Bryant 355CAV Installation, Leveling Legs If Desired, Unit MAY not Operate Hazard

Page 18

355CAV

5/16

(8mm)

(8mm)

5/16

1 3/4(44mm)

1 3/4(44mm)

(8mm)

5/16

(8mm)

5/16

(44mm) 1 3/4(44mm)1 3/4

A89014

Fig. 18 - Leveling Legs

INSTALLATION

Leveling Legs (If Desired)

When furnace is used in upflow position with side inlet(s), leveling legs may be desired. (See Fig. 18.) Install field-supplied, corrosion-resistant 5/16-in. (8 mm) machine bolts and nuts.

NOTE: The maximum length of bolt should not exceed 1-1/2 in. (38 mm).

1.Position furnace on its back. Locate and drill a 5/16-in. (8 mm) diameter hole in each bottom corner of furnace. (See Fig. 18.) Holes in bottom closure panel may be used as guide locations.

2.For each hole, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)

3.Install another nut on other side of furnace base. (Install flat washer if desired.)

4.Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.

NOTE: Bottom closure must be used when leveling legs are used. See Bottom Closure Panel section.

Installation in Upflow or Downflow Applications

NOTE: For downflow applications, this furnace is approved for use on combustible flooring when special base (available from Manufacturer) Part No. KGB is used. Special base is not required when this furnace is installed on Manufacturer’s Cased Coil Assembly or when Manufacturer’s Coil Box is used.

1.Determine application being installed from Table 1.

2.Construct hole in floor per dimensions specified in Table 1 and Fig. 19.

3.Construct plenum to dimensions specified in Table 2 and Fig. 19.

4.If special base (KGASB) is used, install as shown in Fig. 20.

5.If Manufacturer’s Cased Coil Assembly or Manufacturer’s Coil Box is used, install as shown in Fig. 21.

NOTE: Remove furnace perforated discharge duct flanges when they interfere with mating flanges on coil on downflow subbase. To remove furnace perforated discharge duct flange, use hand scanners, wide duct pliers or duct flange tool to bend flange back

and forth until it breaks off. Be careful of sharp edges. (See Fig. 22.)

!CAUTION

UNIT MAY NOT OPERATE HAZARD

Failure to follow this caution may result in intermittent unit operation or performance satisfaction.

Do not bend duct flanges inward as shown in Fig. 22. This will affect airflow across heat exchangers and may cause limit cycling or premature heat exchanger failure. Remove duct flange completely or bend it inward a minimum of 210_F (99_C) as shown in Fig. 22.

Installation in Horizontal Applications

These furnaces can be installed in either horizontal left or right discharge position. In a crawlspace, furnace can either be hung from floor joist or installed on suitable blocks or pad. Furnace can be suspended from each corner by hanger bolts and angle iron supports. (See Fig. 23.) Cut hanger bolts (4 each 3/8-in. all-thread rod) to desired length. Use 1 X 3/8-in. flat washers, 3/8-in. lock washers, and 3/8-in. nuts on hanger rods as shown in Fig. 23. Dimples are provided for hole locations. (See Fig. 2.)

!CAUTION

UNIT MAY NOT OPERATE HAZARD

Failure to follow this caution may result in intermittent unit operation or performance satisfaction.

The entire length of furnace MUST be supported when furnace is used in a horizontal position to ensure proper draining. When suspended, bottom brace supports sides and center blower shelf. When unit is supported from the ground, blocks or pad should support sides and center blower shelf area.

 

A

 

PLENUM

 

OPENING

B

D

 

FLOOR

 

OPENING

 

