Bryant 355CAV Property Damage, Construct a Working Platform, Unit Operation Hazard

Page 14

355CAV

!CAUTION

PROPERTY DAMAGE

Failure to follow this caution may result in property damage.

Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.

NOTE: In Canada, installations shall be in accordance with current NSCNGPIC and/or local codes.

Condensate Trap Location

The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 11.

To relocate condensate trap from the blower shelf to desired location, perform the following:

1.Remove three tubes connected to condensate trap.

2.Remove trap from blower shelf by gently pushing tabs in- ward and rotating trap.

3.Remove casing hole filler cap from casing hole. (See Fig. 2 or 11.)

4.Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.

!WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or death.

Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.

5.Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.

6.Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).

Condensate Trap Tubing

NOTE: See Fig. 11 or tube routing label on main furnace door to check for proper connections.

1.Collector Box Drain Tube

a.Install drain tube coupling (factory-supplied in loose parts bag) into collector box drain tube (blue label) which was previously connected to condensate trap.

b.Connect large diameter drain tube and clamp (factory- supplied in loose parts bag) to drain tube coupling, ex- tending collector box drain tube.

c.Route extended tube (blue label) to condensate trap and cut to appropriate length.

d.Clamp tube to prevent any condensate leakage.

2.Inducer Housing Drain Tube

(a.)Remove and discard LOWER (molded) inducer housing drain tube which was previously con- nected to condensate trap.

(b.)Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to

connect LOWER inducer housing drain connec- tion to condensate trap.

(c.)Determine appropriate length, cut and connect tube.

(d.)Clamp tube to prevent any condensate leakage.

3.Relief Port Tube

a.Extend collector box tube (green label) which was previ- ously connected to condensate trap by splicing to small diameter tube (factory-supplied in loose parts bag).

b.Route extended collector box pressure tube to relief port connection on condensate trap.

c.Determine appropriate length, cut, and connect tube.

d.Clamp tube to prevent any condensate leakage.

Condensate Trap Field Drain Attachment

Refer to Condensate Drain section for recommendations and procedures.

Pressure Switch Tubing

The LOWER collector box pressure tube (pink label) is factory connected to the High Pressure Switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected, extended rerouted, and then reconnected to the pressure switch in HORIZONTAL LEFT applications for 060 and 080 heating input furnaces.

NOTE: See Fig. 11 or tube routing label on main furnace door to check for proper connections.

Modify tube as described below.

1.Disconnect collector box pressure tube (pink label) at- tached to High Pressure Switch.

2.Use smaller diameter tube (factory-supplied in loose parts bag) to extend tube disconnected in Item 1.

3.Route extended tube:

a.Behind inducer housing.

b.Between blower shelf and inducer housing.

4.Determine appropriate length, cut, and reconnect tube to High Pressure Switch connections labeled COLLECTOR BOX.

Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommendations and procedures.

Construct a Working Platform

Construct working platform where all required furnace clearances are met. (See Fig. 3 and 12 or 13.)

!CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in intermittent unit operation.

The condensate trap MUST be installed below furnace. See Fig. 6 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.

NOTE: A 12-in. (305 mm) minimum offset pipe section is recommended with short (5 to 8 ft. or 1.5M to 2.4M) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 12, 13, or 44.)

14

Image 14
Contents Installation Instructions Required Notice for Massachusetts Installations Table of Contents Safety ConsiderationsDimensions In. / mm Environmental Hazard355CAV Clearances to Combustibles Introduction Electrostatic Discharge ESD PrecautionsCodes and Standards Unit Damage HazardProperty Damage Hazard ApplicationsUpflow Application Condensate Trap Tubing Alternate Upflow Orientation Condensate Trap Alternate Upflow OrientationCarbon Monoxide Poisoning Hazard Condensate Trap Freeze Protection Upper Inducer Housing Drain ConnectionCondensate Trap Field Drain Attachment Downflow Applications Condensate Trap LocationHorizontal Left Tube Configuration Horizontal Left SUPPLY-AIR Discharge ApplicationsCombustion AIR Intake Vent Unit Operation Hazard Property DamageConstruct a Working Platform Horizontal Right SUPPLY-AIR Discharge Applications Condenste Trap Field Drain AttachmentProhibit Installation on Back LocationFIRE, EXPLOSION, Injury or Death Hazard Fire or Death HazardHazardous Locations Installation in Horizontal Applications InstallationInstallation in Upflow or Downflow Applications Leveling Legs If DesiredFurnace, Plenum, and Subbase Installed on a Angle AIR Ducts Unit MAY not Operate Fire HazardFIRE, Carbon Monoxide and Poisoning Hazard Gas Piping Fire or Explosion HazardRemoving Bottom Closure Panel Wiring Electrical Shock HazardDisconnect Switch and Furnace Electrical Shock and Fire HazardRemoval of Existing Furnaces from Common Vent Systems AccessoriesFire or Electrical Shock Hazard AIR for Combustion and Ventilation Fire and Explosion HazardCombustion-Air and Vent Pipe Diameter Pipe Fittings Cement Description Marked on PrimersFurnace Control Direct Vent Termination Clearance Ventilated Combustion Air Vent Termination Clearance Vent Pipe Termination for Ventilated Combustion Air System Combustion AIR Pipe Unit Corrosion HazardAttachment of Combustion Air Intake Housing Plug Fitting Combustion Air Termination Ventilated Combustion Air OptionCarbon Monoxide Poisoning Property Damage Hazard Vent PipeCombustion Air Termination-Direct Vent / 2-Pipe System Attachment of Vent Pipe304.8mm minimum 76.2mm minimum Vent Termination Kit Direct Vent / 2-Pipe System Only Vent TerminationExtended Exposed Sidewall Pipes Two-Pipe Termination Kit Direct Vent / 2-Pipe System OnlyWinter Design Maximum Allowable Pipe Length Ft M Number of 90 Elbows BtuhDirect Vent 2-Pipe Only Application Condensate DrainMulti-venting and Vent Terminations Personal Injury HazardContinuous Fan CF Setup Switches START-UP, Adjustment and Safety CheckAir Conditioning A/C Setup Switches Additional Setup Switches SW4Example of Setup Switch in Off Position Prime Condensate Trap with WaterWiring Diagram Inducer Housing Drain Tube Furnace Setup Switch DescriptionSequence of Operation Purge Gas LinesTwo-Stage Thermostat and Two-Stage Low / High Heating Two-Stage Thermostat and Two-Stage Medium/High HeatingThermidistat Mode Continuous Blower Speed Selection from Thermostat Super Dehumidify ModeContinuous Blower Mode Heat PumpStep-Modulating Furnace with Single-Speed Air Conditioning Pump Furnace and Two-Speed Air Conditioner Furnace and Two-Speed Heat PumpSet Gas Input Rate Redundant Automatic Gas ValveBurner Orifice Altitude AVG. GAS 675 Altitude Derate Multiplier for USA Burner FlameSet Thermostat Heat Anticipator Set Temperature RiseGas Rate cu Ft/Hr Check Pressure Switches ChecklistCheck Safety Controls Check Primary Limit ControlChecklist Installation Combustion and Vent PipingCatalog No. II355CAV---060---4
Related manuals
Manual 60 pages 10.1 Kb Manual 14 pages 23.93 Kb