Air Termination Ventilated Combustion Air Option Attachment of Combustion Air Intake Housing Plug FittingCombustion Air Termination-Direct Vent / 2-Pipe System Vent PipeCarbon Monoxide Poisoning Property Damage Hazard Attachment of Vent Pipe304.8mm minimum 76.2mm minimum Extended Exposed Sidewall Pipes Vent TerminationVent Termination Kit Direct Vent / 2-Pipe System Only Two-Pipe Termination Kit Direct Vent / 2-Pipe System OnlyWinter Design Number of 90 Elbows Btuh Maximum Allowable Pipe Length Ft MDirect Vent 2-Pipe Only Multi-venting and Vent Terminations Condensate DrainApplication Personal Injury HazardAir Conditioning A/C Setup Switches START-UP, Adjustment and Safety CheckContinuous Fan CF Setup Switches Additional Setup Switches SW4Prime Condensate Trap with Water Example of Setup Switch in Off PositionWiring Diagram Furnace Setup Switch Description Inducer Housing Drain TubePurge Gas Lines Sequence of OperationTwo-Stage Thermostat and Two-Stage Medium/High Heating Two-Stage Thermostat and Two-Stage Low / High HeatingThermidistat Mode Continuous Blower Mode Super Dehumidify ModeContinuous Blower Speed Selection from Thermostat Heat PumpStep-Modulating Furnace with Single-Speed Air Conditioning Furnace and Two-Speed Heat Pump Pump Furnace and Two-Speed Air ConditionerRedundant Automatic Gas Valve Set Gas Input RateBurner Orifice Altitude AVG. GAS 675 Burner Flame Altitude Derate Multiplier for USASet Thermostat Heat Anticipator Set Temperature RiseGas Rate cu Ft/Hr Check Safety Controls ChecklistCheck Pressure Switches Check Primary Limit ControlCombustion and Vent Piping Checklist InstallationCatalog No. II355CAV---060---4
Related manuals
Manual 60 pages 10.1 Kb Manual 14 pages 23.93 Kb

355CAV specifications

The Bryant 355CAV is a state-of-the-art automated vertical machining center designed to enhance precision and efficiency in the manufacturing sector. Renowned for its robust construction, this machine is engineered to handle a broad spectrum of machining tasks, making it suitable for both small and large-scale production environments.

One of the standout features of the Bryant 355CAV is its advanced CNC control system, which provides users with exceptional ease of use. The intuitive user interface allows operators to program complex machining operations with minimal effort, significantly reducing setup times. The machine's high-speed spindle achieves impressive rotational speeds, which allows for quick material removal, ultimately optimizing productivity and throughput.

The Bryant 355CAV exhibits superior rigidity and stability due to its solid cast iron frame and carefully designed structural components. This construction minimizes vibrations during machining, ensuring that even the most intricate parts are produced with high accuracy. The machine's precision ground linear guideways further enhance its performance by providing smooth motion and high load capacity.

Equipped with a large work envelope, the Bryant 355CAV enables manufacturers to accommodate various part sizes and geometries. Additionally, its automatic tool changers can hold a variety of tools, thus facilitating quick transitions between different machining operations without requiring manual intervention. This flexibility is essential for meeting the diverse needs of modern manufacturing.

Another notable characteristic of the Bryant 355CAV is its energy-efficient design. It integrates modern technologies aimed at reducing power consumption while maintaining optimum performance. This environmentally conscious approach not only cuts operational costs but also aligns with the growing demand for sustainable manufacturing practices.

Moreover, the Bryant 355CAV features advanced monitoring capabilities, allowing operators to track machine performance in real time. Data analytics from these systems can be utilized to improve operational efficiency, reduce downtime, and enhance predictive maintenance protocols.

In summary, the Bryant 355CAV is a versatile, high-performance machining center that showcases cutting-edge features and technologies. Its combination of user-friendly controls, sturdy construction, energy efficiency, and advanced monitoring positions it as a vital asset for manufacturers aiming to elevate their productivity and precision in an increasingly competitive landscape.