C

A96283

Fig. 19 - Floor and Plenum Opening Dimensions

18

Image 18
Contents Installation Instructions Required Notice for Massachusetts Installations Table of Contents Safety ConsiderationsDimensions In. / mm Environmental Hazard355CAV Clearances to Combustibles Introduction Electrostatic Discharge ESD PrecautionsCodes and Standards Unit Damage HazardApplications Upflow ApplicationProperty Damage Hazard Condensate Trap Alternate Upflow Orientation Carbon Monoxide Poisoning HazardCondensate Trap Tubing Alternate Upflow Orientation Upper Inducer Housing Drain Connection Condensate Trap Field Drain AttachmentCondensate Trap Freeze Protection Downflow Applications Condensate Trap LocationHorizontal Left Tube Configuration Horizontal Left SUPPLY-AIR Discharge ApplicationsCombustion AIR Intake Vent Property Damage Construct a Working PlatformUnit Operation Hazard Horizontal Right SUPPLY-AIR Discharge Applications Condenste Trap Field Drain AttachmentProhibit Installation on Back LocationFire or Death Hazard Hazardous LocationsFIRE, EXPLOSION, Injury or Death Hazard Installation in Horizontal Applications InstallationInstallation in Upflow or Downflow Applications Leveling Legs If DesiredFurnace, Plenum, and Subbase Installed on a Angle AIR Ducts Fire Hazard FIRE, Carbon Monoxide and Poisoning HazardUnit MAY not Operate Gas Piping Fire or Explosion HazardRemoving Bottom Closure Panel Wiring Electrical Shock HazardDisconnect Switch and Furnace Electrical Shock and Fire HazardAccessories Fire or Electrical Shock HazardRemoval of Existing Furnaces from Common Vent Systems AIR for Combustion and Ventilation Fire and Explosion HazardCombustion-Air and Vent Pipe Diameter Pipe Fittings Cement Description Marked on PrimersFurnace Control Direct Vent Termination Clearance Ventilated Combustion Air Vent Termination Clearance Vent Pipe Termination for Ventilated Combustion Air System Combustion AIR Pipe Unit Corrosion HazardAttachment of Combustion Air Intake Housing Plug Fitting Combustion Air Termination Ventilated Combustion Air OptionCarbon Monoxide Poisoning Property Damage Hazard Vent PipeCombustion Air Termination-Direct Vent / 2-Pipe System Attachment of Vent Pipe304.8mm minimum 76.2mm minimum Vent Termination Kit Direct Vent / 2-Pipe System Only Vent TerminationExtended Exposed Sidewall Pipes Two-Pipe Termination Kit Direct Vent / 2-Pipe System OnlyWinter Design Maximum Allowable Pipe Length Ft M Number of 90 Elbows BtuhDirect Vent 2-Pipe Only Application Condensate DrainMulti-venting and Vent Terminations Personal Injury HazardContinuous Fan CF Setup Switches START-UP, Adjustment and Safety CheckAir Conditioning A/C Setup Switches Additional Setup Switches SW4Example of Setup Switch in Off Position Prime Condensate Trap with WaterWiring Diagram Inducer Housing Drain Tube Furnace Setup Switch DescriptionSequence of Operation Purge Gas LinesTwo-Stage Thermostat and Two-Stage Low / High Heating Two-Stage Thermostat and Two-Stage Medium/High HeatingThermidistat Mode Continuous Blower Speed Selection from Thermostat Super Dehumidify ModeContinuous Blower Mode Heat PumpStep-Modulating Furnace with Single-Speed Air Conditioning Pump Furnace and Two-Speed Air Conditioner Furnace and Two-Speed Heat PumpSet Gas Input Rate Redundant Automatic Gas ValveBurner Orifice Altitude AVG. GAS 675 Altitude Derate Multiplier for USA Burner FlameSet Temperature Rise Gas Rate cu Ft/HrSet Thermostat Heat Anticipator Check Pressure Switches ChecklistCheck Safety Controls Check Primary Limit ControlChecklist Installation Combustion and Vent PipingCatalog No. II355CAV---060---4
Related manuals
Manual 60 pages 10.1 Kb Manual 14 pages 23.93 Kb

355CAV specifications

The Bryant 355CAV is a state-of-the-art automated vertical machining center designed to enhance precision and efficiency in the manufacturing sector. Renowned for its robust construction, this machine is engineered to handle a broad spectrum of machining tasks, making it suitable for both small and large-scale production environments.

One of the standout features of the Bryant 355CAV is its advanced CNC control system, which provides users with exceptional ease of use. The intuitive user interface allows operators to program complex machining operations with minimal effort, significantly reducing setup times. The machine's high-speed spindle achieves impressive rotational speeds, which allows for quick material removal, ultimately optimizing productivity and throughput.

The Bryant 355CAV exhibits superior rigidity and stability due to its solid cast iron frame and carefully designed structural components. This construction minimizes vibrations during machining, ensuring that even the most intricate parts are produced with high accuracy. The machine's precision ground linear guideways further enhance its performance by providing smooth motion and high load capacity.

Equipped with a large work envelope, the Bryant 355CAV enables manufacturers to accommodate various part sizes and geometries. Additionally, its automatic tool changers can hold a variety of tools, thus facilitating quick transitions between different machining operations without requiring manual intervention. This flexibility is essential for meeting the diverse needs of modern manufacturing.

Another notable characteristic of the Bryant 355CAV is its energy-efficient design. It integrates modern technologies aimed at reducing power consumption while maintaining optimum performance. This environmentally conscious approach not only cuts operational costs but also aligns with the growing demand for sustainable manufacturing practices.

Moreover, the Bryant 355CAV features advanced monitoring capabilities, allowing operators to track machine performance in real time. Data analytics from these systems can be utilized to improve operational efficiency, reduce downtime, and enhance predictive maintenance protocols.

In summary, the Bryant 355CAV is a versatile, high-performance machining center that showcases cutting-edge features and technologies. Its combination of user-friendly controls, sturdy construction, energy efficiency, and advanced monitoring positions it as a vital asset for manufacturers aiming to elevate their productivity and precision in an increasingly competitive landscape.